background image

Starting 

A humidity of 45% to 60% is sufficient for residential 
rooms; a humidity of 40% to 45% should not be ex-
ceeded in storage rooms, archives, etc.  

Regulation with Hygrostat

 

The integrated hygrostat controls the switching functions 
for automatic operation. 

Starting the unit 

After moving the unit, wait at least five minutes 
before starting it to prevent damage to the com-
pressor. 

G

 

Insert the power plug into a cor-
rectly fused plug socket.  

230V/1~ 50 Hz / 10 A fuse.

 

Ensure that the plug S is correctly 
installed in the hose connector on 
the rear of the unit. 

Turn the knob on the operating 
panel counterclockwise to the 
“OFF” position. 

Select the required humidity with 
the hygrostat.  

Approximate values:

 

        CONT.         

ð

         20 % r. F. 

        OFF             

ð

         80 % r. F. 

        white area    

ð 

 

40 % r. F. 

Installation 

 

Install the unit in a horizontal position to ensure the 
trouble-free drainage of condensate. 

Install the unit in the middle of the room, if possible, 
to ensure optimal air circulation. 

If this is not possible due to the on-site situation, 
please ensure that the air can be drawn into the front 
of the unit and exhausted at the back or the top air 
control flap without obstructions. 

Make sure to observe a minimum distance of 50 cm 

Do not install the unit directly near radiators  
or other heat sources. 

Make sure to keep the room to be dried and 
dehumidified closed, so that air from outside cannot 
penetrate into it. 

Entering into and going out of the room should be 
avoided if possible. 

You can obtain better air circulation if you place the 
unit at a height of approx. 1 m. 

Important Hints! 

Make sure that appropriate measures for mainte-
nance and care are taken when the unit is installed 
in dusty surroundings as well as in stables with am-
moniacal atmosphere  

See chapter “Maintenance and Care”. 

The electrical connection of the unit is to be carried 
out according to DIN VDE 0100, part 704. It is to be 
connected to service entrances with residual current 
operated device. 

If the unit is installed in washhouses, showers or 
similar wet areas the user has to protect it by an ade-
quate residual current operated device according to 
the relevant regulations. 

G

 

The filter of the unit is to be controlled and 
cleaned thoroughly before every use. If the air 
suction grille is dirty, please cleaned it up like 
shown in chapter ”Maintenance and Service”.

 

Important Hints:

 

Connection cable extensions may only be used 
when they have been completely unrolled. 

If the condensat tank is  not fitted correctly, the unit 
will not run. 

minimum distance of 0,5 m

 

Please keep distance to the 

 

radiator or other heating sources

 

keep the 

window 

closed 

keep the 

door 

closed 

Содержание ETF 100

Страница 1: ...REMKO powerful like a bear REMKO ETF 100 150 Mobile Dehumidifier Edition GB M02 Operation Technology Spare Parts ...

Страница 2: ......

Страница 3: ...without our prior consent Subject to alterations Operating Instructions Contents page Air Dehumidification 4 Safety Instructions 6 Unit Description 7 Installation 8 Starting 8 Discard the Unit 10 Transport Instructions 10 Cleaning the Filter 11 Contents page Maintenance and Service 11 Exploded View 12 Spare Part List 13 In Case of Troubles 14 Technical Data 14 Wiring Diagram 14 Maintenance and Ser...

Страница 4: ...r kg of dry air absolute water content 1 m of air weighs approx 1 2 kg at 20 C Depending on the temperature each kg of air can only absorb a defined quantity of water vapour When this quantity has been absorbed the air is saturated and has a relative humidity of 100 By relative air humidity we understand the relation be tween the percentage of water vapour contained in the air at the moment concer...

Страница 5: ...On the other hand energy is re leased when gas is liquefied and this energy is called condensation heat The energy rate of evaporation and condensation heat is identical For water this is 2250 kJ kg 4 18 kJ 1kcal This shows that a relatively high energy rate is released through water vapour condensation If the humidity to be condensed is not generated by evaporation within the room but fed from th...

Страница 6: ...condensation tank before moving the unit Do not set the unit up near curtains or drapes Maintain a safety distance of at least 50 cm min 50 cm Ensure that the unit is set up at a safe distance from flammable mate rials Ensure that the dehumidifier is sol idly set up on a level surface The unit may only be operated in an upright position Do not attempt to use the unit while lying on its side or in ...

Страница 7: ...a tion of the room air through the unit will thus reduce the humidity in the room to the desired relative humidity Depending on the air temperature and relative humidity condensation either drips into the condensation trap continuously or during the periodic defrosting phases From there it passes through the integrated outlet into the condensation tank located below it Condensation can also be rel...

Страница 8: ...tall the unit directly near radiators or other heat sources Make sure to keep the room to be dried and dehumidified closed so that air from outside cannot penetrate into it Entering into and going out of the room should be avoided if possible You can obtain better air circulation if you place the unit at a height of approx 1 m Important Hints Make sure that appropriate measures for mainte nance an...

Страница 9: ...rol lamp OPERATION in dicates the correct function of the unit BETRIEB OPERATION To open the flap tap the corrugated surfaces The top side will tip downward per mitting you to adjust the air flow direc tion as required Ensure that the air outlet is unob structed and that sensitive objects such as plants are not directly in the path of the air stream Remove the small grille lid to fill the dispense...

Страница 10: ...rform these steps in reverse order Remove the plug S from the connector on the rear of the unit S Attach a sufficiently long hose to the connector The condensa tion can now be allowed to flow into a drain for example during unattended continuous opera tion To prevent spillage ensure that the plug is cor rectly positioned G Remove the condensation tank and close the drain A below the condensation t...

Страница 11: ...ook the filter holder at the rear only ETF 150 5 Remove only ETF 150 the charcoal filter and replaced as required The charcoal filter insert cannot be cleaned Charcoal filter Filter holder Filter frame with filters 6 Clean the air intake filter in the filter frame With lukewarm water Dirty side down With a vacuum cleaner Dirty side up 7 Clean heavily contaminated fil ters in lukewarm max 40 C soap...

Страница 12: ...12 Exploded View We reserve the right to make changes to the design and dimensions in the interest of technical progress ...

Страница 13: ...essor complete 1103548 38 Accumulator 1103547 39 Rear panel 1103555 40 Support brace 1103538 41 Solenoid 1103530 42 Fan cover 1103539 43 Dry filter 1103549 44 Control board 1103541 45 Display board 1103542 46 Power board 1103543 47 Transport handle 1103544 No Designation Ref No ETF 150 Ref No 1103502 1103503 1103504 1103505 1103506 1103507 1103508 1103509 1103545 1103501 1103510 1103511 1103512 11...

Страница 14: ... than the humidity in the room Unit running no condensation formation Check room temperature The working range of the unit is between 6 C and 32 C Check relative humidity Min 40 Check hygrostat setting and choose a lower setting if required Check air intake filter charcoal filter for contamination Clean or replace as required Check exchanger blades for soiling Lei it clean as required Vaporizer is...

Страница 15: ...e 7 Date 8 Date 9 Date 10 Date Signature Signature Signature Signature Signature 11 Date 12 Date 13 Date 14 Date 15 Date Signature Signature Signature Signature Signature 16 Date 17 Date 18 Date 19 Date 20 Date Signature Signature Signature Signature Signature Unit cleaned exterior Unit cleaned interior Condenser cleaned Vaporizer cleaned Fan blades cleaned Dust filter cleaned or replaced Protecti...

Страница 16: ...REMKO GmbH Co KG Klima und Wärmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 ...

Отзывы: