background image

Models F1 & F1FR Pendent Sprinkler

with Model F1 Recessed Escutcheon

3/4" (19mm) Nominal Adjustment

2-7/8" (72 mm) Dia.

1-3/4"

(44 mm)

2-1/4"

(57 mm) Dia.

Hole in Ceiling

1-15/16"

(49 mm) Dia.

Minimum

Recess

Maximum

Recess

1"

(25 mm)

Face of Fitting

to Face of Ceiling

1-1/8" (29 mm) at
Max. Recess

3/8" (10 mm) at
Min. Recess

Models F1 & F1FR Pendent Sprinkler

with Model FP Recessed Escutcheon

1/2" (13mm) Nominal Adjustment

1"

(25 mm)

2-5/16"

(59 mm) Dia.

Minimum

Recess

Maximum

Recess

1/2"

(12 mm)

3-3/16" (78 mm) Dia.

Face of Fitting

to Face of Ceiling

1-1/2" (38 mm) at
Max. Recess
1" (25 mm) at
Min. Recess

2-7/8" (72 mm) Dia.

1-3/4"

(44 mm)

Minimum

Recess

Maximum

Recess

1-1/4"

(32 mm)

Face of Fitting

to Face of Ceiling
7/8" (22 mm) at

Max. Recess
3/8" (10 mm) at
Min. Recess

2-1/4"

(57 mm) Dia.

Hole in Ceiling

1-15/16"

(49 mm) Dia.

2-1/2"

 (64 mm) Dia.

Hole in Ceiling

Models F1 & F1FR Pendent Sprinkler

with Model F2 Recessed Escutcheon

1/2" (13mm) Nominal Adjustment

Reducing
Fitting

Reducing
Fitting

Reducing
Fitting

Note: Model FP recessed assemblies may not be used where the
pressure in the space above the ceiling is positive with respect to

the protected area. Ensure that the openings in the Model FP cup
are unobstructed following installation.

Vented Cup

Model F1FR56 CCP Conical Concealed Sprinkler

1/2" (13mm) Nominal Adjustment

(Nominal Cover Plate Projection is 1" (25 mm))

1"

(25 mm)

2-5/16"

(59 mm) Dia.

Minimum

Recess

Maximum

Recess

1/2"

(12 mm)

3-5/16" (84 mm) Dia.

Face of Fitting

to Face of Ceiling

1-1/2" (38 mm) at
Max. Recess
1" (25 mm) at
Min. Recess

2-1/2"

 (64 mm) Dia.

Hole in Ceiling

F1_REC_PEND_CCP

Reducing
Fitting

Note: Model CCP concealed assemblies may not be used where

the  pressure  in  the  space  above  the  ceiling  is  positive  with

respect  to  the  protected  area.  Ensure  that  the  openings  in  the
Model CCP cup are unobstructed following installation.

Vented Cup

Recessed and Concealed Installation: Pendent Sprinklers

Figure 5

FP Escutcheon

F1 Escutcheon

(F2 Similar)

CCP Cover Plate

Bulletin 074

October 2022

Page 6 of 9

www.reliablesprinkler.com

Содержание F1FR56

Страница 1: ...ofile compact design Available in a wide variety of finishes Product Description Reliable Model F1FR56 series sprinklers are quick response standard spray automatic fire sprinklers utilizing a sensiti...

Страница 2: ...s Shields New Frames Factory Water Shield cULus FM F 1 Guard cULus FM F 3 Guard with Shield cULus FM Guards and Shields Legacy Frames Factory Water Shield C 1 Guard FM C 3 Guard with Shield cULus FM D...

Страница 3: ...ard Shield Kit FM D 1 Guard cULus FM D 4 Guard Shield Kit FM D 5 Guard Shield Kit cULus FM S 1 Shield cULus FM Sprinkler Wrenches Model W2 pendent Model W4 recessed or concealed Model J New frame with...

Страница 4: ...3 C1 Guard FM D1 Guard cULus Sprinkler Wrenches Model W2 non recessed Model W4 recessed Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus...

Страница 5: ...emperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C Guards Shields New Frames F 2 Guard FM Guards Shields Legacy Frames C1 Guard FM Sprinkler Wrenches Model W2 Model J New frame...

Страница 6: ...justment Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assemblies may not be used where the pressure in the space above the ceiling is positive with respect to the protecte...

Страница 7: ...h Model FP Recessed Escutcheon 1 2 13mm Nominal Adjustment Model F1FR Horizontal Sidewall Sprinkler with Model F2 Recessed Escutcheon 1 2 13mm Nominal Adjustment Model F1FR Horizontal Sidewall Sprinkl...

Страница 8: ...ht Brass Chrome Chrome White Paint Bright Brass 5 Satin Chrome Satin Chrome White Polyester 3 White Polyester Satin Chrome Custom Color Polyester Custom Color Paint Custom Color Polyester 3 Notes 1 Pa...

Страница 9: ...chnical specifications Sprinkler Finish See Table B Recessed Escutcheon 1 2 F1 F2 FP Escutcheon Finish See Table B CCP Cover Plate Temperature Rating 135 F 57 C For use with 135 F 57 C and 155 F 68 C...

Отзывы: