2
Technical data
2.1 Unit data
Series
MXT 264
MXT 354
Operating mode
Wall chest for inverter multisplit
outdoor units for cooling and
heating
Nominal cooling output
1)
kW
2.6
3.5
Nominal heat capacity
2)
kW
2.9
3.5
Application area (room volume), approx.
m
3
80
110
Adjustment range, room temperature
°C
+17 to +30
Operating range
°C/r.H.%
+17 to +32 / 35-65
Refrigerant
R32
Operating pressure, max.
kPa
4200
Air flow volume per stage
m
3
/h
450/580/680
360/470/550
Sound pressure level per stage
3)
dB (A)
35/40/45
35/41/47
Sound power level max.
dB (A)
56
58
Power supply
V/Ph/Hz
230/1~/50
Enclosure class
IP
X 0
Electrical rated power consumption, cooling
1)
W
30
40
Electrical rated power consumption, heating
2)
W
36
48
Electrical rated current consumption, cooling
1)
A
0.13
0.17
Electrical rated current consumption, heating
2)
A
0.16
0.21
Refrigerant connection
Injection pipe
Inches
(mm)
1/4 (6.35)
1/4 (6.35)
Refrigerant connection
Suction pipe
Inches
(mm)
3/8 (9.52)
3/8 (9.52)
Condensate drainage connection
mm
16