Revision lines indicate updated or new data.

The equipment presented in this bulletin is to be installed in accordance with the latest published Standards of the National Fire Protection Association, Factory 

Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products 

manufactured and distributed by Reliable have been protecting life and property for over 90 years, and are installed and serviced by the most highly qualified 

and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.

EG. Printed in U.S.A. 

12 / 13 

P/N 9999970347

The tables below represent the minimum number of sprinklers at a minimum start pressure as per FM DS 8-9

Table 1 – Ceiling – Level protection for Solid Piled, Palletized, Shelf or Bin Box storage arrangements

Ceiling Height

Class 1, 2 & 3

Class 4 and 

Cartoned 

Unexpanded 

Plastics

Cartoned Expanded 

Plastics

Uncartoned 

Unexpanded 

Plastics

Uncartoned 

Expanded Plastics

10’ (3.0)

N/A

N/A

6 @ 20 (1.4)

10 @ 7 (0.5)

See Note 4

10 @ 7 (0.5)

See Note 4

15’ (4.5)

N/A

6 @ 20 (1.4)

6 @ 20 (1.4)

12 @ 7 (0.5)

See Note 4

8 @ 20 (1.4)

See Note 4

20’ (6.0)

6 @ 20 (1.4)

6 @ 20 (1.4)

6 @ 20 (1.4)

8 @ 20 (1.4)

See Note 4

8 @ 40 (2.8)

See Note 4

25’ (7.5)

6 @ 20 (1.4)

6 @ 20 (1.4)

6 @ 20 (1.4)

8 @ 40 (2.8)

See Note 4

12 @ 40 (2.8)

See Note 4

30’ (9.0)

6 @ 25 (1.7)

6 @ 25 (1.7)

10 @ 40 (2.8)

See Note 4

10 @ 40 (2.8)

See Note 4

N/A

35’ (10.7)

See Note 3

8 @ 40 (2.8)

8 @ 40 (2.8)

N/A

N/A

N/A

Table 2 – Ceiling – Level protection for Open Frame Rack Storage Arrangements

Ceiling Height

Class 1, 2 & 3

Class 4 and 

Cartoned 

Unexpanded 

Plastics

Cartoned Expanded 

Plastics

Uncartoned 

Unexpanded 

Plastics

Uncartoned 

Expanded Plastics

15’ (4.5)

N/A

6 @ 25 (1.7)

6 @ 25 (1.7)

12 @40 (2.8)

See Note 4

12 @ 40 (2.8)

See Note 4

20’ (6.0)

6 @ 20 (1.4)

6 @ 25 (1.7)

6 @ 25 (1.7)

6 @ 90 (6.2)

N/A

25’ (7.5)

6 @ 20 (1.4)

6 @ 25 (1.7)

6 @ 25 (1.7)

N/A

N/A

30’ (9.0)

6 @ 30 (2.1)

6 @ 30 (2.1)

N/A

N/A

N/A

35’ (10.7)

See Note 3

8 @ 40 (2.8)

8 @ 40 (2.8)

N/A

N/A

N/A

Notes: 

1.  See FM Data Sheet 8-1 for definitions of comodity classifications
2.  Per Data Sheet 2-0 Section 2.2.3.4.2 the N252EC defaults to extended coverage and the maximum vertical distance below 

ceiling is 12” to center of thermal element.

3.  For ceiling heights above 30’, maximum sprinkler spacing is 12’ x 12’.
4.  500 gpm hose stream required.

Содержание N252 EC Pendent

Страница 1: ... Fire pump size Tank size 6 165 F 74 C and 212 F 100 C temperature ratings 7 Maximum deflector distance from ceiling is 131 2 343 mm 12 305 mm to center line of thermal element 8 This is a Quick Response CMSA sprinkler that meets the requirements of IFC 2015 for the elimination of smoke heat vents in storage occupancies 9 US Pat No 7 624 812 Other Patents Pending See Design Criteria for details Ta...

Страница 2: ...sprinkler systems or pre action sprinkler systems whose sprinkler protection design can be based on the equivalent of a wet pipe system are acceptable 4 Sprinkler Spacing The minimum and maximum linear distances between sprinklers are 10 ft 3 1 m and 14 ft 4 2 m respectively for ceiling heights up to and including 30 ft 9 0 m For ceiling heights over 30 ft 9 0 m and up to 35 ft 10 7 m the maximum ...

Страница 3: ...lers not tightened to recommended torque may cause leakage or impairment of the sprinklers Damaged sprinklers must be replaced immediately Maintenance The Model N252 EC Pendent Control Mode Specific Application Sprinklers should be inspected and the sprinkler system maintained in accordance with NFPA 25 and local jurisdictional requirements Do not clean sprinklers with soap and water ammonia or an...

Страница 4: ...anded Plastics Cartoned Expanded Plastics Uncartoned Unexpanded Plastics Uncartoned Expanded Plastics 10 3 0 N A N A 6 20 1 4 10 7 0 5 See Note 4 10 7 0 5 See Note 4 15 4 5 N A 6 20 1 4 6 20 1 4 12 7 0 5 See Note 4 8 20 1 4 See Note 4 20 6 0 6 20 1 4 6 20 1 4 6 20 1 4 8 20 1 4 See Note 4 8 40 2 8 See Note 4 25 7 5 6 20 1 4 6 20 1 4 6 20 1 4 8 40 2 8 See Note 4 12 40 2 8 See Note 4 30 9 0 6 25 1 7 ...

Отзывы: