2. Standard inlet temperature
Change the value of the setting of the inlet temper-
ature and the outside temperature with "+/-" and
select the next value with "Next". Then confirm with
"OK".
User level
Expert level
¯
Settings
¯
e.g. unmixed cycle
¯
Cooling curve adjustment
¯
Setting the standard inlet temperature
A cooling function via the cooling curve setting
is only enabled by REMKO if the corresponding
humidity probe is installed!
NOTICE!
At least one dew point monitor with corre-
sponding probes should be installed to protect
the system in the case of panel heating.
3. Set the standard outside temperature
The standard outside temperature can be changed
in the user and expert level.
Here, it is possible to set the outside temperature
to the respective value for heating and cooling
mode.
Cooling is active if the stored cooling limit is
exceeded by the set value.
Example: The room target temperature is 20 °C
and the set cooling limit is 4 K. If a temperature of
over 24 °C is now measured at the external probe,
cooling will be active. The inlet temperature falls as
the outside temperature rises, up to the value
assigned for the outside temperature. When set-
ting the cooling curve, make sure that the dew
point is not undershot with panel heating (e.g. if the
underfloor system is to be cooled). REMKO recom-
mends protecting the system with dew point moni-
tors in the case of panel heating.
Access this parameter as follows:
User level
Expert level
¯
Settings
¯
Heating/cooling
¯
Building adaptation
¯
Standard outside temperature
Fixed value control cooling circuit mode
Specify the set temperature for fixed value control.
With this, the cooling circuit regulates to an aver-
aged temperature. The value is calculated from the
inlet temperature plus the return temperature
divided by two.
User level
Expert level
¯
Settings
¯
e.g. unmixed cycle
¯
Fixed value
Operating the cooling cycle with a fixed value is
not recommended, as it will cause the heat
pump to operate inefficiently and there is a risk
that the dew point will be undershot.
Cooling is active if the set cooling limit is exceeded
by the set value. Example: The room target tem-
perature is 20 °C and the set cooling limit is 4 K. If
a temperature of over 24 °C is now measured at
the external probe, cooling will be active. The
cooling function is immediately active if the oper-
ating mode is set from "Automatic" to "Cooling".
29