For the dimensions of C/C1, see page 16.
A technical clearance of at least 80cm is required at the front (service side) of the
boiler. However, we recommend that the clearance is at least 100cm. We
recommend a clearance of at least 40cm above the boiler. If the air supply filter is
used, there must be a clearance of at least 65cm. A minimum of 30cm is
required on the side of the flue gas discharge, and a minimum of 30cm is also
required on the other side, or 80cm, if this is the operating side.
T003768-E
*Spacing required if this is operating side.
21
MAINTENANCE
AREAS
GAS 610
ECO PRO
MAINTENANCE
AREAS
C + 1100*
C + 600
C
300
300
800*
80
0*
14
50
80
0*
152
5*
30
50
*
60
0
C
C
30
0
30
0
80
0*
D
E*
80
0*
800*
800*
1450
Service Area