Fig. 35: Dimensions for the strip foundation
(plan view)
For the designations of 1, 3, 5, 8, 9 and 11, please
refer to the legend for the Fig. 34
dimensioning of the strip foundation (in mm)
Dime
nsion
ML 265 DC
AT
ML 355 DC
AT
ML 525 DC
AT
ML 685 DC
AT
A
800
B
200
C
487
514
540
D
300
333
350
E
287
314
340
Condensate drainage connection
Due to the dew point shortfall on the evaporator,
condensation is created on the indoor unit in
cooling mode and on the outdoor unit in heating
mode.
Below the evaporator is a collection tray, which
must be connected to a drain.
n
The condensate drainage line should have an
incline of min. 2% (Fig. 36). This is the respon-
sibility of the customer. If necessary, fit vapour-
diffusion-proof insulation.
n
Route the unit's condensate drainage line
freely into the drain line. If the condensate runs
directly into a sewer pipe, fit a trap to prevent
any unpleasant odours.
n
When operating the unit at outside tempera-
tures below 0 °C, ensure the condensate
drainage line is laid to protect it against frost.
The lower part of the housing and condensate
tray is also to be kept frost free in order to
ensure permanent draining of the condensate.
If necessary, fit a pipe heater.
n
Following installation, check that the conden-
sate run off is unobstructed and ensure that the
line is durably leak tight.
min. 2%
Fig. 36: Condensate drainage connection - Indoor
unit
The condensate hose is designed to be connected
on the right and the left side (view from front).
Remove the stopper from the corresponding con-
nection.
Safe drainage in the event of leakages
The REMKO oil separator OA 2.2 fulfils the fol-
lowing list of requirements from regional regula-
tions and laws.
NOTICE!
Local regulations or environmental laws, for
example the German Water Resource Law
(WHG), can require suitable precautions to pro-
tect against uncontrolled draining in case of
leakage to provide for safe disposal of escaping
refrigerator oil or hazardous media.
NOTICE!
If condensate is removed via a duct in accord-
ance with DIN EN 1717, ensure that any micro-
biological contamination present on the waste-
water side (bacteria, fungi, viruses) cannot
enter the unit connected to it.