15

Commissioning

1.

 

Check all connections, even those 
which were sealed at the factory 
(flange, anode sleeve), for leak-
tightness.

2.

 

Then check all pipes for any leaks 
and, if necessary, fix them.

3.

 

Test the safety module and valves 
between the cold water supply and 
hot water tank for function. 

During initial filling, the discharge 
valve must be open. The warm water 
tank is fully filled, when water which is 
free of bubbles starts to run out of the 
discharge pipe of the valve. 

Once the water has been heated 
successfully, the set temperature, 
the actual temperature of the water 
produced and that shown on any 
temperature indicator should be 
approximately the same. 

Commissioning should only be 

performed and documented by 

specially trained personnel.

      NOTE

Heating the water in the tank causes its 
volume to increase.
During the heating process, 
the expansion water generated in 
the internal boiler should drip out of 
the safety valve. 
This dripping is necessary to the function 
of the unit, and must not be prevented 
by retightening the valves.

4.

 

Test the self-actuating shut-off of 
the system, any installed electrical 
heating attachments and/or 
the boiler.

 

    ATTENTION

The warm water drain pipe as well 
as parts of the safety equipment 
may become hot.

Содержание EWS 300

Страница 1: ...REMKO TANK SYSTEMS Tank for process hot water EWS 300 Operation Technology Edition GB W12...

Страница 2: ......

Страница 3: ...g manual is a translation of the German original Subject to modifications no liability accepted for errors or misprints Safety notes 4 Environmental protection and recycling 5 Warranty 5 Intended use...

Страница 4: ...can cause malfunctions Units and components may not be operated in areas where there is an increased risk of damage Observe the minimum clearances Safety notes The electrical supply is to be adapted t...

Страница 5: ...torage of hot water Any different or additional use shall be classed as non intended use The manufacturer supplier assumes no liability for damages arising from such use The user bears the sole risk i...

Страница 6: ...k hot water may escape ATTENTION When placing the tank back into service ensure that it is filled with water and that water which is free of bubbles is escaping from the valves Permanent decommissioni...

Страница 7: ...a specialist at least once every 2 years of operation and this inspection must be documented If servicing tasks are performed the cleaning and servicing flange should be opened and the tank inspected...

Страница 8: ...f the water the nominal capacity in order to ensure that the statics of the load bearing surface are not exceeded Ensure proper clearance from firing systems Installation may only be performed by auth...

Страница 9: ...pumps fin tube heat exchangers electric heaters must be electrically insulated from the tank For the protection of the above mentioned plug in built in components against the current induced corrosion...

Страница 10: ...nnection pressure tight The hot water heaters are pressure tight tanks for which pressure tight connections can be made If the line pressure is higher a customer provided pressure reducing valve must...

Страница 11: ...w restrictor installed between the safety valve and the cold water feed of the tank The safety valve must be set to a triggering pressure which is below the nominal pressure of the tank After the conc...

Страница 12: ...ue to significant energy loss a circulation connection should be avoided when possible If a highly branched service water network requires a circulation line this must be well insulated and the circul...

Страница 13: ...uit ATTENTION However under no circumstances may the supply and return lines be blocked as otherwise the water in the register will not have room to expand and there is a risk of damage to the heat ex...

Страница 14: ...missioning Before being placed into service the register must be flushed in order to remove any soiling e g scale from the heating circuit The smooth pipe heat exchanger register must be rinsed out pr...

Страница 15: ...et temperature the actual temperature of the water produced and that shown on any temperature indicator should be approximately the same Commissioning should only be performed and documented by specia...

Страница 16: ...with 50 C tank temperature and 45 C tap temperature Screw in heater installation depth EWS 300 I F A B C E 85 G H Unit type Dimensions in mm H D A B C E F G I EWS 300 1435 680 320 840 990 1160 345 11...

Страница 17: ...e C 10 10 10 10 Heating circuit flow rate l h 600 1200 1800 2400 Cycle output kW 16 0 22 7 26 4 28 8 Supply temperature C 60 60 60 60 Hot water temperature C 50 50 50 50 Cold water temperature C 10 10...

Страница 18: ...18 REMKO EWS 300 Notes...

Страница 19: ...19...

Страница 20: ...reserve the right to make technical changes and provide no warranty as to the accuracy of this data REMKO GmbH Co KG Air conditioning and heating technology Im Seelenkamp 12 D 32791 Lage Postfach 1827...

Отзывы: