P/N 9999970524

Bulletin 178 
December 2019

Page 5 of 5

www.reliablesprinkler.com

Installation

Glass bulb sprinklers have orange bulb protectors to minimize 
bulb damage during shipping, handling, and installation. Re-
liable sprinkler installation wrenches are designed to install 
sprinklers with bulb protectors in place. Remove the bulb pro-
tector at the time when the sprinkler system is placed in service 
for fire protection. Removal of the bulb protector before this time 
may leave the bulb vulnerable to damage. Remove bulb protec-
tors by undoing the clasp by hand. Do not use tools to remove 
bulb protectors. 

Model J112SS series sprinklers must be installed with the Re-
liable sprinkler installation wrench identified in this Bulletin. 
Any other wrench may damage the sprinkler. Recommended 
installation torque is 14 to 20 lb.ft (19 to 27 N.m). Do not tighten 
sprinklers over the maximum recommended installation torque. 
Exceeding the maximum recommended installation torque may 
cause leakage or impairment of the sprinkler. 

Recessed pendent sprinklers are to be installed as shown in 
Fig. 4 or Fig 5., as applicable to the specific model being in-
stalled. Model J112SS series recessed pendent sprinklers may 
only be installed with the Reliable Model F1 or Model FP re-
cessed escutcheon. The use of any other recessed escutcheon 
will void all approvals and negate all warranties. The Reliable 
Model FP escutcheon may not be used in ceilings having pos-
itive pressure with respect to the space below. Ensure that the 
openings in the Model FP escutcheon/can assembly are unob-
structed following installation. 

Maintenance

Model J112SS series sprinklers should be inspected and the 
sprinkler system maintained in accordance with NFPA 25. Do 
not clean sprinklers with soap and water, ammonia or any other 
cleaning fluids. Remove dust by gentle vacuuming. Replace 
any sprinkler which has been painted (other than factory ap-
plied) or damaged in any way. A stock of spare sprinklers 
should be maintained to allow quick replacement of damaged 
or operated sprinklers. Prior to installation, sprinklers should 
be maintained in the original cartons and packaging until used 
to minimize the potential for damage to sprinklers that would 
cause improper operation or non-operation.

Model J1 Wrench

Model RJ Wrench

Listings and Approvals

Listed by Underwriters Laboratories, Inc. and certified by
Underwriters Laboratories of Canada (cULus)

UL Listing Category

Sprinklers, Automatic and Open Extended Coverage Sprinklers
UL Guide Number – VNIV.

Ordering Information

Specify:

1.  Sprinkler Model: [J112SS Pendent] [J112SS Upright] 
2.  Temperature Rating: [155°F (68°C)] [200°F (93°C)] 
                                      [286°F (141°C)]   
3.  Finish: [None] [White Polyester] [Black Polyester]
     [Custom Color Polyester]
4.  Escutcheon: (Pendent Only)
                  Model F1 (Ordinary Hazard Only)
                  Model FP