Checking/setting values for O
2
/CO
2
at full load
1. Measure the percentage of O
2
/CO
2
in the flue gases.
2. Compare the measured value with the checking values in the table.
Tab.28 Checking/setting values for O
2
/CO
2
at full load for G20 (H
gas)
Values at full load for G20 (H
gas)
O
2
(%)
CO
2
Quinta Pro 30
4,3 - 4,8
9,0
- 9,3
Quinta Pro 45
4,3 - 4,8
9,0
- 9,3
Quinta Pro 55
4,3 - 4,8
9,0
- 9,3
Quinta Pro 65
4,3 - 4,8
9,0
- 9,3
Quinta Pro 90
3,4 - 3,9
9,5
- 9,8
Quinta Pro 115
4,2 - 4,7
9,1
- 9,4
(1) Nominal value
Tab.29 Checking/setting values for O
2
/CO
2
at full load for G31
(propane)
Values at full load for G31 (pro
pane)
O
2
(%)
CO
2
Quinta Pro 30
4,1 - 4,6
10,7
- 11,0
Quinta Pro 45
4,1 - 4,6
10,7
- 11,0
Quinta Pro 55
4,1 - 4,6
10,7
- 11,0
Quinta Pro 65
4,1 - 4,6
10,7
- 11,0
Quinta Pro 90
4,1 - 4,6
10,7
- 11,0
Quinta Pro 115
4,4 - 4,9
10,5
- 10,8
(1) Nominal value
Caution
The O
2
values at full load must be lower than the O
2
values at
low load.
The CO
2
values at full load must be higher than the CO
2
values
at low load.
3. If the measured value is outside of the values given in the table, cor
rect the gas/air ratio.
4. Using adjusting screw A, adjust the percentage of O
2
/CO
2
for the
gas type being used to the nominal value. This should always be in
side the highest and lowest setting limit.
Fig.40
Position of adjusting screw A
AD-0000067-01
A
A
7 Commissioning
46
123157 - v.12 - 07022018