Heating capacity RVD 684 DC
0,00
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
7,00
7,50
8,00
8,50
-15
-10
-5
0
7
10
2
1
3
A
[°C]
Fig. 7: Performance curves, heating RVD 684 DC (data for room temperature FK 27 °C/TK 19°C)
A: Outside temperature / 1: COP
2: Heating capacity in kW
3: Power consumption in kW
Outside temperature in °C
-15
-10
-5
0
7
10
Heating capacity in kW
4.22
5.57
4.92
5.76
7.03
7.66
Power consumption in kW
1.52
1.62
1.71
1.81
1.90
1.96
COP
2.78
2.83
2.88
3.19
3.70
3.92
Cooling capacity RVD 684 DC
0,00
0,50
1,00
1,50
2,00
2,50
3,00
3,50
4,00
4,50
5,00
5,50
6,00
6,50
7,00
7,50
8,00
8,50
20
25
30
35
40
2
1
3
A
[°C]
Fig. 8: Performance curves, cooling RVD 684 DC (data for room temperature FK 27 °C/TK 19°C)
A: Outside temperature / 1: EER
2: Cooling capacity in kW
3: Power consumption in kW
Outside temperature in °C
20
25
30
35
40
Cooling capacity in kW
8.02
7.70
7.36
7.03
6.68
Power consumption in kW
1.69
1.84
2.00
2.17
2.32
EER
4.74
4.18
3.69
3.24
2.88
15
Содержание RVD 1054 DC
Страница 67: ...Resistance values for probes T1 T2 T3 and T4 K Ohm K Ohm K Ohm K Ohm 67 ...
Страница 68: ...Resistance values for probe T5 K Ohm K Ohm K Ohm K Ohm REMKO RVD series 68 ...
Страница 83: ...No Designation 31 Shut off valve mounting plate 32 Condensate tray heating 33 Crankcase heating 83 ...
Страница 85: ...85 ...
Страница 86: ...REMKO RVD series 86 ...
Страница 87: ......