2.
Pendent
Conventional
Upright
Model F156 Upright, Pendent & Conventional Sprinklers
Installation Wrench:
Model D Sprinkler Wrench
Model F156/F1 or F2
Installation Data:
Nominal
Orifice
Thread
Size
Nominal K Factor
Sprinkler
Height
Approval
Organization
Sprinkler Identification Number
(SIN)
US
Metric
Upright
Pendent
Standard-Upright (SSU) and pendent Deflectors Marked to Indicate Position
½” (15mm)
(1)
½” NPT(R½)
5.6
80
2.25” (57mm)
1, 2, 3, 4
RA1325
(2)
RA1314
(2)(3)
Conventional-Install in Upright or Pendent Position
15mm
(1)
½” NPT(R½)
5.6
80
57mm
3, 4
RA1375
(1)
Refer to Bulletin 024 for Special Response Sprinklers (F1S5-56)
(2)
cULus Listed corrosion resistant (Polyester coated) sprinkler.
(3)
Polyester coated FM Approved sprinkler.
Model F156 Recessed Pendent Sprinkler
(1)
Installation Wrench:
Model GFR2 Sprinkler Wrench
Installation Data:
Nominal
Orifice
Thread
Size
K Factor
Sprinkler
Height
Sprinkler Identification Number
(SIN)
US
Metric
½” (15mm)
½” NPT(R½)
5.6
80
2.25” (57mm)
RA1314
(1)
Refer to escutcheon data table for approvals & dimensions
Model F156/FP