REMKO HTL 170 Скачать руководство пользователя страница 21

21

Setting the pump pressure

The pump pressure should be 
adjusted, and checked if necessary, 
during burner commissioning and 
during every service. 

Adjust the pump pressure as follows: 

1.   Remove the stopper 

on the measurement nozzle 
"P".

2.   Fit a suitable oil pressure 

manometer here.

3.   Open all oil shut-off devices.

4.

 

 Switch on the burner.

5.   Set the required oil pressure in 

accordance with the nozzle size 
and the unit capacity.

6.   Switch off the burner after 

completing the adjustments.

7.   Remove the oil pressure 

manometer again.  
Re-fit stopper incl. seal.

HTL80 

Turning to the left

 (

)  

= smaller scale value

larger

 pressure behind 

the baffle plate

lower

 power range

Turning to the right

 (

+

)  

= larger scale value

smaller

 pressure behind 

the baffle plate

upper

 power range

HTL 170

Turning to the left

 (

+

)  

= larger scale value

smaller

 pressure behind 

the baffle plate

upper

 power range

Turning to the right

 (

)  

= smaller scale value

larger

 pressure behind 

the baffle plate

lower

 power range

Adjusting the secondary air
(nozzle fitting adjustment)

Carry out the presetting 
of the secondary air as follows:

Set the nozzle fitting 2 
to the desired value with 
the adjusting screw 1.

Air flap

3

4

1

2

All values provided are only preliminary settings and must be adapted or calibrated in accordance with the exhaust gas analysis.

The quantity of combustion air 
required is adjusted by means 
of the adjusting screw 3.
The air flap is set according 
to the unit capacity and the further 
burner settings.

Adjusting the air flap

Adjust the air flap as follows: 

1.   Loosen the knurled nut 4.
2.   Set the adjusting screw 3 

accordingly.

  Turn to the right = Less air

 

Turn to the left = More air

4.   After having set the adjusting 

screw 3 lock it again with 
the knurled knob 4.

Additional notes

   If the flame should give off 

sooty smoke or break away 
with a fully opened air flap, 
reduce the pressure behind 
the baffle plate with the help 
of the secondary air setting

   It may also be necessary 

to open the air inlet nozzle 
further

nOTE

Never let the pump run 
for extended periods without 
any fuel. Never leave the units  
for extended periods with 
a pump that has run dry.

ATTEnTiOn

If the burner should carry out 
a fault shut-down once again 
after the start phase, then 
another reset should be carried 
out after a waiting period 
of 5 minutes has passed. 

Further reset procedures must 
be prohibited as there is 
a danger of deflagration. 

Содержание HTL 170

Страница 1: ...Edition GB D09 REMKO HTL 80 HTL 170 Oil heating systems Operation Technology Replacement parts...

Страница 2: ......

Страница 3: ...errors or misprints Made by REMKO Safety notes 4 Unit description 5 Installation instructions 6 Safety device 7 Exhaust ducting 8 Before commissioning 9 10 Commissioning 10 11 Shutdown 11 Care and mai...

Страница 4: ...ashers etc Portable fuel containers must only be set up and used in observance of the technical rules for combustible liquids TRbF 20 Any additional conditions from the respective regional building re...

Страница 5: ...direction of the fan motor as standard With factory fitted forced air oil burners the HTL 170 units have integrated REMKO Multiflex oil pre heating fitted as standard With the HTL 80 this is availabl...

Страница 6: ...installed in well ventilated spaces and not in living areas or similar recreational areas Room heating The units may only be operated for room heating with a room thermostat accessory The fresh air su...

Страница 7: ...perature of ca 220 C is reached the fill medium will be emptied and the safety device is permanently triggered Resetting is no longer possible The controller is no longer fully functional and must be...

Страница 8: ...sories It is also possible to operate the units outside or in open rooms halls without exhaust gas routing However we recommend fitting a 1m exhaust gas duct with a rain hood on top example 2 in order...

Страница 9: ...ght left Mixed air operation For operation of the unit in mixed air mode it is necessary to fit the intake nozzles available as accessories In order to guarantee adequate air throughput the second int...

Страница 10: ...outside temperatures Even at low outside temperatures it is necessary to ensure that there is an adequate supply of heating oil that is capable of flowing Paraffin formation can start with temperatur...

Страница 11: ...atically after a brief burner pre ventilation if heat is required and then runs fully automatically Shutdown 3 1 4 Attention Never interrupt the power supply prior to the completion of the follow up c...

Страница 12: ...e defective parts properly replaced Check the fan blades and combustion chamber with heat exchanger for contamination at regular intervals and clean these if necessary Check the on site oil tank regul...

Страница 13: ...rner flange Observe dimensions in the sketch 6 Clamp the flame tube firmly into place with the clamping screw 7 whilst lifting the burner slightly 3 tilt 7 Lastly tighten the bottom 2 fastening screws...

Страница 14: ...routing when operating with hoses Air inlets or outlets are not free or are inadequate 8 Check whether the Burner fault indicator light on the control panel is illuminated If this is the case then re...

Страница 15: ...als are processed the majority of which are recyclable You also contribute to environmental protection by ensuring that your old equipment is only disposed of in an environmentally friendly manner The...

Страница 16: ...61 20 24 3 2 12 13 32 34 35 42 46 47 50 52 51 53 54 55 70 We reserve the right to modify the dimensions and design as part of the ongoing technical development process 12 61 Temperature probe REMKO Mu...

Страница 17: ...4 Sealing cap 1104728 1104784 35 Centre wall 1104841 1104862 36 Intake grill right left 1104842 1104863 40 Back wall 1104843 1104864 41 Switching cabinet cmpl 1104783 1 1104865 42 Seal for switching c...

Страница 18: ...2 2 4 4 2 4 3 1 HW 07 13 N PE L1 N 230 V 50 Hz C 5 V Option EDV Nr 1071411 A B 11 14 31 34 12 32 Legend C Capacitor H1 Operating lamp green H2 External burner fault lamp red HR Auxiliary relay KL Ter...

Страница 19: ...temperature limiter X1 Terminal block M Fan motor WS Burner connector 7 pole RT Thermostat receptacle V Multiflex oil pre heating 1F3 1 Controller fuse 2K2 1 Mains fuse 2K2 2 Time relay 2K3 1 Mains fu...

Страница 20: ...setting must be adapted to the unit specific and structural conditions A B M G Fig 2 M G Fig 1 Size dimensions A B C D HTL 80 5 5 7 3 HTL 170 7 8 5 3 Required nozzle size The selection of the require...

Страница 21: ...fitting 2 to the desired value with the adjusting screw 1 Air flap 3 4 1 2 All values provided are only preliminary settings and must be adapted or calibrated in accordance with the exhaust gas analy...

Страница 22: ...only by authorised specialists and in accordance with the legal provisions 1st BImSchV A corresponding measurement log should be generated Unit to be maintained only by authorised specialists in accor...

Страница 23: ...10 340 Max total pressure Pa 410 520 Fuel Heating oil EL acc to DIN 51603 1 or diesel fuel Max fuel consumption l h 8 3 15 5 Danfoss oil nozzle2 USG 1 75 60 S 3 00 80 S Pump pressure approx 2 bar 12 1...

Страница 24: ...ust be advisers to our customers in air conditioning and heating technology Customer service Our units operate precisely and reliably However in the event of a malfunction REMKO customer service is qu...

Отзывы: