![RenewAire EV450IN Скачать руководство пользователя страница 14](http://html1.mh-extra.com/html/renewaire/ev450in/ev450in_installation-operation-and-maintenance-manual_1440994014.webp)
1.800.627.4499
14
EV-Series Indoor
ERV
INSTALLATION
The EV450IN has integral flanges for mounting to a wall (Figure 5.2.0) or hanging from a ceiling
(Figure 5.2.1).
Please note that the threaded rod, bolts, nuts, or other fasteners are not included. If hanger
bolts or threaded rod are used each must be capable of carrying the weight of the unit and
must be no less than 3/8" diameter.
A vibration isolator kit, 45VIB accessory, is available for hanging the unit and includes 4 rubber
isolation mounts and eight washers. An hanging bracket kit, 45EVHB accessory, is available
for hanging the unit from a ceiling with doors opening horizontally. The 45EVHB kit can also be
used for floor mount legs. With all installations, adequate clearance for the filter access door
latches must be provided.
If doors need to be removed for installation or services see figures 5.2.2 and 5.2.3 show the
rubber door keepers. In order to remove doors these keepers must be removed.
www.renewaire.com (800) 627- 4499
FIGURE 5.2.0 UNIT MOUNTED TO WALL USING INTEGRAL MOUNTING FLANGES