12

Remeha P 420

06/04/06 - 300008441-001-C

Chimney connection

The high-performance features of modern boilers and their use in
specific conditions as a result of the advance in burner technology
(e.g. first-stage or low modulation range operation) lead to very low
flue gas temperatures (<160°C).

For this reason :
- Use flue gas pipes designed to enable the flow of condensates

which may result from such operating modes in order to prevent
damage to the chimney.

- Install a draining tee at the bottom of the chimney.

The use of a draught moderator is recommended as well.

1 Flue  size

Refer to applicable regulations while determining the size of the flue.
Please note that P 420 boilers have pressurised and tight furnaces
and that the pressure at the nozzle must not exceed 0 mbar, unless
special sealing precautions have been taken, for instance in order to
connect a static condenser/regenerator.

2 Chimney connection

The connection shall be removable, and offer minimum load losses,
i.e. it must be as short as possible with no sudden change in section.
Its diameter shall always be at least equal to that of the boiler outlet,
i.e.:
ø 250 mm: for 7 to 10 sections
ø 300 mm: for 11 to 14 sections.

Содержание P 420

Страница 1: ...Remeha P 420 Fuel oil gas boilers Technical instructions English 06 04 06 63190 UK...

Страница 2: ...s for connecting the boiler to the heating circuit 10 3 Filling the system 11 4 Sludge removal 11 Chimney connection 12 1 Flue size 12 2 Chimney connection 12 Fuel oil or gas connections 13 Electrical...

Страница 3: ...engineering practice as requested in article 3 3 of the directive 97 23 EC it is certified by compliance with the directives 90 396 EC 92 42 EC 73 23 EC and 89 336 EC Warning The boiler shall be asse...

Страница 4: ...ned for connecting to a flue pipe which require a separate automatic fuel oil or gas burner The useful power of P 420 boilers is between 300 and 780 kW Models available Boiler with control panel which...

Страница 5: ...43 3 511 4 511 4 613 6 613 6 681 8 681 8 761 4 761 4 818 2 818 2 886 4 Number of sections 8 9 10 11 12 13 14 Water capacity l 366 409 452 495 538 581 624 Water resistance T 10K mbar 37 55 86 105 136 1...

Страница 6: ...plugged Boiler type P 420 8 P 420 9 P 420 10 P 420 11 P 420 12 P 420 13 P 420 14 A 250 250 250 300 300 300 300 B 2 1 2 2 1 2 2 1 2 3 3 3 3 C 135 175 190 240 250 290 or Plain plate D 235 235 235 254 2...

Страница 7: ...loor can support the weight of the boiler when it is fitted for operation If the boiler location is not determined precisely leave enough space around the boiler to facilitate monitoring and maintenan...

Страница 8: ...e particularly corrosive These compounds are present for example in aerosol sprays paints solvents cleaning products washing products detergents glues snow clearing salts etc Therefore Do not suck in...

Страница 9: ...Flow switch 6 Air separator 7 Automatic bleed valve 9 Isolation valve 10 3 way mixing valve 11 Boiler pump 12 Sludge decanting pot particularly recommended on older installations 13 Flush valve 14 Wa...

Страница 10: ...the following formulae Nominal water flow Qn 0 86 Pn 20 Minimum flow Qmin 0 86 Pn 45 this flow also corresponds with the minimum recycle flow in the boiler Maximum water flow Qmax 0 86 Pn 5 Qn flow in...

Страница 11: ...y to an expansion vessel which opens out onto the air the system must include manual bleeder valves in addition to automatic bleeder valves with the capability to bleed the system by themselves when i...

Страница 12: ...tom of the chimney The use of a draught moderator is recommended as well 1 Flue size Refer to applicable regulations while determining the size of the flue Please note that P 420 boilers have pressuri...

Страница 13: ...lation of the burner door 1 Max attachment diameter Max B 290 mm Max B 330 mm with 4 fastenings at 15 or 45 Refer to the instructions supplied with the burner Electrical connections ZRefer to the conn...

Страница 14: ...d as soon as required and as the chimney at least once a year or more depending upon applicable regulations and specific needs Cut the power supply to the boiler Remove the upper front panel Open the...

Страница 15: ...am below The 8 figure part number of the baffle plate is moulded into the metal Flue ways P 420 8 P 420 9 P 420 10 P 420 11 P 420 12 P 420 13 P 420 14 Upper 8229 0010 and 8229 0022 2 x 8229 0010 2 x 8...

Страница 16: ...leaning hatches 2 Cleaning the casing material Use a soapy solution and a sponge only Rinse with clean water and dry with chamois leather or a soft cloth 3 Precautions required in the case of long boi...

Страница 17: ...operation should be required only a few times in each heating season with very low quantities of water otherwise look for the leak and repair it 2 Draining We advise you against draining the system un...

Страница 18: ...18 Remeha P 420 06 04 06 300008441 001 C Spare parts P 420 To order a spare part quote the reference number next to the part required 10 02 06 UK 300004749 002 B Boiler body...

Страница 19: ...19 06 04 06 300008441 001 C Remeha P 420 Cladding...

Страница 20: ...20 Remeha P 420 06 04 06 300008441 001 C Insulating material for body Panel RC 1...

Страница 21: ...with opening 175 19 8229 0531 Plate for combustion chamber door with opening 190 19 8229 0533 Plate for combustion chamber door with opening 240 19 8339 0509 Plate for combustion chamber door with op...

Страница 22: ...8545 8003 Complete side panel left width 610 mm 112 8545 8005 Complete side panel left width 930 mm 113 8545 8007 Complete front side panel right 114 8545 8000 Complete side panel right width 610 mm...

Страница 23: ...23 06 04 06 300008441 001 C Remeha P 420...

Страница 24: ...ctions as well as any drawings and technical descriptions supplied remain our property and shall not be multiplied without our prior consent in writing Ours is a policy of continuous development We re...

Отзывы: