Electrical wiring HTS 130
4.1 Overview of electrical connection cables
B
C
4
6
A
2
D
5
3
7
1
Fig. 8: Overview of electrical connection HTS 130
A: Outdoor unit
B: Indoor module
C: Customer-provided sub-distribution
D: Outdoor sensor
1: Mains supply line, indoor module,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
2
2: Mains supply line, booster heating,
400V / 3~ / 50Hz, 16A, e.g. 5 x 2.5 mm
2
3: Power supply from indoor to outdoor module /
condensate drainage heating,
230V / 1~ / 50Hz, 10A, e.g. 5 x 1.5 mm
2
4: Control cable, outdoor module 0-10V
(sheathed) / Sensor cable (sheathed),
e.g. 5 x 1.0 mm
2
5: Sensor cable on outdoor sensor,
e.g. 2 x 1.0 mm
2
6: Mains supply line to control unit (I/O module)
230V / 1~ / 50Hz, e.g. 3 x 1.5 mm
2
7: Utility signal for Smart-Control S16,
e.g. 2 x 1,0 mm
2
WARNING!
The configuration of the core cross sections can
only
be defined by an installation specialist!
NOTICE!
For an existing block the heat pump by the
utility (utility switching) must be used the control
contact S 16 of the Smart-Control.
All cable insertions to the indoor module are
made from above!
All cable insertions to the outdoor module are
made from below!