background image

32

MOTOR WILL NOT RUN

1.  Confirm 120V AC to the controller. Also, to verify correct polarity, check 

for 120 V AC between hot supply and ground.

  If there is no voltage, check for a loose connection where it connects to 

the controller.

2.  If there is 120 volts to the controller, check for loose connections or a 

locked rotor. If the rotor cannot be freed the motor and blower assembly 

must be replaced.

MOTOR RUNS, PREPURGE TIME ELAPSES BUT MAIN 

FLAME NOT ESTABLISHED.

1.  Check to see if main manual gas valve is open.

2.  Check  for  a  loose  connection  at  the  transformer,  or  a  defective 

transformer.

3.  Check for a loose connection at the gas valve.

4.  Check  for  open  pressure  switches  or  open  reset  button.  Check  for 

blockage in the intake and exhaust venting or at the vent hoods. If no 

blockage is found, check vinyl tubing for cuts or crimps. If this tubing is 

damaged it must be replaced. If these steps do not eliminate the problem, 

replace the pressure switches.

5.  Check to see if there is resistance across the igniter terminal with an 

OHM meter. If there is no continuity, the igniter is broken and should be 

replaced.

  If  the  igniter  appears  to  function  properly,  then  verify  that  the  inlet 

pressure is within the range shown in Table 4. The gas valve supplied on 

the appliance is not designed to open against a higher inlet pressure of 

10.5"WC (2.59kPa) for natural gas and 14.0"WC (3.45kPa) for propane 

gas. At this time, also check to make sure the inlet pressure is not lower 

than 4.0"WC (.98kPa) for natural gas and 11.0"WC (2.74kPa) for propane 

gas. If the inlet pressure is not within these limits then adjust the supply 

pressure accordingly.

 

If the inlet pressure falls within the allowable limits, then verify that 

the manifold pressure, when the gas is fully open, with the heater 

running, is as called out in Table 4: that is, 0"WC (0kPa) for both 

natural  and  propane  gas.  If  the  manifold  pressure  is  not  correct 

then  adjust  accordingly.  See  "ADJUSTMENT  PROCEDURE"  in 

"OPERATING  INSTRUCTIONS"  sections  for  manifold  pressure 

adjustment procedure.

6.  If the inlet and manifold pressures are within the limits specified in step 5, 

then reset the appliance. Verify 24V AC at the gas valve during the three 

(3) second ignition trial, after the igniter reaches operating temperature. 

If 24V AC at the gas valve is not seen during this period, the controller 

must be replaced.

  If there is 24V AC at the gas valve during the four second ignition trial and 

the manifold pressure does not increase above 0" W.C. then verify that the 

manual gas control valve is in the “ON” position (see page 20). If the valve 

is in the “ON” position and the previous voltage and gas pressure conditions 

are met, then the gas valve is defective and must be replaced.

  Note  that  a  positive  manifold  pressure  reading  of  approximately 

 

1.5" (.38 kPa) W.C. is normal during the prepurge portion of the ignition 

cycle due to the location of the gas orifice.

MOTOR RUNS, BURNER LIGHTS MOMENTARILY, 

THEN LOCKS OUT

1.  Reset the appliance two more times to ensure that all of the air has been 

purged from the gas line.

2.  If the burner lights momentarily but does not sustain ignition, verify 

that the inlet pressure is not greater than 10.5" WC (2.59 kPa) for 

natural gas and 14.0" WC (3.45 kPa) for propane gas or lower than 

the minimal supply pressure which is 4.0" WC (.09kPa) for natural 

gas and 11.0"WC (2.74 kPa) for propane gas. Also, verify that the 

manifold pressure is correct, that is, 0"WC (0kPa) for both natural 

and propane gas 199 models. If the manifold pressure is not correct 

then  adjust  accordingly.  See  "ADJUSTMENT  PROCEDURE"  in 

"OPERATING  INSTRUCTIONS"  sections  for  manifold  pressure 

adjustment procedure.

3.  Check for the reversed polarity in the supply wiring. This controller is 

polarity sensitive. If the hot and neutral supply wires are reversed, the 

controller will not sense flame. Reverse the supply wires and try to fire 

the unit. 

NOTE:  

Always turn off and disconnect main supply wiring before servicing 

the unit.

4.  Check connecting wire to the flame sensor. Verify that the flame sensor 

has not been damaged in any way.

5.  Verify that the air supply is adequate. The air inlet screen or blower wheel 

may be restricted. Also, check the installation for proper ventilation. See 

AIR REQUIREMENTS.

6.  Check the venting system for the correct sizing, excess or insufficient. 

See VENTING.

7.  Check for maximum inlet pressure of 10.5"WC (2.59 kPa) for natural 

gas  and  14.0"WC  (3.45  kPa)  for  propane  gas  and  the  manifold 

pressure which is 0"WC (o kPa) for both natural and propane gas 

199 models. Please note that the manifold pressure listed is the 

maximum value for the manifold pressure. Do not set the manifold 

pressure higher than the value show in Table 4. OVER FIRING the 

heater will result in a rough ignition and/or noisy operation.

8.  Confirm  that  the  air  inlet  screen  (see  Figures  7  &  8)  is  free  of 

obstructions.

  

CAUTION

Do not reach into the burner housing or combustion chamber if the heater is 

still hot. Allow the heater to cool and always use gloves as the combustion 

chamber  and  the  burner  sleeve  and  housing  can  become  very  hot  after 

operation. OVER FIRING is a dangerous condition that must be corrected 

immediately.

GAS FAILS TO SHUT OFF

Check for defective gas valve or thermostat. If operation is incorrect, 

replace.

REPLACEMENT PARTS

Replacement parts may be ordered through authorized dealers, servicers, 

or distributors. Refer to the Yellow Pages for where to call or contact 

 

1-800-821-2017. When ordering parts be sure to state the quantity, 

part number and description of the items including the complete model 

and serial number as it appears on the product. Refer to the parts list 

for more information.

Содержание RUF 100 199

Страница 1: ...RVICE MAINTENANCE LIMITED WARRANTY WARNING If the information in these instructions is not followed exactly a fire or explosion may result causing property damage personal injury or death Do not store...

Страница 2: ...wed in all cases Authorities having jurisdiction should be consulted before installations are made In the absence of local codes the installation must comply with the current editions of the National...

Страница 3: ...ch are not listed in this section WATER TEMPERATURE CONTROL TABLE OF CONTENTS ROUGH IN DIMENSIONS 2 FOREWORD 2 FEATURES 3 4 Water Temperature Control 3 High Limit Switch E C O 4 Dishwashing Machine Re...

Страница 4: ...pa and 173 Kpa Flow pressures above 25 pounds per square inch 173 Kpa or below 15 pounds per square inch 103 Kpa will result in improperly sanitized dishes Where pressures are high a water pressure re...

Страница 5: ...sometimes installed in locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detec...

Страница 6: ...ER ISOLATION PIPE HANGERS ARE USED THIS PREVENTS ANY VIBRATIONS FROM BEING TRANSMITTED INTO THE LIVING SPACES HARD WATER Where hard water conditions exist water softening or the threshold type of wate...

Страница 7: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no less than one half 1 2 inch in size GAS VENT DIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS INSPECTION The st...

Страница 8: ...INTAKE IN WINDY COLD AREAS THE MAXIMUM PRACTICAL DISTANCE BETWEEN THESE TWO TERMINALS IS RECOMMENDED FIGURE 6 U S DIRECT VENT CAUTION TO PREVENT EXHAUSTING PRODUCTS FROM CIRCULATING TO THE AIR INTAKE...

Страница 9: ...1 The intake vent terminal and the exhaust vent terminal must terminate on the same exterior wall and must be located at a minimum of 24 61cm from the vertical centerline of the exhaust vent terminal...

Страница 10: ...the same side of roof 4 The center line of the intake vent termination and the center line of the exhaust vent termination must be no closer than 24 61cm 5 The intake vent terminal and the exhaust ve...

Страница 11: ...r ABS cement to join PVC or CPVC pipe and fittings SAFETY PRECAUTION PRIMERS AND CEMENTS ARE EXTREMELY FLAMMABLE AND MUST NOT BE STORED OR USED NEAR HEAT OR OPEN FLAME ALSO USE ONLY IN A WELL VENTILAT...

Страница 12: ...s that the electrical contacts on this air flow switch be open before it will allow the blower to come on BLOCKED OUTLET PROVER SWITCH SEE FIGURE 12 The Blocked Outlet Prover Switch is set up to shut...

Страница 13: ...T BE READILY ACCESSIBLE AND NOT SUBJECT TO FREEZING CONDITIONS INSTALL IN ACCORDANCE WITH RECOMMENDATIONS OF SERVING GAS SUPPLIERS REFER TO THE NATIONAL FUEL GAS CODE FIGURE 13 CONNECTION OF GAS PIPE...

Страница 14: ...This heater is equipped with an approved temperature and pressure relief valve ASME ratings cover pressure relief CSA ratings cover release rate with temperature actuation FOR SAFE OPERATION OF THE WA...

Страница 15: ...al Supply Voltage is reversed the controller will not sense flame Verify polarity before connecting the unit 3 This unit may never be connected to any existing heating system or component s previously...

Страница 16: ...he desktop screen if there are no active fault or alert conditions An example of this screen is shown to the right The first temperature on this screen is the temperature of the water inside the tank...

Страница 17: ...u DISPLAY ACTION From the Main Menu press Select to enter the Temperatures screen DISPLAY 2 Operating States In the main desktop screen there are some specific Operating States that are indicated on t...

Страница 18: ...that can occur during operation These are Alerts and Faults Alerts This is a non safety related condition that the control has detected that may cause the water heater to operate in a less than optima...

Страница 19: ...on about the water heater and the current status of specific conditions can be found INSTALLATION OR SERVICE OF THIS WATER HEATER REQUIRES ABILITY EQUIVALENT TO THAT OF A LICENSED TRADESMAN IN THE FIE...

Страница 20: ...he unit is installed and filled with water and the inlet pressures confirmed simply turn the switch on and observe operation Cycle the unit off and on several times to ensure proper operation OPERATIN...

Страница 21: ...45kpa Nominal Gas Supply Pressure 7 0 WC 1 74Kpa 11 0 WC 2 74Kpa Minimum Gas Supply Pressure 4 8 WC 1 18Kpa 8 5 WC 2 08 Kpa Manifold Pressure 0 WC OKpa 0 WC OKpa HIGH ALTITUDE INSTALLATIONS WARNING T...

Страница 22: ...GAS TO APPLIANCE FOR YOUR SAFETY READ BEFORE OPERATING WARNING If you do not follow these instructions exactly a fire or explosion may result causing property damage personal injury or loss of life OP...

Страница 23: ...onnect switch 2 Close the cold water inlet valve to heater 3 Open a nearby hot water faucet to vent the system 4 Open the heater drain valve 5 If the heater is being drained for an extended shutdown i...

Страница 24: ...sly it may be due to thermal expansion of water in a closed water supply system or it may be due to a faulty relief valve Thermal expansion is the normal response of water when it is heated In a close...

Страница 25: ...OF WATER IN THE HOT WATER SYSTEM MUST BE PROVIDED NOTE CONNECT RETURN LINE FROM HOT WATER CIRCULATING LOOP IF USED TO COLD WATER INLET LINE PIPE TO OPEN DRAIN INSTALL IN ACCORDANCE WITH LOCAL CODES I...

Страница 26: ...PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR HOT WATER SUPPLIED TO FIXTURES CAUTION IF BUILDING COLD WATER SUPPLY HAS A BACK FLOW P...

Страница 27: ...TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 4 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN...

Страница 28: ...TH LOCAL CODES TWO TEMPERATURE TWO HEATERS ONE PRE HEATER ONE BOOSTER HEATER WITH OR WITHOUT BUILDING RECIRCULATION DANGER TEMPERATURE SETTING SHOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER...

Страница 29: ...HOULD NOT EXCEED SAFE TEMPERATURE AT FIXTURES SEE WATER TEMPERATURE CONTROL WARNING ON PAGE 5 IF HIGHER PREHEAT TEMPERATURES ARE NECESSARY TO OBTAIN ADEQUATE BOOSTER OUTPUT ADD AN ANTI SCALD VALVE FOR...

Страница 30: ...nits with the higher water flow may have a shortened life Dimensions shown are for minimum space occupied by the water heaters assemblies Space for the venting system and unit servicing must be added...

Страница 31: ...er drain valve is tightly closed Also check the cleanout opening for leakage 2 The apparent leakage may be condensation which forms on cool surfaces of the heater and piping 3 If the outlet of the rel...

Страница 32: ...at a positive manifold pressure reading of approximately 1 5 38 kPa W C is normal during the prepurge portion of the ignition cycle due to the location of the gas orifice MOTOR RUNS BURNER LIGHTS MOME...

Страница 33: ...33 NOTES...

Страница 34: ...34 NOTES...

Страница 35: ...ranty shall be void and shall have no effect if the design or structure of the water heater is or is attempted to be modified or altered in any way including but not limited to by attaching non compan...

Страница 36: ...36...

Отзывы: