Safety Hints

 

 
When using this unit make sure always to observe 
the applicable building and fire protection regula-
tions as well as the rules of the trade cooperative 
association. 

 

l

The unit may be operated only by those persons who 
have been instructed accordingly. 

 

l

The unit is to be installed and operated in such a way 
as to ensure that the employees are not endangered 
by waste gases and radiation heat and that no fire 
can break out. 

 

l

The unit  may only be installed and operated in 
rooms, when the air rate fed to the unit is sufficient 
for combustion. 

 

l

Make sure to install mobile liquid gas reservoir on a 
solid ground and in a vertical position. 

 

l

Liquid gas reservoir may never be used in a lying po-
sition while the unit is operating (gas leakage in the li-
quid phase). 

 

l

The unit may be operated only in well aerated rooms. 
Persons may not stay permanently in the room where 
the unit has been installed. Relevant prohibition signs 
are to be fastened to the entrances. 

 

l

The unit is to be installed and operated on a solid 
non combustible ground. 

 

l

It is to be ensured that no combustible objects/
materials can be sucked in. 

 

l

The unit may not be installed or operated in in-
flammable and explosive surroundings. 

 

l

A safety zone of 1.5 m around the unit and a mini-
mum distance of 3 m at the unit’s exhaust opening 
are to be observed, even regarding non combustible 
objects. 

 

l

The unit’s exhaust opening may not be reduced or 
equipped with hoses or pipings. 

 

l

Make sure not to introduce foreign matters into the 
unit. 

 

l

The air suction lattice is always to be kept free from 
dirt and loose objects. 

 

l

Make sure not to expose the unit to direct water jets. 

 

l

All electric cables outside the unit are to be protected 
from damage (e.g. caused by animals, etc.). 

 

l

Make sure to cut off the gas supply and to pull the 
mains plug out of the mains socket when mainte-
nance and repairs are carried out. 

 

l

Safety devices may be neither bridged nor  
blocked. 

General Hints

 

 

²

The unit may be operated only by those persons who 
have been instructed regarding the unit’s operation 
and the handling of liquid gas. 

 

²

When using the unit make sure always to obser-
ve the guiding principles of the countries and 
states concerned. 

 

²

The unit may only be operated in rooms when 

 
–   the air rate fed to the unit is sufficient for com- 
     bustion  and 

 
–   the rooms are well ventilated and deventilated and 

 
–   the percentage of the substances which are  
     injurious to health in the breathed in air has  
     no inadmissible concentration. 

 

good and natural ventilation and deventilation 

is given if e.g. the room volume in m³ corresponds to 
at least 30 times the nominal heat load in kW of all 
the units being operated in the room, and if a natural 
air exchange through doors and windows is ensured, 

or 

if there are permanently open ventilation possibili-

ties for ingoing and outgoing air near the ceiling and 
the floor, of which the size in m² corresponds to at 
least 0.003 times the nominal heat load in kW of all 
the units being operated in the room. 

 

²

A uniform unit connection pressure of 1.5 bar 
(1500 mbar) of the category I 3B/P is necessary 
for all the countries of the European Community. 

 
     The connection pressure may not fall below or  
     exceed the required value. 

 

²

Make sure to use exclusively components, such as 
gas hose, pressure controller and hose security devi-
ces (protection against breakage) or safety devices 
against gas leakage, that have been tested and are 
suitable for the intended purpose. The pressure con-
trollers must have a firmly regulated initial pressure 
of 

1500 mbar 

and are to be equipped with a security 

device against hose breakage. 

 

²

Hose pipes are to be protected generally against 
chemical, thermal and mechanical damage. 

 

²

The persons charged with the operation of the unit 
have to check it prior to starting work to make sure 
that there are no visible defects. If there are defects 
which affect the unit’s operational reliability, its opera-
tion is to be stopped! 

 

²

The unit may be only maintained by trained persons 
and only original spare parts may be used. 

 

²

If the unit has been switched off by the temperature 
limiter due to overheating, the reason for the fault 
has to be detected and eliminated. 

Содержание PGT 100

Страница 1: ...REMKO strong as a bear Propane Heater REMKO PGT 30 PGT 100 Edition GB L07 Operation Technology Spare Parts...

Страница 2: ...Drawing PGT 100 12 List of spare parts PGT 100 13 Block diagrams 14 Technical data 15 G Always keep these operating instructions near or on the device G PGT 100 PGT 30 PGT 60 Mobile Propane Heaters O...

Страница 3: ...ted only by those persons who have been instructed regarding the unit s operation and the handling of liquid gas When using the unit make sure always to obser ve the guiding principles of the countrie...

Страница 4: ...constant unit connection pressure of 1 5 bar 1500 mbar must be ensured also during con tinuous operation G 1 2 Install only in well ventilated rooms not in rooms which people will be using for longer...

Страница 5: ...you use a bottle battery consisting of at least 3 bottles All bottle valves must be open to ensure regular gas supply T connection high pressure hose 0 4 m pressure controller hose break protection g...

Страница 6: ...ed set or repai red the gas supply has to be cut off and the mains plug has to be unplugged from the mains socket Setting and maintenance work is to be carried out only by authorized specialists Any o...

Страница 7: ...rode incorrectly set Set according to instructions check porcelain insulation of electro des 9 Suction protective lattice of air supply fan is dirty Clean suction protective lattice 10 switching off b...

Страница 8: ...8 We reserve the right to make modifications in dimensions and construction in the interests of technical progress Drawing PGT 30...

Страница 9: ...37 clutch disc 38 gas burner 39 protection socket 40 retaining bracket not shown pressure controller with hose break protection 2 running metres gas hose 2 running metres HD gas hose for building sit...

Страница 10: ...10 Drawing PGT 60 We reserve the right to make modifications in dimensions and construction in the interests of technical progress...

Страница 11: ...t 1101197 30 solenoid valve 1101376 31 thermostat socket 1101018 32 shunt plug 1101019 33 gas connection nipple 3 8 lks 1101134 34 control knob cpl 1101192 36 traction relief 1101267 37 operating swit...

Страница 12: ...12 Drawing PGT 100 We reserve the right to make modifications in dimensions and construction in the interests of technical progress...

Страница 13: ...er 28 tube fitting M10 x 1 29 gas pipe R D Fig No Description 30 support bracket rear 31 operating switch 32 traction relief 33 connecting cable with plug 34 shunt plug 35 thermostat socket 36 control...

Страница 14: ...de ZT ignition transformer Block Diagram PGT 100 HS auxiliary relay I ionisation electrode KL terminal strip M fan motor MV solenoid valve NK after cooling thermostat RS burner relay socket RT room th...

Страница 15: ...uring DIN 45635 01 KL 3 Technical Data Automatic burner relay Working voltage 230 V 15 10 Frequency 50 Hz 40 60 Hz Safety time 5 seconds Waiting time after interference cut off ca 60 seconds Allowable...

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage Postfach 1827 Telefon 0 52 32 606 0 Telefax 0 52 32 606260...

Отзывы: