background image

Model F1-56-300 Pendent Sprinkler

SIN RA2514

 

Technical Specifications

 Style:

Pendent
Recessed Pendent

 Threads:

 1/2” NPT or ISO 7-R1/2

 Nominal K-Factor:

 5.6 (80 metric)

 Max. Working Pressure:

 300 psi (20.7 bar)

 

Material Specifications

 Thermal Sensor:

 5 mm Glass Bulb

 Sprinkler Frame:

 Brass Alloy

 Cap:

 Bronze Alloy

 Sealing Washer:

 Nickel with PTFE

 Load Screw:

 Copper Alloy

 Deflector:

 Brass Alloy

 

Sprinkler Finishes 

(See Table B)

 

Sensitivity

Standard response

Temperature Ratings 

(1)

 135°F (57°C)
 155°F (68°C)
 175°F (79°C)
 200°F (93°C)
 286°F (141°C)

360°F (182°C)

 

 

Recessed Escutcheons

 Model F1
 Model F2
 Model FP

Guards & Shields (New Frame)

(2)

F-7 Guard
F-8 Guard/Shield Kit

S-1 Shield

Guards and Shields (Legacy Frame)

D-1 Guard

D-5 Guard with Shield

S-1 Shield

Sprinkler Wrenches

 Model W2 (non-recessed)
 Model W4 (recessed or concealed)

 Model J (New frame with guard installed)
 Model JD (Legacy frame with guard installed)

 

Listings and Approvals

 cULus Listed

Notes:

1. 

286°F (141°C) and higher temperature rated sprinkler not listed for recessed use.

2.  Not suitable for recessed pendent installation.

Model F1-56-300 Pendent Sprinkler Components and Dimensions

Figure 2

F1FR_HALF_PEND_INT

Deflector

Glass Bulb

(3 mm)

Wrench Flat

Threads

3 1/4" [83mm]

2 1/4" [57mm]

1" [25mm]

Load Screw

Cap/Seal

Assembly

Shown with Optional S-1 Water

Shield (Ordered Separately)

Note: 

Please refer to Figure 3 for recessed installation.

Bulletin 075

October 2022

Page 3 of 6

www.reliablesprinkler.com

Содержание F1-56-300 Series

Страница 1: ...1 56 300 series sprinklers are specifically listed with and may only be installed with Reliable listed recessed escutcheons Refer to the technical information on the following pages for specific listings for recessed and concealed installations and refer to Figure 3 for dimensional information When fitted with an approved water shield these sprinklers may considered intermediate sprinklers for use...

Страница 2: ...nse Temperature Ratings 135 F 57 C 155 F 68 C 175 F 79 C 200 F 93 C 286 F 141 C 360 F 182 C Guards Shields New Frame F 1 Guard F 3 Guard with Shield Guards and Shields Legacy Frame C 3 Guard with Shield D 1 Guard D 3 Guard with Shield Sprinkler Wrench Model W2 Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Listed Model F1 56 300 Uprig...

Страница 3: ...7 Guard F 8 Guard Shield Kit S 1 Shield Guards and Shields Legacy Frame D 1 Guard D 5 Guard with Shield S 1 Shield Sprinkler Wrenches Model W2 non recessed Model W4 recessed or concealed Model J New frame with guard installed Model JD Legacy frame with guard installed Listings and Approvals cULus Listed Notes 1 286 F 141 C and higher temperature rated sprinkler not listed for recessed use 2 Not su...

Страница 4: ... mm Minimum Recess Maximum Recess 1 1 4 32 mm Face of Fitting to Face of Ceiling 7 8 22 mm at Max Recess 3 8 10 mm at Min Recess 2 1 4 57 mm Dia Hole in Ceiling 1 15 16 49 mm Dia 2 1 2 64 mm Dia Hole in Ceiling Models F1 F1FR Pendent Sprinkler with Model F2 Recessed Escutcheon 1 2 13mm Nominal Adjustment F1_REC_PEND Reducing Fitting Reducing Fitting Reducing Fitting Note Model FP recessed assembli...

Страница 5: ...ester 3 White Polyester Satin Chrome Custom Color Polyester Custom Color Polyester 3 Lead 3 Wax 3 6 Wax over Lead 3 6 Notes 1 Paint or any other coating applied over the factory finish will void all approvals and warranties 2 Model FP escutcheons utilize a galvanized steel cup with a finished trim ring 3 cULus Listed as corrosion resistant 4 For 200 F 93 C maximum temperature rated sprinklers only...

Страница 6: ...ing Model F1 56 300 Deflector Orientation Upright Pendent Temperature Rating See sprinkler technical specifications Sprinkler Finish See Table B Recessed Escutcheon F1 F2 FP Escutcheon Finish See Table B Sprinkler Wrench Model W2 upright non recessed pendent Model W4 recessed concealed pendent Model J with guard installed Note 286 F 141 C and higher temperature rated sprinklers are not listed to b...