General

Furnish packaged terminal (air conditioners) (heat
pumps) of the sizes and capacities shown on the sched-
ule and/or specifications. The units shall be located as
shown in the drawings and each shall include wall
sleeve, outdoor louver, heating/cooling chassis, front
panel and subbase (optional 208/230v).

All units shall be ETL and CETL listed for safety and 
ARI certified for capacity and performance. Units shall be
Remington

®

Model designated with prefix (PTAC) (PTHP)

or equal.

Overall dimensions for the basic unit (excluding louver)
shall not exceed 42" wide, 16" high and 20

3

/

4

" deep.

Standard wall sleeve dimensions shall not exceed 16"
high, 42" wide and 13

3

/

4

" deep. Units furnished with an

electrical subbase shall not exceed 42" wide, 20" high
and 20

3

/

4

" deep.

Units shall be designed to operate on (208/230)
(265/277) volts, 60 Hz, single-phase power.

The E.E.R. shall be from 11.6 to 9.2 and COP from 3.4 
to 2.8.

Heating/Cooling Chassis

Chassis shall be slide-in, plug-in type with a self-con-
tained, hermetically sealed refrigerant circuit. All 
chassis sheet metal parts shall be coated with a poly-
ester based powder paint or galvanized for maximum
corrosion resistance.

The chassis shall consist of the following components:
vibration isolated, permanent split capacitor rotary-type
compressor, rifled copper tubed evaporator and con-
denser coils with high efficiency raised lance aluminum
plate fins that are hydrophilic coated to resist corrosion
and mechanically expanded to the tubes for maximum
heat transfer and a capillary restrictor type refrigerant
metering device. Coils shall be factory tested at 300 psig
(heat pump models shall also include reversing valve
and charge balancing device).

A positive-closing, manual fresh air damper shall be
included within the chassis to provide the option of fresh
air during operation.

System airflow shall be accomplished by the use of the
separate outdoor and indoor fan motors. Motors shall be
permanent split capacitor, totally enclosed and perma-
nently lubricated. A single speed motor shall directly
drive the outdoor fan. The outdoor fan shall be construct-
ed out of high impact resistant polymer and consist of
multiple propeller-type blades with a slinger ring
designed to efficiently remove condensate. The indoor

fan assembly shall consist of a single centrifugal fan that
is forward curved and directly connected to a two-speed
motor. All fans shall be statically and dynamically bal-
anced to provide for quiet and smooth operation.

During the cooling cycle, the compressor and both fan
motors shall be energized. Condensation accumulated
on the indoor coil shall be drained into the outdoor 
section of the unit where it is to be picked up by the out-
door fan and transferred to the outdoor coil where it 
shall then be evaporated to enhance units' capacity and
efficiency.

(Electric Resistance Heat Only Models) During the 
heating cycle, only the indoor fan motor and the electric
resistance heaters are energized. The compressor shall
not be energized. Heaters shall be high mass cal-rod
type with high limit cutout. Electric resistance heaters
shall be universal in design such that the type of power
cord specified with the heating/chassis determines the
respective heater size as shown in the schedule and/or
specifications. Electric resistance heaters must be locat-
ed behind the indoor coil and must not be visible or
accessible through the indoor discharge grille.

(Reverse Cycle Heat Pump Models) During the heating
cycle, the reversing valve, compressor and both fan
motors will be energized. Depending on the outdoor air
temperature, two distinct heating modes shall be avail-
able. Namely, compressor only or electric heat only.
Minimum outdoor temperature for compressor operation
shall be 25°F. Between outdoor temperature of 25°F and
45°F, the compressor and electric heater will alternate as
required to maintain indoor temperature. When the out-
side temperature is below 25°F, the electric heat-only
mode shall be utilized. The electric heaters shall be high
mass cal-rod type with high limit cutout. Electric resist-
ance heaters shall be universal in design such that the
type of power cord specified with the heating/chassis
determines the respective heater size as shown on the
schedule and/or specifications. Electric resistance
heaters must be placed behind the indoor evaporator coil
and must not be visible or accessible through the indoor
discharge grille. Condensation accumulated on the out-
door coil during reverse cycle heating MUST not be
evaporated against the indoor coil as it could contami-
nate the indoor air with pollutants and odors.
Condensation accumulated during reverse cycle heating
shall transfer from chassis into wall sleeve by means of a
thermostatically controlled drain valve. Condensate shall
exit wall sleeve via weep holes or optional indoor/outdoor
drain kit.

Engineering Guide Specifications - Remington

®

Model

Содержание Amana PTC

Страница 1: ...Packaged Terminal Air Conditioners and Heat Pumps Architects and Engineers Manual...

Страница 2: ...p Front Cleanable Filter Standard Standard Standard Standard Standard Standard Standard Standard Automatic Indoor Frost Control Standard Standard Standard Standard Standard Option Corrosion Treated Ch...

Страница 3: ...llation page 14 Drain Kit Installation page 15 Unit Dimensions page 16 Table of Contents Bi Directional Discharge Grille High Efficiency Refrigeration Coils Chassis Fits Any Standard 16 H x 42 W x 133...

Страница 4: ...Costs The overall system design is greatly simplified allowing designers to devote more time to other areas and reducing overall costs Architectural Design Freedom Eliminates the need for large mecha...

Страница 5: ...ditional labor required to enable the damper Extra Humidity Control Remington is the only AC manufacturer to offer the Cool Dry Dehumidification Mode standard on all units The system is designed to pr...

Страница 6: ...H x 42 W x 133 4 D wall opening Remington conditioners are compatible with most existing wall thermostats and remote control interfaces for added savings on installation labor and costs Insulated wall...

Страница 7: ...for guest comfort and energy savings Automatically controls unit shut off after a specified time 1 to 15 hours Adjustable minimum and maximum room temperature set points Allows wireless remote contro...

Страница 8: ...ectly connected to a two speed motor All fans shall be statically and dynamically bal anced to provide for quiet and smooth operation During the cooling cycle the compressor and both fan motors shall...

Страница 9: ...ours This will automatically compensate for the cold or warm radiation effect felt from the mass in the walls floor and furnishings until they normalize The 2 F offset is maintained for the first cycl...

Страница 10: ...disconnects are also available To ease field installation subbase must have adjustable side channels with predrilled adjusting holes and score lines Additionally subbase shall have adjustable levelin...

Страница 11: ...65V models and is optional for 208V 230V models Figure 1 shows the subbase and dimensions Power Supply Wiring All wiring must be done in accordance with all local and National Electrical Code requirem...

Страница 12: ...select the number of hours 1 15 after which the unit will turn off To turn the unit on preset the unit to the desired mode and temperature and turn it off Press the TIMER key repeatedly to select the...

Страница 13: ...ll sleeve applications 111 2 D that do not conform to industry standard depth 133 4 D Drain Kits Internal or external mounted drain kits Pre drilled wall sleeve simplifies drain kit installation Subba...

Страница 14: ...Amps 18 5 20 7 18 0 18 5 20 7 18 5 Capacity Btuh 7 100 7 400 7 300 8 900 8 900 8 900 11 000 11 400 11 400 14 000 14 500 14 400 Cooling EER 11 6 11 5 10 7 10 6 10 4 10 4 10 0 9 9 10 1 9 3 9 3 9 2 Full...

Страница 15: ...Page 13 Wiring Diagrams Model PTAC 07B 09B 12B 15B...

Страница 16: ...wall and panel wall applications for positive anchoring to the wall For thicker walls wall sleeve extensions are available from your local Remington representative Air splitters must be included in w...

Страница 17: ...wall sleeve has been installed Note When using the ex ternal drain kit the sleeve must be flush or beyond the out side finished wall do not recess Install the external drain kit as follows 1 Assemble...

Страница 18: ...available in 3 or 4 height with depth adjustable from 43 8 to 133 4 Unit pictured with subbase installed but can also be floor mounted without subbase for 208V 230V applications Side View Top View Fro...

Страница 19: ...m Blue MGN Medium Green SPECIAL COLOR We can match your color A color chip or sample should be sent to our Customer Service Department A sample chip will be returned to you for your approval Please co...

Страница 20: ......

Отзывы: