Installation

The Model J168 Upright Sprinklers are to be installed as 

follows:

•  Install in upright position only.
•  Apply pipe thread sealant to NPT threads, hand 

tighten into the sprinkler fitting.

•  Install sprinkler by wrench boss only.
•  Wrench tighten with the dedicated J1 Sprinkler 

Wrench.

•  A leak tight  ¾ NPT (R¾) sprinkler joint can be 

obtained with a torque of 14 - 20 ft. lbs. 

•  Higher torques may compromise the seal or func-

tion integrity of the sprinkler.

Maintenance

Model J168 Sprinklers should be inspected and the 

sprinkler system maintained in accordance with NFPA 
25.  Do not clean sprinklers with soap and water, ammo-
nia or any other cleaning fluids. Remove dust by using a 
soft brush or gentle vacuuming. Remove any sprinkler that 
had been painted (other than factory applied) or damaged 
in any way. A stock of spare sprinklers should be main-
tained to allow quick replacement of damaged or operated 
sprinklers. Prior to installation, sprinklers should be main-
tained in the original cartons and packaging until used to 
minimize the potential for damage to sprinklers that would 
cause improper operation or non-activation.

Engineering Speci

fi

 cation

Model J168 Standard Response
Upright Sprinkler

Sprinklers shall be standard response upright spray sprin-

klers cULus Listed for use in occupancy classifications up 
to and including extra hazard, and for storage occupancies 
in accordance with NFPA 13.  Sprinkler construction shall 
be a bronze, die-cast frame with grooved wrench flat and 
copper-alloy deflector.   Water seal assembly shall consist 
of a fusible solder thermal element utilizing a center strut 
solder-in-compression principle of construction with metal 
Belleville spring washer, coated on both sides with Teflon 
film.  Sprinkler temperature rating shall be [165 °F (74 °C)] 
[212 °F (100 °C)] [286 °F (141 °C)].  Sprinklers shall have 
a nominal K-factor of 16.8 (241.9) and have a ¾” NPT (R) 
thread.  The rated working pressure shall be 175 psi (12.1 
bar).  Standard finish shall be bronze.  Sprinklers shall be 
Reliable Model J168 standard response upright sprinklers, 
Bulletin 011 (SIN RA1124).

Special Application Finishes Option:

Exposed sprinklers subject to corrosive atmospheres shall 

have a factory-applied [165 °F (74 °C) clear wax-coated] 
[212 °F (100 °C) brown wax-coated] [lead plated for 165 °F 
(74 °C), 212 °F (100 °C), or 286 °F (141 °C)] [wax-coated 
over lead plated] corrosion resistant coating. 

Note:

 1. Grooved sprinkler boss provided to insure that the Sprinkler 

wrench does not slip during installation.         

           2. A tight ¾” NPT sprinkler joint should be obtained with a torque of 14 to 20 ft. lbs. Higher levels of torque may distort the sprinkler inlet 
               cause leakage or impairment. 