Error messages on the Smart Control
Operating messages, warnings and error display on the Smart-Control
Operating messages
ID
Description
Desig. Details
ID6000 Storage tank 1: Max.
temperature reached
The temperature on one of the probes in storage tank 1 is
higher than the maximum permitted storage tank temperature
ID6001 HW request
There is an active requirement to charge the storage tank
ID6002 Heat pump compressor
start
Heat pump compressor start
ID6003 Switching cycle disa-
bled (I/O2)
The heat pump was disabled in order to reduce the compres-
sor's switching cycles
ID6005 Internal pump lead time
The internal pump runs at reduced speed during the pump
lead time
ID6006 Switching cycle disa-
bled
The heat pump was disabled in order to reduce the compres-
sor's switching cycles
ID6007 Min. holding time
The heat pump is disabled due to a min. holding time
ID6008 Disable signal
S16
The heat pump is disabled due to a disable signal
ID6009 Disable signal (I/O 2)
The heat pump is disabled due to a disable signal
ID6010 Heat pump compressor
start (I/O 2)
Heat pump compressor start
ID6012 Defrosting HP (I/O 2)
Defrost heat pump
ID6020 Pump internal
after-run time
The internal pump runs at a reduced speed during the pump
after-run time
ID6022 Min. holding time (I/O2)
The heat pump is disabled due to a min. holding time
ID6103 Heat demand HP
Heat demand, heat pump
ID6104 Cooling demand HP
Cooling demand, heat pump
ID6105 Defrost heat pump
Defrost heat pump
ID6107 Standby mode active
Standby mode active
ID6108 Random delay after
power failure
Random delay after power failure (up to 200 seconds after
power returns) - the purpose of the random delay is to avoid a
system overload due to many consumers being switched on
at the same time
ID6109 Outdoor temp. Heat
pump usable limit
Outdoor temp. Heat pump usable limit - the heat pump is disa-
bled due to the usable limits being exceeded or not being
reached
ID6111
Heat pump bivalence
temperature
Heat pump bivalence temperature - the heat pump is disabled
because the temperature has dropped below the bivalence
temperature
ID6113 Solar heating
Solar heating - heat generators are disabled
ID6114 Temperature dropped
below dew point
Compressor is disabled for cooling function