REMKO ATR-4 Скачать руководство пользователя страница 8

Setting the Functions

 

When you press the

 PROG 

program button for 6 

seconds, you are taken to a menu where various 
basic functions can be set. The functions are 
shown on the left-hand side of the display and 
the corresponding value or status on the right. 

When you press the 

SET 

program button, you are taken to the desired set-

ting option. The setting option blinks on the display. 
By pressing the 

+

 or 

– 

program buttons, the value of the selected setting op-

tions can be changed and your selection confirmed by pressing the 

SET

 

button. 
After confirming the last function, the unit returns to the operating mode from 
which the 

Setting the Functions

” 

menu was accessed. 

The individual parameters mean the following:

 

Setting the Control Parameters

 

When you press the

 PROG 

program button for 6 

seconds, you are taken to a menu where various 
basic functions can be set. The functions are 
shown on the left-hand side of the display and 
the corresponding value or status on the right. 

When you press the 

SET 

program button, you are taken to the desired set-

ting option. The setting option blinks on the display. 
By pressing the 

+

 or 

– 

program buttons, the value of the selected setting op-

tions can be changed and your selection confirmed by pressing the 

SET

 

button. 
After confirming the last function, the unit returns to the operating mode from 
which the 

Setting the Control Parameters

” 

menu was accessed. 

The individual parameters mean the following:

 

When used as a two-point control mechanism:

 

Parameter 

Default setting  Minimum value  Maximum value 

Activation difference

 

± 1.0 K

 

± 0.1 K

 

± 3.0 K

 

Per proportional control

 

± 3.0K

 

± 1.0 K

 

± 10.0 K

 

Pulse width

 

5 min

 

1 min

 

15 min

 

When used as a pulsating control mechanism:

 

Содержание ATR-4

Страница 1: ...REMKO ATR 4 Electronic Clock Thermostat Edition GB H12 Operation Technology Original REMKO REMKO powerful like a bear...

Страница 2: ......

Страница 3: ...are made to the supplied unit Electronic Clock Thermostat REMKO ATR 4 Important Always keep these operating instructions near or on the unit Contents Page Functionality 4 Operating Controls 4 Comfort...

Страница 4: ...left hand side of the display shows the operating mode Comfort Temperature The desired comfort temperature 5 to 40 C is set on the upper rotating knob 2 It is displayed on the right hand side of the...

Страница 5: ...ed on the right hand side of the display The unit continues to record the current temperature but all control functions are completely switched off Hand Button The button makes it possible to change t...

Страница 6: ...again Selecting the Operating Mode The main operating modes are selected by pressing one of the three program buttons on the left You can select from the following modes Automatic Comfort continuous...

Страница 7: ...fect When you press the SET program button you are taken to the desired set ting option Program point number Time Day Temperature mode Each selected setting option blinks on the display By pressing th...

Страница 8: ...you press the PROG program button for 6 seconds you are taken to a menu where various basic functions can be set The functions are shown on the left hand side of the display and the corresponding val...

Страница 9: ...eating Co cooling 2PPu 2 point Pulsating function display When the control function is switched from 2 point to pulse and vice versa this results in the corresponding parameters being calculated on th...

Страница 10: ...nductors from becoming loose that meets the requirements of EN 60730 Part 1 This can be achieved for example by securing the lines with cable bindings Compliance with VDE 0100 EN 60730 Part 1 as well...

Страница 11: ...of the housing If the entire panel is removed it is possible that the housing no longer com pletely closes M O DI M I DO F R SASO M O DI M I DO F R SASO G Note The electronic clock thermostat must be...

Страница 12: ...REMKO heater is made at terminals 1 and 3 For cooling units to terminals 1 and 2 G Caution There must be a power current of 230 V 50 Hz at terminals 6 and 7 at all times for the unit to function We re...

Страница 13: ...P15 P16 The following tables can be used to enter individual customer data Customer Data Timer program Control parameters Activation difference or Proportional control Pulse duration Functions Sensor...

Страница 14: ...timer Power reserve 1 approx 15 minutes Display LC display Operating current 230 V AC 10 Power consumption approx 2VA Relay contact 1 isolated change over contact Max supply of switch current 10 4 A 2...

Страница 15: ......

Страница 16: ...REMKO GmbH Co KG Klima und W rmetechnik D 32791 Lage Im Seelenkamp 12 D 32777 Lage PO Box 1827 Phone 49 5232 606 0 Fax 49 5232 606260 E Mail info remko de Internet www remko de...

Отзывы: