background image

www.reliablesprinkler.com

Product Description

Model J112SS series sprinklers are cULus Listed extend-
ed coverage spray sprinklers intended for installation in 
accordance with NFPA 13.  Model J112SS sprinklers have 
a frame, deflector, and cap made of Type 316 Stainless 
Steel. Coverage areas up to 400 ft

2

 (37 m

2

) per sprinkler 

with a maximum spacing of up to 20 ft by 20 ft (6.1 m by 
6.1 m) are permitted for both Light Hazard and Ordinary 
Hazard occupancies. Listed flows and pressures for each 
hazard classification and sprinkler spacing are provided in 
this Bulletin. The Model J112SS is cULus Listed as quick-re-
sponse sprinklers for Light Hazard occupancies. When used 
in the Ordinary Hazard occupancies, Model J112SS series 
sprinklers are cULus Listed as quick-response for spacings 
up to 14 ft by 14 ft (4.3 m by 4.3 m) and standard-response 
for other listed spacings up to 20 ft by 20 ft (6.1 m by 6.1 m). 

Model J112SS Pendent and J112SS Upright sprinklers 
use a glass bulb operating element and are cULus Listed 
as Corrosion Resistant Sprinklers. Model J112SS Pendent 
sprinklers are cULus Listed for use with the Model FP re-
cessed escutcheon, which provides up to ½ inch (13 mm) of 
adjustment. In addition, for Ordinary Hazard occupancies, 
the Model J112SS Pendent sprinklers are cULus Listed for 
use with the Model F1 recessed escutcheon that provides 
up to ¾ inch (19 mm) of adjustment.  Both escutcheons are 
manufactured from Type 316 stainless steel alloy.

Application

Model J112SS series sprinklers are intended for installation 
in Light Hazard and Ordinary Hazard occupancies in ac-
cordance with NFPA 13. The sprinklers must be installed in 
accordance with the requirements of NFPA 13 for extended 
coverage spray sprinklers and the requirements identified 
in this Bulletin. In addition to the installation requirements 
of NFPA 13, cULus Listed Specific Application Criteria for 
installation under concrete tee construction is provided in 
this Bulletin.

cULus Listed

K11.2 (160 metric)

Model J112 Stainless Steel Series Sprinklers

Extended Coverage Sprinklers 

for Light Hazard and Ordinary Hazard 

Bulletin 178 December 2019

Model J112SS Upright

Model J112SS Pendent

Model J112SS Sprinkler Summary

Model

Orientation

Sprinkler Identification Number (SIN)

J112SS

Pendent

R7816

J112SS

Upright

R7826

Table A

FP Recessed Escutcheon

F1 Recessed Escutcheon

Отзывы: