Operation

Regular care, maintenance and 
observation of some basic points 
will ensure trouble-free operation 
and a long service life. 

Care and maintenance

Prior to performing any 
work, ensure the equipment 
is isolated from the voltage 
supply and secured to prevent 
accidental switch-on!

      CAUTION

Temporary  Shutdown

1.  Allow the indoor unit to run for 

2 to 3 hours in air circulation 
mode or in cooling mode at the 
maximum temperature setting 
in order to remove any residual 
moisture from the unit.  

2.  Shut down the system using 

the remote control  

3.  Switch off the voltage supply 

to the unit.

4.  Cover as much of the unit as 

possible with plastic foil to 
protect it against the weather. 
 

Permanent Shutdown 

Ensure that equipment and 
components are disposed of 
accordance with local regulations, 
e.g. through authorised disposal 

Shutdown

Care 

■ 

Ensure the unit is protected 
against dirt, mould and other 
deposits.

■ 

Clean the unit using a damp 
cloth. 
Do not use a jet of water.

■ 

Do not use any caustic, abrasive 

or solvent-based cleaning 
products.

 

When operating the fan, clean 

the fins of the unit prior to long 
shutdown periods.

Maintenance 

■ 

It is recommended that 

maintenance contract with 

annual maintenance interval 

with an appropriate specialist 

company. 

This ensures the operational 
reliability of your equipment!

      TIP

The compressor in the outdoor 
unit is operated by means of 
regulating the control board in the 
outdoor unit.

The chapter on "Regulation" in 
the manual for the outdoor unit 
must therefore be observed.

Type of task
 
Checks/Maintenance/Inspections

Commissioning

Monthly

Six-monthly

Yearly

General

Measure voltage and current

Function compressor

Check fan is functioning correctly

Dirt on liquefier

Check refrigerant fill quantity

Check condensation drain

Test insulation

Check moving parts

Sealing test for refrigerant circuit

 

1)

The statutory regulations 
require an annual sealing 
test for the refrigerant circuit 
in relation to the refrigerant 
filling level. The inspection 
and documentation is to be 
carried out by corresponding 
specialist engineers.

      NOTE

1) see note

and recycling specialists or at 
collection points.
 
Contact REMKO GmbH & Co. KG 
or your contract partner for local 
specialist companies near you.

Help save on energy consump-
tion in stand-by mode! If the 
device, system or component 
is not in use, we recommend 
disconnecting the power sup-
ply. Components with a safety 
function is excluded from our 
recommendation!

      TIP

9

Содержание MVT 1050 DC

Страница 1: ...Edition GB C01 REMKO MVT MVT 600 DC MVT 900 DC MVT 950 DC MVT 1050 DC Inverter multisplit outdoor units Operation Technology Spare parts...

Страница 2: ......

Страница 3: ...ycling 4 Warranty 4 Intended use 5 Transport and packaging 5 Description of the equipment 5 6 Combinations 7 8 Operation 9 Shutdown 9 Care and maintenance 9 Troubleshooting and customer service 10 11...

Страница 4: ...ould only be set up and installed by qualified personnel The setup connection and operation of the unit and its components must be in accordance with the operating conditions stipulated in this manual...

Страница 5: ...n valves and a liquefier fan The outdoor unit is combinable with REMKO indoor units of series MXW in accordance with the cooling output see chapter Combinations The outdoor unit refrigerant circuit is...

Страница 6: ...System design The connection between indoor units A B C D and outdoor units connection circuit A B C D of the outdoor unit is achieved with refrigerant pipes and a control line Injection pipe Suction...

Страница 7: ...s Combination 13 Combination 14 Combination 15 Combination 16 Combination 17 Combination 18 Combination 19 Combination 20 Combination 21 Combination 22 MXW MXD MXT 200 201260 261350 351520 521 One ind...

Страница 8: ...1 MXW MXD MXT 200 260 350 520 One indoor unit Combination 1 Combination 2 Combination 3 Combination 4 Two indoor units Combination 5 Combination 6 Combination 7 Combination 8 Combination 9 Combination...

Страница 9: ...tenance It is recommended that maintenance contract with annual maintenance interval with an appropriate specialist company This ensures the operational reliability of your equipment TIP The compresso...

Страница 10: ...on the outdoor unit running Fan winter controller should be checked Leaking refrigerant circuit Are there signs of severe frost on the large stop valve Repair by a specialist Fault Possible cause Chec...

Страница 11: ...between outdoor and indoor unit Contact specialist dealer P0 Excessive temperature Klixon compressor Check refrigerant Check the resistance of the compressor sensor normal 0 P1 High pressure sensor ha...

Страница 12: ...basic length of the refrigerant pipe exceeds 5 metres For the quantity of additional refrigerant refer to chapter Add refrigerant Only use the union nuts for the refrigerant pipes included in the del...

Страница 13: ...d by the measures Wind If the unit is being installed in windy areas ensure the air discharges in the prevailing wind direction If this is not the case it may be necessary to install a windbreak provi...

Страница 14: ...s and potential cracking are the consequences Minimum clearances Oil return measures Outdoor unit Oil pump bend in suction pipe to outdoor unit 1 x every 2 5 metres of rising pipe Radius min 50 mm max...

Страница 15: ...mentary information for Installation When combining the outdoor unit with indoor unit MXW 350 the connection of the refrigerant pipes differs In this case install the expansion fittings to the outdoor...

Страница 16: ...completely extracted from the system the valves on the pressure gauge station are closed and the valves on the outdoor unit are opened as described in the chapter on Commissioning All electrical inst...

Страница 17: ...Suction pipe A A B B C C Control board Control board Trans former Trans former Trans former Trans former Sensor Sensor Sensor suction pipe Sensor suction pipe Heating Heating Fan motor Fan motor Power...

Страница 18: ...ve A B C D Compressor Line filter C B A D Indoor units Heating Fan motor Power output 230V 1 50Hz Inverter valve Power board Sensor Suction pipe High pressure switch Low pressure switch Sensor MVT 105...

Страница 19: ...ns cable 230 V 1 50 Hz L1 N PE N L N L1 MVT 900 DC Indoor unit Circuit A Plug Outdoor unit Circuit A Indoor unit Circuit B Indoor unit Circuit C Plug Outdoor unit Circuit B Plug Outdoor unit Circuit C...

Страница 20: ...a basic quantity of refrigerant In addition an additional amount of refrigerant must be added for refrigerant pipe lengths exceeding 5 meters per circuit Refer to the following chart Note that the emp...

Страница 21: ...pen the stop valves by turning them anti clockwise using a spanner If leaks were found draw off the refrigerant and rework the defective connection It is imperative that the vacuum creation and drying...

Страница 22: ...sensor liquefier Temperature sensor air inlet Liquefier Temperature sensor hot gas Power consumption compressor Degree of opening for electronic Expansion valve no 4 Degree of opening for electronic e...

Страница 23: ...45 C 12 45 50 C 13 50 55 C 14 55 60 C 15 60 65 C 16 65 70 C Display Temperature 15 7 5 C 20 5 0 C 25 2 5 C 30 0 C 35 2 5 C 40 5 0 C 45 7 5 C 50 10 0 C 55 12 5 C 60 15 0 C 65 17 5 C 70 20 0 C 75 22 5...

Страница 24: ...ensions and constructional design as part of the ongoing technical development process Unit dimensions All values in mm MVT 600 DC MVT 900 DC MVT 950 DC 560 335 705 315 845 595 335 860 305 900 MVT 105...

Страница 25: ...r compressor 111103 111033 111053 9 Condenser liquefier fan 111104 111034 111109 111081 10 Stop valve suction pipe 111035 111036 111055 111082 11 Stop valve injection pipe 111037 111038 111056 111083...

Страница 26: ...0 10 80 13 50 Electr starting current max A 35 35 40 67 Electrical power consumption max kW 3 10 4 00 4 80 6 30 Compressor model Rotary piston Twin pistons Flow regulator Electronic expansion valves R...

Страница 27: ...VT 1050 DC Kombination mit 4 x MXW 260 0 00 2 00 4 00 6 00 8 00 10 00 12 00 14 00 16 00 18 00 24 12 7 4 0 5 7 15 Au entemperatur C Heizleistung kW Reihe MVT 1050 DC Characteristic curves heat Heating...

Страница 28: ...mentation Inverter multisplit outdoor units Series Designation REMKO MVT 600 DC MVT 900 DC MVT 950 DC MVT 1050 DC Series Class Number 783 784 785 1042 Applicable regulations MA RL 2006 42 EC Machine d...

Страница 29: ...Notizen...

Страница 30: ...REMKO MVT 30...

Страница 31: ......

Страница 32: ...salesmen above all they must advise our clients in the areas of air conditioning and heating technology Customer Service Our equipment is precise and reliable However should a fault should occur REMKO...

Отзывы: