Troubleshooting and customer service

 

 

The unit has been manufactured using state-of-the-art production methods and has been tested several

times to ensure that it works properly. If malfunctions should occur, please check the unit as detailed in the

list below. Please inform your dealer if the unit is still not working correctly after all the function checks have

been performed.

Fault description

Cause

Remedy

The unit does not start or switches

itself off.

Master switch off.

Switch on the main switch.

Power failure

Check voltage and if necessary

wait until turned on again.

Defective mains fuse

Arrange to have exchanged

Power supply defective

Repair by certified serv. centre.

Operational temperature range too

low or exceeded.

Observe operational tempera-

ture range 18 to 35 °C.

Internal reservoir full.

Empty reservoir.

The ambient temp. of the unit lies

outside the operating range (18 to

35 °C).

Do not operate the unit outside

the operating range.

The unit does not work or works at

reduced cooling capacity.

Exhaust air hose kinked, extended,

routed downwards or blocked.

Ensure that there is a clear

path for the exhaust air.

Filter contamination, inlet or outlet

blower openings blocked by foreign

bodies.

Clean filter.

Minimum clearances too small.

Observe minimum clearances.

Windows and doors open / heat

load was increased.

Close doors and windows /

reduce heat load.

Negative pressure in the installa-

tion room whilst the unit is oper-

ating with wall pass-through.

Balance out the pressure in the

installation room.

"Cooling" operating mode is not

used.

Use "AUTO, HI, MED or LO"

operating mode.

Unit will be switched by means of

the timer function.

Press "I / 0" key again.

Temperature setting too high.

Reduce temperature.

Overvoltage due to local lightning

strike.

Switch unit off and separate

from the power supply for 5

mins., then start anew.

The unit does not respond to the

infra-red remote control.

Batteries in the remote control are

empty or the distance to the

receiver is too great.

Insert new batteries / reduce

distance.

After battery exchange, incorrect

polarity of batteries.

Insert the batteries with the cor-

rect polarity. Observe marking.

Condensate discharge on unit.

Unit standing at an angle.

Stand vertically.

The stopper for the condensate

drain is not correctly inserted or is

damaged.

Insert stopper correctly or

replace if necessary.

 

 

 

 

 

17

Содержание RKL 300

Страница 1: ...Assembly and operating instructions Read the instructions prior to performing any task REMKO RKL 300 RKL 300 S Line RKL 360 RKL 360 S Line Local Air Conditioner 0058 2014 01 Edition 2 en_GB...

Страница 2: ...g inal Read these operating instructions carefully before commis sioning using this device These instructions are an integral part of the system and must always be kept near or on the device Subject t...

Страница 3: ...nspection 5 1 8 Unauthorised modification and changes 5 1 9 Intended use 5 1 10 Warranty 5 1 11 Transport and packaging 6 1 12 Environmental protection and recycling 6 2 Technical data 7 2 1 Unit data...

Страница 4: ...ay be fatal or cause serious injury WARNING This combination of symbol and signal word warns of a potentially hazardous situation which if not avoided may be fatal or cause serious injury CAUTION This...

Страница 5: ...e factory The units may only be secured or mounted on stable structures walls or floors n Mobile units must be set up securely on suit able surfaces and in an upright position Sta tionary units must b...

Страница 6: ...ion and recycling Disposal of packaging All products are packed for transport in environ mentally friendly materials Make a valuable contri bution to reducing waste and sustaining raw mate rials Only...

Страница 7: ...60 410 450 360 410 450 Sound pressure level per stage 2 dB A 49 51 53 49 51 53 Sound power level max dB A 61 61 Power supply V Ph Hz 230 1 50 230 1 50 Enclosure class IP 20 20 Electr rated power consu...

Страница 8: ...ns of a condensate pump located in the unit the con denser evaporates the condensate and discharges it to the outside via the exhaust air hose The unit filters and dehumidifies the air thereby creatin...

Страница 9: ...rge difference between the target room temperature set and the current room temperature a high fan stage will be automatically selected Conversely with a small difference a small fan stage will be aut...

Страница 10: ...ollows 1 Switch the unit off with the I 0 key and pull out the power plug 2 Place a suitable container underneath the con densate drain of the internal reservoir The con densate drain is located on th...

Страница 11: ...of the unit can be implemented via the remote control supplied Please refer to the Con trol panel section for the functions of the keys The range of the remote control is ca 5 metres 2 1 5 3 15 4 6 F...

Страница 12: ...the power supply must be of a sufficient cable size and must only be used fully rolled out Fig 6 Power supply n Check whether the stopper in the condensate drain is present and correctly installed Th...

Страница 13: ...is advis able to feed the exhaust air to the outdoor area or to outdoors Exhaust air routing variants You can route the exhaust air out of the building as follows Via a flat nozzle The flat nozzle sup...

Страница 14: ...e inside of the wall In order to avoid cold bridges insulate the telescopic tube with suitable insulation material 3 Brick the slide tube into the core hole such that it sits flush on both sides of th...

Страница 15: ...KM Condensate pump CM Compressor OLP Compressor fuse CX1 Capacitor M1 CX2 Capacitor M2 CX3 Capacitor CM TH Temperature probe MS1 Microswitch tank full MS2 Microswitch pump Colour coding BK Black BR B...

Страница 16: ...e 1 Switch the unit on with the I O key 2 Select cooling mode with the MODE key The AUTO LED must illuminate 3 Set the desired target temperature with the THERMO CONTROL key The selected target temper...

Страница 17: ...cked Ensure that there is a clear path for the exhaust air Filter contamination inlet or outlet blower openings blocked by foreign bodies Clean filter Minimum clearances too small Observe minimum clea...

Страница 18: ...contract with an appropriate specialist firm This enables you to ensure the operational reli ability of the plant at all times Filter cleaning The unit is equipped with two air filters These can be w...

Страница 19: ...o the rear of the unit 3 Place a suitable container underneath the condensate drain of the internal reservoir The condensate drain is located on the lower rear side of the unit 4 Pull out the stopper...

Страница 20: ...the unit 8 7 30 20 21 31 15 18 19 25 32 26 24 27 28 14 11 12 13 3 29 4 5 23 22 1 2 10 9 17 16 34 33 36 35 37 Fig 18 Exploded view drawing We reserve the right to modify the dimensions and design as pa...

Страница 21: ...KL 300 RKL 360 RKL 360 1 Front panel By request with the serial number 2 Recessed grip 3 Cover control panel 4 Outlet grill 5 Fins 6 Shift lever for fins 7 Back wall 8 Air filter recirculation 9 Unit...

Страница 22: ...tor 29 Fin motor 30 Exhaust air filter 31 Power supply with plug 32 Compressor capacitor 33 Capacitor evaporator fan 34 Capacitor condenser fan 35 Exhaust air hose cpl 36 Infrared remote control 37 Se...

Страница 23: ...ded view drawing 20 Exploded view of the unit 20 I Installation 12 M Maintenance 18 O Operation Control panel 9 R Recirculated air filter 12 S Safety Dangers of failure to observe the safety notes 4 G...

Страница 24: ...REMKO RKL 24...

Страница 25: ...25...

Страница 26: ...REMKO RKL 26...

Страница 27: ......

Страница 28: ...t as advisers to our customers in air conditioning and heating technology SFlbCustomer Service Our equipment operates precisely and reliably However in the event of a fault REMKO customer service is q...

Отзывы: