background image

Troubleshooting

NOTE

If all of the functional checks 
have been carried out without 
any findings, please contact an 
authorised service station. 

Malfunction

Possible cause

Remedial measures

• The unit does not start .
•  The display does not light up.
•  The LED does not illuminate.

No mains voltage.

•   Check the power supply

 

or fuses or switches 
on site.

• The unit does not start.

Air humidity in room too low.

Probe defective.

High/low pressure malfunction.

The unit is not within its usable 
limits of 10 - 36 °C.

•   Check the integrated hygrostat and 

set it to a low relative humidity, 
e.g. 40 % RH. 

•   Ensure that the room humidity is 

not below 40 % RH.

•   Contact a qualified technician.

•   Check the room conditions and 

alter as required. 

• The compressor does not start.

The compressor switched 
off automatically due to an 
overly high condenser 
temperature.

Lack of air ventilation.

Overly high ambient 
temperature.

Contaminated filter/intake 
device.

Check the following points if the unit 
does not start after 45 minutes:  

•   Check if the fan(s) is/are working.
•   Check if the intake filter is 

contaminated.

•   Check that the intake and outlet 

openings are free of contamination.

•   Check whether the heat exchanger 

fins are contaminated.

•   Check whether the room 

temperature is above 36 °C.  
If the room temperature is above 
36°C, the unit must be switched 
off.

NOTE

If it is not possible to 
determine the cause of the 
fault, switch off the unit 
immediately and disconnect it 
from the mains power supply 
to prevent further damage.

CAUTION

Work on the refrigerant 
system and on the electrical 
equipment must only be 
conducted by a specially-
authorised specialist! 

CAUTION

Prior to maintenance or 
repair work, the unit must be 
disconnected from the mains 
power supply.

20

REMKO SLE 45-85

Содержание SLE 45

Страница 1: ...Edition GB N03 REMKO SLE 45 85 Swimming pool dehumidifiers Operation Technology Spare parts ...

Страница 2: ......

Страница 3: ...rors or misprints Air dehumidification 4 6 Safety notes 6 Unit description 7 Set up 8 11 Commissioning 12 13 Unit function 14 Wireless remote control 15 17 LED remote control 18 Care and maintenance 19 Troubleshooting 20 Fault and information messages 21 Diagram cooling cycle 22 Electrical wiring diagram 23 Intended use 24 Customer service and guarantee 24 Environmental protection and recycling 24...

Страница 4: ... released from parts of a building or materials is absorbed by the surrounding air As a result the moisture content increases which ultimately gives rise to corrosion mould rot peeling of paint and other unwanted damage By way of example the diagram shows the corrosion rate of metal in different levels of humidity Air dehumidification Relative humidity Corrosion rate With regard to energy consumpt...

Страница 5: ... temperature to fall below it Building materials and structures are capable of absorbing considerable volumes of water such as brick 90 190 l m heavy concrete 140 190 l m and limestone 180 270 l m The drying of moist materials such as masonry is effected as follows The moisture moves from the inside of the material to its surface Evaporation occurs on the surface transfer of water vapour to the am...

Страница 6: ...ed for the drying process is not only dependent on the output of the unit but is determined to a greater extent by the speed at which the material or building section loses its moisture Safety notes The units have been subjected to extensive material functional and quality inspections prior to delivery However dangers can result from the units if they are used improperly or not as intended by untr...

Страница 7: ...that caused by mould must be prevented Operating sequence The unit is switched on and off using the integrated hygrostat The hygrostat is set to 60 RH in the factory The respective unit function is indicated by a multi colour LED display on the front of the unit The fan extracts the moist room air via the lower part of the front panel Heat is removed from the room air on the cold evaporator The ai...

Страница 8: ...s etc and avoid frequent entry to or exit from the room as much as possible In order to achieve optimum room air circulation using the dehumidifier the supply and exhaust air openings must remain clear Secure the wall spacers provided with the unit to the bottom corners of the unit using adhesive 341 341 341 437 437 450 450 450 Wall mounted bracket for the units SLE 45 SLE 65 SLE 85 Comply with al...

Страница 9: ...efore starting the unit Follow one of the following two instructions depending on the unit equipment Installing the SLE panel without LED light function To equip the unit with the panel follow these instructions 1 Open the connection flap on the bottom 2 Guide the power cable through the cable gland and then onwards to the terminal block 3 Then attach the cable for the power supply Connect the L1 ...

Страница 10: ...e cable end with the plug contact through the bottom gap Attach the cable with the cable ties to the strain relief and shorten the ends of the cable ties accordingly 5 Guide the power cable through the cable gland and then onwards to the terminal block 6 Then attach the cable for the power supply Connect the L1 phase accordingly to the first grey terminal L1 from the left Connect the zero phase N ...

Страница 11: ...l with LED function into the top edge use the top guide pins to centre it and then let it rest gently 14 Angle the panel slightly downwards and connect the plug contact on the terminal block to the plug contact on the panel 15 Stow the cable in the connection box 16 Push the panel using the bottom guide pins 17 Tighten the two locks clockwise so that the bottom of the panel can no longer be lifted...

Страница 12: ...rol board These can be used to navigate around the menu structure of the control board and to couple the control board with a wireless remote control NOTE If the air humidity is lower that the set value the unit will not start up even if the mains voltage is connected Control board front Control board The units are equipped with an electronic controller This features various interfaces and a displ...

Страница 13: ... RH The default value is set to OF Code SI The code SI stands for the maintenance interval that the operator or fitter requires This value is indicated in weeks and can be set from 01 to 99 The default value is OF Code tE The code tE stands for testing and the value St for self test To start the self test press OK and to cancel it hold the down key down for 5 seconds Menu structure To define the s...

Страница 14: ...ressor This safety function protects the compressor against an overload caused by overly high pressure in the cooling cycle In order to prevent damage to the condenser the units are equipped with a mechanism that prevents the compressor being immediately switched back on after it is switched off via the mains power supply The compressor does not switch back on until after a waiting time of approx ...

Страница 15: ... and Enter The display values and the air humidity scale have a value range of 0 to 99 RH The display values and the air temperature scale have a value range of 0 C to 40 C Information display The information display shows the setpoint values for the unit Fault messages together with the fault symbols are also displayed here Power supply The wireless remote control can be powered using 2 AAA batte...

Страница 16: ... in place and the board has been returned to the previous position the unit can now be provided with power in order to couple it with the wireless remote control Then screw the housing parts back into place Switching on and coupling the remote control The wireless remote control must be coupled with the unit before it can be used To do so carry out the following steps 1 Insert the batteries provid...

Страница 17: ...ding option of OF has been set to a value on the control board itself Please read pages 12 and 13 to set these values The Left and Right keys can be used to set these parameter values The parameter is confirmed as a new setpoint using the Enter key When this is confirmed the remote control switches back to the symbol and exits the menu If you would like to exit the user setup menu do not press any...

Страница 18: ...emote control to change modes You can use the Change mode key to select from 11 different programs 1 Solid colour red 2 Solid colour green 3 Solid colour blue 4 Solid colour yellow 5 Solid colour violet 6 Solid colour turquoise 7 Solid colour white 8 RGB alternating jumping 9 Seven alternating colours jumping 10 RGB alternating cross fading 11 All colour alternating cross fading Changing the batte...

Страница 19: ...OTE Regular care and maintenance is fundamental to a long service life and fault free operation of the unit Cleaning the suction filter Check the suction filter at regular intervals and clean if necessary The filter is secured in the intake grille on the front panel Light filter contamination can be remedied with careful blowing or suction Heavier contamination may be remedied by rinsing the filte...

Страница 20: ...automatically due to an overly high condenser temperature Lack of air ventilation Overly high ambient temperature Contaminated filter intake device Check the following points if the unit does not start after 45 minutes Check if the fan s is are working Check if the intake filter is contaminated Check that the intake and outlet openings are free of contamination Check whether the heat exchanger fin...

Страница 21: ...t be established and rectified by specialist personnel Acknowledgement possible only by way of unlocking sequence Initiate the sequence by pressing the OK key HP High pressure level detected Malfunction must be established and rectified by specialist personnel Acknowledgement possible only by way of unlocking sequence Initiate the sequence by pressing the OK key Fault messages Unlocking sequence I...

Страница 22: ...o modify the dimensions and design as part of the ongoing technical development process 1 2 3 4 5 6 7 Legend 1 Compressor 2 Evaporator 3 Condenser 4 Thermal expansion valve 5 Dry filter 6 Solenoid valve 7 Fan SLE 45 85 22 REMKO SLE 45 85 ...

Страница 23: ...serve the right to modify the dimensions and design as part of the ongoing technical development process Legend FAN 1 fan motor 1 FAN 2 fan motor 2 FAN 3 fan motor 3 CAP 1 capacitor 1 CAP 2 capacitor 2 CAP 3 capacitor 3 Fan motors SLE 45 FAN 1 SLE 65 FAN 1 and FAN 2 SLE 85 FAN 1 FAN 2 and FAN 3 L N PE Display USB RS485 _ Ext RH T Alarm 12 V DC Remote Operator Panel L1L1L1 N N PE LED Trafo LED ligh...

Страница 24: ...oints Disposal of the old unit The manufacturing process for the units is subject to continuous quality control Only high grade materials are processed the majority of which are recyclable You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environment friendly manner Therefore only bring the old unit to an authorised recycling business or ...

Страница 25: ...25 ...

Страница 26: ...1 10 2 3 4 5 6 7 8 9 11 12 13 14 15 16 17 18 19 21 20 22 Exploded view of the unit 23 26 REMKO SLE 45 85 ...

Страница 27: ...es 12 Solenoid valve 13 Dry filter 14 Copper piping set 15 Condensate tray 16 Unit panel 16a Unit panel white LED 16b Unit panel RGB LED 17 Fan module 18 Fan 19 Evaporator 20 Condenser 21 Temperature valve 22 Compressor insulation 23 Side panel 23a White LED side panel 23b RGB LED side panel Not illustrated White LED transformer Not illustrated RGB LED transformer Not illustrated RGB LED control u...

Страница 28: ... 0 1 0 Output alarm 2 0 Alarm output off 1 Alarm output on 6 10 Evap_temp1 decimal 40 100 0 Temperature of evaporator 1 Decimal Can be used as an integer value for temperature Fraction Can be converted to a decimal value To obtain the total value use the equation for floating point numbers Value decimal fraction 256 11 Evap_temp1 fraction 40 100 0 7 12 Evap_temp2 decimal 40 100 0 Temperature of ev...

Страница 29: ...ow byte can be used 21 Amb_hum Low byte 12 22 RH_set 40 95 40 Humidity setpoint 23 RH_Fan 40 95 40 Humidity setpoint for extractor fan start 13 24 Temp_set decimal 0 36 0 Temperature setpoint Used in the same way as Evap_temp1 25 Temp_set fraction 16 30 Fail_start 0 1 0 Status of Fail_start mode 31 SB_mode 0 1 0 Standby mode status 17 32 DEH_mode 0 1 0 Dehumidification status 33 Ice_mode 0 1 0 Def...

Страница 30: ...reater than this value Used in the same way as Evap_temp1 45 HP alarm Temp fraction 41 80 Fan_function 0 1 0 Activate fan function in standby mode 81 42 82 Time_wait_ fan 60 7200 3600 Waiting time until fan starts up in standby mode if activated seconds 83 43 84 Time_run_ fan 15 600 60 Fan operating time in standby mode if activated seconds 85 44 86 RH_Fen 0 1 0 Activate deactivate extractor fan f...

Страница 31: ..._mode 1 DEH Mode Ice_mode 1 ICE Mode LP_mode 1 LP Mode HP_mode 1 HP Mode Sens_mode 1 SENS Mode AmbT_mode 1 AMBT Mode AmbRH_mode 1 AMBRH Mode Service_ena 1 ENABLED Mode The USB interface is used for transferring data logs from the unit to a USB stick The unit data is saved every three hours and stored in the internal memory Switching the status to fault mode also triggers the storage of data If the...

Страница 32: ...ignature 17 Date Signature 18 Date Signature 19 Date Signature 20 Date Signature Comments Unit type Unit number 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 Unit cleaned outside Unit cleaned inside Condenser cleaned Evaporator cleaned Fan function checked Unit checked for damage Safety devices checked All fastening screws checked Electrical safety check Test run Unit to be maintained only by...

Страница 33: ...witching voltage from RUN and FAIL contact V 50 50 50 Max switching current from RUN and FAIL contact A 0 5 0 5 0 5 HEAT contact voltage V 12 12 12 Maximum current limit of a HEAT contact mA 60 60 60 Refrigerant 1 R407C Refrigerant quantity kg 0 7 0 9 1 2 Sound pressure level LpA 1m 2 dB A 46 47 50 Depth mm 335 335 335 Width mm 1015 1165 1500 Height mm 816 816 816 Weight kg 62 76 103 IP enclosure ...

Страница 34: ...Technical data Light equipment White LED RGB LED Operating voltage V DC 12 12 Power W 28 28 Average service life h 25 000 Lumen Lumen approx 400 2150 Lamp White LED RGB LED ...

Страница 35: ...uchte nicht ausgetauscht werden L E D White LED 1123005 This light contains integrated LED bulbs The bulbs in the light cannot be replaced A A A B C D E LED Weiß 1123004 874 2012 Diese Leuchte enthält eingebaute LED Lampen Die Lampen können in der Leuchte nicht ausgetauscht werden L E D White LED 1123004 This light contains integrated LED bulbs The bulbs in the light cannot be replaced White LED E...

Страница 36: ...advisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is quickly on the scene Our comprehensive network of experienced dealers guarantees quick and reliable service REMKO INTERNATIONAL and also right in your neighbourhood Take advantage of our experience and advice ...

Отзывы: