Features

• 

cULus Listed for areas of coverage up to 256 square feet

• 

Fast response 212°F (100°C) fusible link operating element

Product Description

The Reliable Model KFR-CCS Combustible Concealed 
Space Sprinkler is an upright, special sprinkler designed to 

provide protection of specific light hazard combustible and 

noncombustible concealed spaces requiring sprinkler protection. 

The Model KFR-CCS Sprinkler utilizes a fast response solder-

link fusible element that has demonstrated response times in 

laboratory tests which are five to ten times faster than standard 

response sprinklers. This feature enables the sprinkler to apply 

water to a fire much faster than standard response sprinklers of 

the same temperature rating.

Application

The Model KFR-CCS sprinkler is specifically listed for the 
protection of horizontal combustible concealed spaces up to 36” 
deep as described in NFPA 13 and as detailed in this bulletin.

In addition, the Model KFR-CCS sprinkler is specifically listed for 
the protection of horizontal combustible concealed spaces with 
wood truss and bar joist construction up to and including 60” 

(900 mm) deep.

Installation

Model KFR-CCS Sprinklers are to be installed in the upright 
position with their frames arms parallel to the pipe.  When 
installing the Model KFR-CCS sprinkler use only the Reliable 
Model W2 installation wrench.  Usage of any other type of 
installation wrench may damage the sprinkler and will void 
the manufacturer’s warranty. Damaged sprinklers must be 

immediately replaced.  A leak tight ½” NPT (R1/2) sprinkler joint 

can be obtained with an installation torque of approximately 8 -18 
ft-lbs (10.8 – 24.4 N

.

m) after application of an appropriate thread 

sealant. Do not tighten sprinklers over these recommended limits. 

Doing so may cause leakage and/or premature operation.

www.reliablesprinkler.com

K-factor 5.6 (80); SIN RA4454

cULus Listed

Model KFR-CCS 

Combustible Concealed Space Sprinkler

Bulletin 044 December 2022

Maintenance

Reliable Model KFR-CCS series sprinklers should be inspected 
and the sprinkler system maintained in accordance with NFPA 
25, as well as the requirements of any Authorities Having 
Jurisdiction.  Prior to installation, sprinklers should remain in the 

original cartons and packaging until used. This will minimize the 

potential for damage to sprinklers that could cause improper 
operation or non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or
any other cleaning fluids. Remove dust by gentle vacuuming
without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory
applied). A stock of spare sprinklers should be maintained to
allow quick replacement of damaged or operated sprinklers.
Failure to properly maintain sprinklers may result in inadvertent

operation or non-operation during a fire event.

Guarantee

For Reliable Automatic Sprinkler Co., Inc. guarantee, terms, and 
conditions, visit www.reliablesprinkler.com.

Ordering Information

Specify: Model KFR-CCS Sprinkler

W2 Wrench

Model W2 Wrench

Содержание KFR-CCS

Страница 1: ...damage the sprinkler and will void the manufacturer s warranty Damaged sprinklers must be immediately replaced A leak tight NPT R1 2 sprinkler joint can be obtained with an installation torque of appr...

Страница 2: ...onal sprinklers that are required for protection of CPVC piping that is offset over an obstruction Maximum Distance Spacing Between Sprinklers Refer to Figures 2 through 7 Maximum Coverage Area Per Sp...

Страница 3: ...whichever is smaller Where the members at the bottom of the concealed space are greater than 6 in 150 mm tall installing CPVC piping directly on top of those members shall be permitted When using 1 i...

Страница 4: ...NCEALED SPACE ABOVE THE TOP OF THE CEILING WHICHEVER IS SMALLER SEE NOTE 1 HYDRAULIC DESIGN AREA REQUIREMENTS A WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE PROVIDED AT MAXIMUM AREAS OF 10...

Страница 5: ...E PROVIDED AT MAXIMUM AREAS OF 1000 ft2 93 m2 OR LESS CALCULATE ALL SPRINKLERS WITHIN THE COMPARTMENTED AREA 2 WET SYSTEM WHERE DRAFT CURTAINS OR FULL HEIGHT WALLS ARE NOT PROVIDED OR PROVIDED AT AREA...

Страница 6: ...R WHERE THIS DISTANCE IS LESS THAN 12 in 300 mm 1A WHERE CEILING IS NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1...

Страница 7: ...S THAN 12 in 300 mm 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE SOLID OR COMPOSITE WO...

Страница 8: ...NOT SUPPORTED BY JOISTS EXAMPLE SUSPENDED A C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE...

Страница 9: ...C T MEASUREMENT POINT IS TOP OF CEILING 2 DEFLECTOR DISTANCE BELOW BOTTOM OF JOIST TO 1 1 2 in TO 4 in 38 mm TO 100 mm BELOW BOTTOM OF TOP CHORD IN NO CASE SHALL DEFLECTOR BE ABOVE THE BOTTOM OF THE S...

Отзывы: