background image

 

 

E. Installing 240 Volt Circuits

 

 

Reliance Controls 6-Circuit Transfer switch (In Kit) is shipped from 
the factory with one installed handle tie on two adjacent circuits.

 

 

Let’s assume that, according to your set-up plan, Switches A & B 
on the 6-Circuit transfer switch will be used to supply power to your 
well pump, a 240 Volt appliance.  (Figure 6)

 

 

1. 

Find the two red and the two black wires marked A & B.

 

2. 

Turn off the double pole breaker for the well pump in the load 
center.

 

3. 

Disconnect the two installed wires on the double pole  breaker.

 

4. 

Cut the two red wires from marked A & B at a length 
convenient for them to reach to the double pole breaker. Strip 
5/8” from the end of each red wire. Connect both red wires to 
the double pole circuit breaker in place of the wires you just 
removed from that breaker.  It doesn’t matter in what  order.

 

5. 

Cut the two black wires marked A & B to a length convenient to 
reach the wires you removed from the double pole breaker in

 

#3. Strip 5/8” from the end of each wire.

 

6. 

Connect one of the wires you removed from the double pole 
breaker in #3 with one of the black wires (either A & B) with 
an appropriate wire connector. Similarly, connect the other 
wire you removed with the remaining black wire with an 
appropriate w i re connector.

 

 

F. Completing the Installation of the 

Transfer Switch

 

 

When you have wired all of the circuits from the transfer switch into 
your load center and have properly installed the green and white 
wires to the ground and neutral bars, you have finished the 
installation. 

 

Just a few more steps to wrap things up.

 

 

1. 

Replace the cover of the load center.

 

2. 

If you have not already done so, fill in the chart on the transfer 

switch to identify your emergency circuits and the toggle 
switches they correspond  to.

 

3. 

Do not turn the main and individual circuit breakers in your load 

center back on until you have installed all other transfer switch 
components in Sections G and H which follow.

 

 

When Installing 240 Volt Circuits

 

 

 

The transfer switch circuits with 20 Amp breakers must be con- 
nected only to branch circuits with 20 Amp breakers in the load 
center. Do not connect transfer switch circuits to any branch cir- 
cuits greater than 20 Amps, except A and B positions (30A max). 
A 20 amp breaker can be changed to a 15 amp breaker if needed. 

 

NOTE:

 The transfer switch circuits with 15 Amp breakers can be 

connected to branch circuits with either 15 or 20 Amp breakers 
in the load center.  This is because there is 12 AWG behind all 
switches except A and B which use 10 AWG.  

 

 

 

Removing handle ties. 

If there are no 240 volt or multi-wire circuits in the transfer switch installation, handle ties on the 

switches are not needed. To remove a handle tie, place the handle-tied switches in a position opposite of the other 
switches. Rotate the cylindrical spacer between the switches upward repeatedly until the threaded shaft is exposed on the 
right switch. Grab the threaded shaft and continue to rotate the spacer upward until the spacer is free, being carefully not 
to drop the spacer when it becomes free. Remove the shaft from the switch. If the shaft is not exposed after several 
revolution of the spacer, insert a small slot screwdriver in the hole in the right switch and continue rotating the spacer 
upward while the screw driver prevents the shaft from rotating.

 

Adding handle ties.

 If additional ties are needed to accommodate additional 240 volt or multi-wire circuits, they can be 

added to adjacent pairs of switches.

 

Figure 6

 

WARNING

 

Содержание PRI/TRAN 2 RN Series

Страница 1: ...n this Manual 1 About Generators and Transfer Switches 2 Key Product Components 3 Pre Planning the Load on Your Generator 4 Installation Instructions 5 Mounting the Transfer Switch 5 Connecting the Co...

Страница 2: ...dicates a potentially hazardous situation that if not avoided could result in death or serious injury Caution indicates a potentially hazardous situation that if not avoided may result in minor or mod...

Страница 3: ...little pre planning by 1 Picking the key electrical appliances you want to power in an emergency 2 Finding the essential circuit breakers that control these devices 3 Creating a map of all of the othe...

Страница 4: ...ion stops the power from the branch circuit from both utility and generator power at the circuit toggle switch Handle ties Handle ties are inserted into two adjacent toggle switches and are used for 2...

Страница 5: ...lan the setup of your transfer switch Use the running watts of your appliances rather than starting watts when dividing them between the two halves of the transfer switch Check your appliances for act...

Страница 6: ...up battery powered lighting to clearly illuminate your work area 2 Turn off the main utility breaker Figure 3 3 Remove the cover of your load center Keep in mind that the wires on the utility side of...

Страница 7: ...ter Do not connect transfer switch circuits to any branch circuits greater than 20 Amps except circuits A B which may be connected to 30 Amp circuits Any of the breakers can be changed NOTE The transf...

Страница 8: ...n the chart on the transfer switch to identify your emergency circuits and the toggle switches they correspond to 3 Do not turn the main and individual circuit breakers in your load center back on unt...

Страница 9: ...let plug insert the white wire into the hole marked W and tighten the screw on the side of the plug Do the same with the red wire into the hole marked X and the black wire into the hole marked Y NOTE...

Страница 10: ...perating properly and that you are ready for the next power outage Operation of Transfer Switch WithyourRelianceControlstransferswitchinstalled itisnotnecessary toturnoffanyofyourloadcenterbreakerswhe...

Страница 11: ...10 TRANSFER SWITCH PRODUCT SPECIFICATIONS NOTES...

Страница 12: ...A B C D E F Controls these essential appliances I will need during a power outage So I will need to turn these other devices off which are on the same circuits HOME CIRCUIT MAPPING CHART...

Страница 13: ...and Reliance shall not be liable for any incidental special or consequential damages The cost of labor to remove or install a replacement component or Switch is not included in this warranty The foreg...

Отзывы: