3.
Model F1FR-300 Quick Response Extended Coverage Recessed Horizontal Sidewall Sprinkler
Deflector:
QREC-9
Installation Wrench:
Model W4 Sprinkler Wrench
Approval Type:
Quick Response Extended Coverage – Light Hazard Occupancy
Installation Data:
Nominal
Orifice
Size
Thread
Size
“K” Factor
Sprinkler
Length
Approval
(2)
Organizations
Sprinkler
Identification
Number (SIN)
US
Metric
17
/
32
”
(20mm)
¾” NPT
(R¾)
8.0
115.3
2.95”
(75mm)
1, 2
R5962
(2)
Refer to Escutcheon Data Table for approvals and dimensions.
Installation Data:
COVERAGE AREA
Flow Rate
gpm (L/min)
Pressure
psi (bar)
Maximum
Coverage Area
Width x Length
ft. x ft. (m x m)
Temperature
Rating
(1)
Deflector to Ceiling
Dimension
Min. - Max.
Inches (mm)
UL
UL
26 (98.4)
29 (109.8)
29 (109.8)
32 (121.1)
36 (136.3)
39 (147.6)
10.6 (0,7)
13.1 (0,9)
13.1 (0,9)
16.0 (1,1)
20.2 (1,4)
23.8 (1,6)
16 x 16 (4.9 x 4.9)
16 x 16 (4.9 x 4.9)
16 x 18 (4.9 x 5.5)
16 x 20 (4.9 x 6.0)
16 x 22 (4.9 x 6.7)
16 x 24 (4.9 x 7.3)
135°F (57°C)
155°F (68°C)
175°F (78°C)
6 - 12 (153 - 305)
4 - 12 (102 - 305)
4 - 12 (102 - 305)
4 - 12 (102 - 305)
4 - 12 (102 - 305)
4 - 12 (102 - 305)
33 (124.9)
39 (147.6)
40 (151.4)
46 (174.1)
33 (124.9)
40 (151.4)
46 (174.1)
17.0 (1,2)
23.8 (1,6)
25.0 (1,7)
33.1 (2,25)
17.0 (1,2)
25.0 (1,7)
33.1 (2,25)
18 x 18 (5.5 x 5.5)
14 x 26 (4.3 x 7.9)
18 x 22 (5.5 x 6.7)
14 x 26 (4.3 x 7.9)
18 x 18 (5.5 x 5.5)
18 x 22 (5.5 x 6.7)
14 x 26 (4.3 x 7.9)
135°F (57°C)
135°F (57°C)
135°F (57°C)
135°F (57°C)
155°F (68°C)
155°F (68°C)
155°F (68°C)
4 - 12 (102 -305)
4 - 6 (102 - 153)
4 - 12 (102 - 305)
6 - 12 (153 - 305)
4 -12 (102 - 305)
4 - 12 (102 - 305)
6 - 12 (153 - 305)