Commissioning
Basic operations
Setting the maximum flow temperature with On/Off-control
P101 = 0
Setting the maximum flow water
temperature with connected outdoor
sensor T4.
(starting with illuminated display):
1. Press the right arrow button:
The display shows: Basic Settings;
2. Press the OK button;
3. Press the right arrow button until
CH temp:
The display shows: CH temp 85°C;
4. Press the + or - button to adjust the
desired flow temperature and press
the OK button.
Setting the maximum flow water
temperature without outdoor sensor
T4.
(starting with illuminated display):
1. Press the right arrow button until
Timeprog-options;
2. Press the OK button;
3. Press the right arrow button until
Timeprog CH;
4. Press the OK button;
5. Press the right arrow button until
Day Temp;
6. Press the OK button;
The display shows: T_day
7. Press the + or - button to adjust the
desired flow temperature and press
the OK button.
Basic
Settings
CH temp
85 °C
Timeprog
options
Timeprog
CH
Day
Temp
T_day
85 °C