Align the legs of the draft hood with the slots provided. 

Insert the legs and secure the draft hood to the water 

heater’s top with the four screws provided as shown in 

Figure 9. Do not alter the draft hood in any way. If you are 

replacing an existing water heater, be sure to use the draft 

hood supplied with this water heater.

Vent Pipe Size                                                               

It is important that you follow the guidelines in these 

instructions for sizing a vent pipe system. If a transition 

to a larger vent size is required, the vent transition 

connection must be made at the draft hood outlet.

Vent Connectors                                                          

1.  Type B, Double wall, U.L. Listed Vent Pipe.
2.  Single wall Vent Pipe.
Maintain the manufacturer’s specified minimum clearance 

from combustible materials when using type B double wall 

vent pipe.
Vent connectors made of type B, double wall vent pipe 

material may pass through walls or partitions constructed 

of combustible material if the minimum listed clearance is 

maintained.
Maintain a six inch minimum clearance from all 

combustible materials when using single wall vent pipe.
IMPORTANT: Single wall vent pipe cannot be used for 

water heaters located in attics and may not pass through 

attic spaces, crawl spaces or any confined or inaccessible 

location. A single wall metal vent connector cannot pass 

through any interior wall.
When installing a vent connector, please note the following 

(See Figures 10-12):
• 

Install the vent connector avoiding unnecessary bends, 

which create resistance to the flow of vent gases.

• 

Install without dips or sags with an upward slope of at 

least 1/4-inch per foot.

• 

Joints must be fastened by sheet metal screws or other 

approved means. It must be supported to maintain 

clearances and prevent separation of joints and 

damage.

• 

The length of the vent connector cannot exceed 75% of 

the vertical vent height.

• 

The vent connector must be accessible for cleaning, 

inspection, and replacement.

• 

Vent connectors cannot pass through any ceiling, floor, 

firewall, or fire partition.

• 

It is recommended (but not mandatory) that a minimum 

12 inches of vertical vent pipe be installed on the draft 

hood prior to any elbow in the vent system.

IMPORTANT: Existing vent systems must be inspected for 

obstructions, corrosion, and proper installation.

Chimney Connection                                                  

IMPORTANT: Before connecting a vent to a chimney, 

make sure the chimney passageway is clear and free of 

obstructions. The chimney must be cleaned if previously 

used for venting solid fuel appliances or fireplaces. Also 

consult local and state codes for proper chimney sizing 

and application or, in the absence of local and state 

codes, the “National Fuel Gas Code”, ANSI Z223.1(NFPA 

54)-current edition.

• 

The connector must be installed above the extreme 

bottom of the chimney to prevent potentially blocking 

the flue gases.

• 

The connector must be firmly attached and sealed to 

prevent it from falling out.

• 

To aid in removing the connector, a thimble or slip joint 

may be used.

• 

The connector must not extend beyond the inner edge 

of the chimney as it may restrict the space between it 

and the opposite wall of the chimney (Figure 10).

LISTED LINED
CHIMNEY

2 FT. MINIMUM ABOVE ANY OBJECT 
WITHIN 10FT. HORIZONTALLY

DO NOT EXTEND 
VENT BEYOND EDGE
OF CHIMNEY

VENT
CONNECTOR

 

3 FT. MINIMUM

 

MAINTAIN
CLEARANCE*

SEAL 

SLOPE

UP 1/4 IN.

PER FT.

MINIMUM

CHIMNEY TERMINATION VENT SYSTEM

SUPPORT
STRAP

FIGURE 10.

Do not terminate the vent connector in a chimney that has 

not been certified for this purpose. Some local codes may 

prohibit the termination of vent connectors in a masonry 

chimney.

Vertical Exhaust Gas Vent                                          

Vertical exhaust gas vents must be installed with 

U.L. listed type B vent pipe according to the vent 

manufacturer’s instructions and the terms of its listing. 
It must be connected to the water heater’s draft hood by a 

listed vent connector or by directly originating at the draft 

hood opening.
Vertical gas vents must terminate with a listed cap or 

other roof assembly and be installed according to their 

manufacturer’s instructions.
Gas vents must be supported to prevent damage, joint 

separation, and maintain clearances to combustible 

materials (Figures 11 and 12).
IMPORTANT: This gas vent must be terminated in a 

vertical position to facilitate the removal of the burnt gases.
An unused chimney flue or masonry enclosure may be used 

as a passageway for the installation of a gas vent (Figure 12).
Common (combined) venting is allowable with vertical type 

B vent systems and lined masonry chimneys as long as 

proper draft for the water heater is established under all 

conditions of operation. CAUTION: DO NOT common vent 

this water heater with any power vented appliance.
Figures 10-12 are examples of vent pipe system 

installations and may or may not be typical for your 

specific application. Consult the “National Fuel Gas Code”, 

NFPA 54, ANSI Z223.1-current edition and the guidelines 

set forth by prevailing local codes.

Содержание FVIR GAS WATER HEATER

Страница 1: ...diately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire department Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal inj...

Страница 2: ... 17 Combination Space Heating Potable Water System 17 18 Solar Installation 18 Important Information About this Water Heater 19 Operating Your Water Heater 20 25 White Rodgers Gas Valve Thernostat Lighting Instructions 20 RobertShaw Gas Valve Thermostat Lighting Instructions 21 Checking the Draft 21 Burner Flames 22 Emergency Shutdown 22 Water Temperature Regulation 22 23 Operational Conditions 23...

Страница 3: ...ity equivalent to a licensed tradesman in the fields of plumbing air supply venting and gas supply including a thorough understanding of the requirements of the National Fuel Gas Code as it relates to the installation of gas fired water heaters The service agency must also have a thorough understanding of this instruction manual and be able to perform repairs strictly in accordance with the servic...

Страница 4: ...void all ignition sources if you smell Natural or LP gas Do not expose water heater control to excessive gas pressure Use only gas shown on rating plate Maintain required clearances to combustibles Keep ignition sources away from faucets after extended period of non use Read instruction manual before installing using or servicing water heater ...

Страница 5: ...LED IN A CLOSED WATER SYSTEM M N L E P X Y MANIFOLD TUBE IGNITER WIRE MAIN BURNER PILOT TUBE THERMOCOUPLE IGNITER ROD U MANIFOLD BURNER ASSEMBLY MANIFOLD DOOR DISCHARGE PIPE DO NOT CAP OR PLUG 6 MAXIMUM AIR GAP FLOOR DRAIN GAS CONTROL KNOB WATER TEMPERATURE DIAL ADJUSTING DIAL TOP VIEW OFF POSITION PILOT POSITION ON POSITION S GAS CONTROL VALVE THERMOSTAT WHITE RODGERS GAS CONTROL KNOB WATER TEMPE...

Страница 6: ... future users of this water heater will need it for future reference Service to the FVIR System should only be performed by a qualified technician Examples of a qualified technician include licensed plumbers authorized gas company personnel and authorized service personnel IMPORTANT The manufacturer and seller of this water heater will not be liable for any damages injuries or deaths caused by fai...

Страница 7: ...n the area of the water heater leave the area immediately and call the fire department from a neighbor s home Do not attempt to clean the spill until all ignition sources have been extinguished Fire or Explosion Hazard WARNING Read instruction manual before installing using or servicing water heater Improper use may result in fire or explosion Maintain required clearances to combustibles Keep comb...

Страница 8: ...used in conjunction with a piped drain pan These devices are available from some plumbing supply wholesalers and retailers and detect and react to leakage in various ways Sensors mounted in the drain pan that trigger an alarm or turn off the incoming water to the water heater when water is detected Sensors mounted in the drain pan that turn off the water supply to the entire home when water is det...

Страница 9: ...tural gas water heater to an L P gas supply Do not connect an L P gas water heater to a natural gas supply Failure to follow these instructions can result in death explosion or carbon monoxide poisoning Explosion Hazard Gas Requirements IMPORTANT Read the rating plate to be sure the water heater is made for the type of gas you will be using in your home This information will be found on the rating...

Страница 10: ... in the occurrence of a leak in the system the gas will settle at floor level Basements crawl spaces closets and areas below ground level will serve as pockets for the accumulation of gas Before lighting an L P gas water heater smell all around the appliance at floor level If you smell gas follow the instructions as given in the warning on the front page When your L P tank runs out of fuel turn of...

Страница 11: ...by a qualified technician using the installation instructions Examples of a qualified technican include gas technicians authorized gas company personel and authorized service persons Failure to so do can result in death or carbon monoxide poisoning IMPORTANT Air for combustion and ventilation must not come from a corrosive atmosphere Any failure due to corrosive elements in the atmosphere is exclu...

Страница 12: ...e typical examples of each method Louvers and Grilles In calculating free area for ventilation and combustion air supply openings consideration must be given to the blocking effect of protection louvers grilles and screens These devices can reduce airflow which in turn may require larger openings to achieve the required minimum free area Screens must not be smaller than 1 4 mesh If the free area t...

Страница 13: ...ied by CSA International this certification applies to the vent damper device only and does not mean they are certified for use on this water heater U L recognized fuel gas and carbon monoxide CO detectors are recommended in all applications and should be installed using the manufacturer s instructions and local codes rules or regulations IMPORTANT If you lack the necessary skills required to prop...

Страница 14: ...ay is clear and free of obstructions The chimney must be cleaned if previously used for venting solid fuel appliances or fireplaces Also consult local and state codes for proper chimney sizing and application or in the absence of local and state codes the National Fuel Gas Code ANSI Z223 1 NFPA 54 current edition The connector must be installed above the extreme bottom of the chimney to prevent po...

Страница 15: ...e as specified under Closed System Thermal Expansion 5 Install a shut off valve in the cold water inlet line It should be located close to the water heater and be easily accessible Know the location of this valve and how to shut off the water to the heater 6 A temperature and pressure relief valve must be installed in the opening marked Temperature and Pressure T P Relief Valve on the water heater...

Страница 16: ...The use of valves that may cause excessive restriction to water flow is not recommended Use only 95 5 tin antimony or other equivalent solder Any lead based solder must not be used Piping that has been treated with chromates boiler seal or other chemicals must not be used Chemicals that may contaminate the potable water supply must not be added to the piping system Closed System Thermal Expansion ...

Страница 17: ...use with space heating applications If this water heater is to be used to supply both space heating and domestic potable drinking water the instructions listed below must be followed Temperature and Pressure Relief Valve Explosion Harzard Temperature pressure relief valve must comply with ANSI Z21 22 CSA 4 4 and ASME code Properly sized temperature pressure relief valve must be installed in openin...

Страница 18: ...ts previously used with non potable water heating appliances when used to supply potable water Some jurisdictions may require a backflow preventer in the incoming cold water line This may cause the temperature and pressure relief valve on the water heater to discharge or weep due to expansion of the heated water A diaphragm type expansion tank suitable for potable water will normally eliminate thi...

Страница 19: ...anges Questions Contact Residential Technical Assistance by referencing the phone number on the front of the Installation Instructions and Use Care Guide Installation Checklist Water Heater Location Water heater location is important and can affect system performance Please check the following Installation area free of corrosive elements and flammable materials Centrally located with the water pip...

Страница 20: ... above on this label Set the thermostat to lowest setting PILOT LIGHTING Turn thermostat dial fully clockwise until it stops Push the gas control knob down slightly and turn clockwise to OFF SEE FIGURE A NOTE Knob cannot be turned from PILOT to OFF unless knob is pushed down slightly Do not force Wait ten 10 minutes to clear out any gas If you then smell gas STOP Follow B in the safety information...

Страница 21: ...rve the pilot through the view port Do not release the reset button Repeat immediately if pilot does not light on the first try If the pilot does not light by the fourth attempt with the igniter repeat steps 4 7 Continue to hold the button for about 1 minute after the pilot is lit Release the reset button and it will pop back up Pilot should remain lit If the pilot light goes out repeat steps 3 7 ...

Страница 22: ...our hot water needs a means such as a mixing valve should be used at the hot water taps used by these people or at the water heater Mixing valves are available at plumbing supply or hardware stores see Figure 14 Follow manufacturer s instructions for installation of the valves Before changing the factory setting on the thermostat see Figure 19 Using the lowest hot water temperature that meets your...

Страница 23: ...e limit switch or ECO Energy Cut Off in the tank is used to shut off the unit if the water temperature exceeds 195 F 91 C The ECO is a single use switch which if activated requires complete replacement of the entire gas control valve thermostat If the ECO should activate the water heater cannot be used until the gas control valve thermostat is replaced by a qualified technician Contact your local ...

Страница 24: ...e the Repair Parts Illustration section for anode rod location TEFLON is a registered trademark of E I Du Pont De Nemours and Company Draining and Flushing It is recommended that the tank be drained and flushed every 6 months to remove sediment which may build up during operation The water heater should be drained if being shut down during freezing temperatures To drain the tank perform the follow...

Страница 25: ...owing maintenance procedures are for the FVIR System components and should be performed by a qualified technician Replacement parts may be ordered through your plumber or the local distributor Parts will be shipped at prevailing prices and billed accordingly When ordering replacement parts always have the following information ready 1 model serial and product number 2 type of gas 3 item number 4 p...

