Installation

Model F1 Series sprinklers must be installed in accordance 
with NFPA13 and the requirements of all applicable authorities 
having jurisdiction.  Model F1-56-300 Series sprinklers must be 
installed with the Reliable sprinkler installation wrench identified 
in this Bulletin. Any other wrench may damage the sprinkler.  The 

Models W2 and W4 wrenches have two sets of jaws.  Use the 

smallest set of jaws that fit on the wrench flats of the sprinkler.  

A leak tight sprinkler joint can be obtained with a torque of 6 
to 18 lb-ft (11 to 24 N

.

m). Do not tighten sprinklers over the 

maximum recommended installation torque. Exceeding the 
maximum recommended installation torque may cause leakage or 
impairment of the sprinkler.

Glass bulb sprinklers have orange bulb protectors or protective 
caps to minimize bulb damage during shipping, handling and 

installation. Reliable sprinkler installation wrenches are designed 

to install sprinklers with bulb protectors in place. Remove the bulb 
protector at the time when the sprinkler system is placed in service 
for fire protection. Removal of the bulb protector before this time 
may leave the bulb vulnerable to damage. Remove bulb protectors 
by undoing the clasp by hand. Do not use tools to remove bulb 

protectors.

Standard Finishes

Special Application Finishes

Sprinkler

F1, F2 and FP

(2)

Escutcheons

Sprinkler

F1, F2 and FP

(2)

Escutcheons

Bronze

Brass

Electroless Nickel PTFE

(3)

Bright Brass

Chrome

Chrome

Bright Brass

(4)

Satin Chrome

White Polyester

(3)

White Polyester

Satin Chrome

Custom Color Polyester

Custom Color Polyester

(3)

Lead

(3)

Wax

(3)(6) 

Wax over Lead

(3)(6)

Notes:

1. 

Paint or any other coating applied over the factory finish will void all approvals and warranties.

2. 

Model FP escutcheons utilize a galvanized steel cup with a finished trim ring.

3. 

cULus Listed as corrosion resistant.

4. 

For 200°F (93°C) maximum temperature rated sprinklers only.

5. 

Clear wax used on ordinary temperature rated sprinklers; brown wax used on intermediate temperature rated sprinklers.  Brown wax may be used on 
high temperature rated sprinklers where the ambient temperature does not exceed 150°F (66°C).

Finishes

(1)

Table B

 Wrenches

Model W2 (upright, pendent)

Model W4 

(recessed, concealed pendent)

Model J (with guard installed)

Maintenance

Reliable Model F1-56-300 series sprinklers should be inspected 

and the sprinkler system maintained in accordance with NFPA 
25, as well as the requirements of any Authorities Having 

Jurisdiction.

Prior to installation, sprinklers should remain in the original 
cartons and packaging until used. This will minimize the potential 
for damage to sprinklers that could cause improper operation or 

non-operation.

Do not clean sprinklers with soap and water, ammonia liquid or 
any other cleaning fluids. Remove dust by gentle vacuuming 

without touching the sprinkler.

Replace any sprinkler which has been painted (other than factory 

applied). A stock of spare sprinklers should be maintained to 
allow quick replacement of damaged or operated sprinklers.  
Failure to properly maintain sprinklers may result in inadvertent 
operation or non-operation during a fire event.

Bulletin 075

October 2022

Page 5 of 6

www.reliablesprinkler.com

Содержание F1-56-300 Series

Страница 1: ...1 56 300 series sprinklers are specifically listed with and may only be installed with Reliable listed recessed escutcheons Refer to the technical information on the following pages for specific listings for recessed and concealed installations and refer to Figure 3 for dimensional information When fitted with an approved water shield these sprinklers may considered intermediate sprinklers for use...

Страница 2: ...nse Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C Guards Shields New Frame F 1 Guard F 3 Guard with Shield Guards and Shields Legacy Frame C 3 Guard with Shield D 1 Guard D 3 Guard with Shield Sprinkler Wrench Model W2 Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Listed Model F1 56 300 Uprig...

Страница 3: ...7 Guard F 8 Guard Shield Kit S 1 Shield Guards and Shields Legacy Frame D 1 Guard D 5 Guard with Shield S 1 Shield Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Listed Notes 1 286 F 141 C and higher temperature rated sprinkler not listed for recessed use 2 Not su...

Страница 4: ... mm Minimum Recess Maximum Recess 1 1 4 32 mm Face of Fitting to Face of Ceiling 7 8 22 mm at Max Recess 3 8 10 mm at Min Recess 2 1 4 57 mm Dia Hole in Ceiling 1 15 16 49 mm Dia 2 1 2 64 mm Dia Hole in Ceiling Models F1 F1FR Pendent Sprinkler with Model F2 Recessed Escutcheon 1 2 13mm Nominal Adjustment F1_REC_PEND Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assembli...

Страница 5: ...ester 3 White Polyester Satin Chrome Custom Color Polyester Custom Color Polyester 3 Lead 3 Wax 3 6 Wax over Lead 3 6 Notes 1 Paint or any other coating applied over the factory finish will void all approvals and warranties 2 Model FP escutcheons utilize a galvanized steel cup with a finished trim ring 3 cULus Listed as corrosion resistant 4 For 200 F 93 C maximum temperature rated sprinklers only...

Страница 6: ...ing Model F1 56 300 Deflector Orientation Upright Pendent Temperature Rating See sprinkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B Sprinkler Wrench Model W2 upright non recessed pendent Model W4 recessed concealed pendent Model J with guard installed Note 286 F 141 C and higher temperature rated sprinklers are not listed to b...

Отзывы: