Electrical wiring diagram
KP 8 connection
KP 8
PE: Earth conductor (green/yellow)
N: Neutral conductor (blue)
L: Phase conductor (brown)
Power supply, 230 V/,1~, 50 Hz
N
PE
L
Electrical wiring
1. Insert the 2 m long 4-pin
connection cable of the reservoir
into the socket of the condensate
pump.
2. Connect the supplied double cable
with the 6-pin plug into the free
socket of the condensate pump.
3. Connect the 6 cores as shown
in the wiring diagram below.
When using the malfunction contacts, unused cable ends must
be properly insulated (terminal block).
!
CAUTION
NC
C
NO
Changeover contact, see table 1
NC: Normally closed contact (white)
Connection see tab. 1, column 2
C: Common contact (black)
Connection see tab. 1, column 3
NO: Normally open contact (violet)
Connection of malfunction signalling device
Indoor unit Connection to NC (white)
Connection to C (black)
RXW
Control conductor, contact
3
on IT
Control conductor, contact
3
on AT
RVT
Control conductor, contact
S
on IT
Control conductor, contact
S
on AT
MXW
Control conductor, contact
S
on IT
Control conductor, contact
S
on AT
ML...DC
Control conductor, contact
S
on IT
Control conductor, contact
S
on AT
RXT
Phase conductor, input
S
on IT
*)
MVW
Disconnect the CN 19 (WATER) in the middle and connect
pump contacts NC (white) and contact C (black).
*) varies, depending on where the 230V, 1~, 50Hz power supply comes from!
4. Check assembly again and perform
a functional test.
5. Fill water into the condensate
tray and check whether the pump
is switched on and the condensate
is pumped out to the drain on site.
To check the air conditioner's alarm
contact, add enough water to trigger it.