Страница 26: ...IGURE 25 FIGURE 26 Replacing the Pilot Pilot Tube Assembly 1 Remove the manifold burner assembly See Removing the Manifold Burner Assembly 2 Lift the retainer clip straight up from the back of the two piece wire connector using a flat blade screwdriver then remove the two piece wire connector from the manifold door Figure 25 IMPORTANT Be careful not to bend or alter the position of the pilot tube ...

Страница 27: ...r Assembly Replacing the Manifold Burner Assembly WARNING Explosion Hazard Tighten both manifold door screws securely Remove any fiberglass between gasket and combustion chamber Replace viewport if glass is missing or damaged Replace two piece wire connector if missing or removed Replace door gasket if damaged Failure to follow these instructions can result in death explosion or fire 1 Check the d...

Страница 28: ...h or fine grit sandpaper Removing and Replacing the Gas Control Valve Thermostat IMPORTANT This water heater has a resettable thermal switch installed Do not attempt to disable or modify this feature in any way Use only factory authorized replacement parts Removing the Gas Valve 1 Turn off the gas supply to the water heater at the manual gas shut off valve This valve is typically located beside th...

Страница 29: ...rmal switch TROUBLESHOOTING CHART PROBLEM POSSIBLE CAUSE S CORRECTIVE ACTION BURNER WILL NOT IGNITE 1 Pilot not lit 2 Thermostat set too low 3 No gas 4 Dirt in the gas lines 5 Pilot line clogged 6 Main burner line clogged 7 Non functioning thermocouple 8 Non functioning thermostat 9 Heater installed in a confined area 1 Light pilot 2 Turn temp dial to desired temperature 3 Check with gas utility c...

Страница 30: ... inlet 8 Advise customer DRIP FROM RELIEF VALVE 1 Excessive water pressure 2 Heater stacking 3 Closed water system 1 Use a pressure reducing valve and relief valve 2 Lower the thermostat setting 3 See Closed System Thermal Expansion THERMOSTAT FAILS TO SHUT OFF 1 Thermostat not functioning prop erly 2 Improper calibration 1 Replace thermostat 2 Replace thermostat COMBUSTION ODORS 1 Insufficient se...

Страница 31: ... manual for specific requirements NO Is the pilot tube damaged NO Does the flame arrestor show signs of discoloration and or debris Shut off the gas supply to the water heater at the manual gas shut off valve then contact Residential Technical Assistance by referencing the phone number on the front of the Installation Instructions and Use Care Guide YES YES YES YES YES YES YES YES YES NO Contact a...

Страница 32: ...BAFFLE 4 HEAT TRAP NIPPLES COLD SOME MODELS 5 HEAT TRAP NIPPLES HOT SOME MODELS 6 COLD WATER DIP TUBE 7 ANODE ROD 8 TEMPERATURE PRESSURE RELIEF VALVE LOCATED TOP OR SIDE 9 DRAIN VALVE 10 GAS CONTROL VALVE THERMOSTAT with wire leads 11 OUTER DOOR 12 PILOT PILOT TUBE ASSEMBLY KIT Natural Gas 13 PILOT PILOT TUBE ASSEMBLY KIT L P Gas 14 BURNER Natural Gas 15 BURNER L P Gas 16 MANIFOLD DOOR ASSEMBLY Na...

Страница 33: ...ocouple two piece wire connector with retainer clip thermal switch and pilot assembly Natural Gas Low Nox Item 17 Manifold door assembly which contains the manifold tube gasket door pilot tube thermocouple two piece wire connector with retainer clip thermal switch and pilot assembly L P Gas Item 18 Contains two piece wire connector and retainer clip Item 19 Contains manifold door gasket Item 20 Co...

Страница 34: ...34 NOTES ...

Страница 35: ...d in a non corrosive and non contaminated atmosphere used with factory approved anode s installed in its original installation location in the United States its territories or possessions and Canada sized in accordance with proper sizing techniques for residential water heaters bearing a rating plate which has not been altered defaced or removed except as required by the warrantor used in an open ...

Страница 36: ...PONSIBLE FOR WATER DAMAGE LOSS OF USE OF THE UNIT INCONVENIENCE LOSS OR DAMAGE TO PERSONAL PROPERTY OR OTHER CONSEQUENTIAL DAMAGE THE WARRANTOR SHALL NOT BE LIABLE BY VIRTUE OF THIS WARRANTY OR OTHERWISE FOR DAMAGE TO ANY PERSONS OR PROPERTY WHETHER DIRECT OR INDIRECT AND WHETHER ARISING IN CONTRACT OR IN TORT IF THE GLASS LINED TANK IN THIS WATER HEATER SHALL PROVE UPON EXAMINATION BY THE WARRANT...

Отзывы: