Maintenance
Model DH56 Quick Response Dry Sprinklers should be in-
spected and the sprinkler system maintained in accordance
with NFPA 25. Do not remove the factory applied thermally
sensitive wax fillet between the bulb supporting cup and the
wrenching boss. Do not replace this wax with a substitute
substance. An alternate substance may interfere with proper
operation of the sprinkler. Do not clean sprinklers with soap
and water, ammonia or any other cleaning fluids. Remove
dust by using a soft brush or gentle vacuuming. Remove any
sprinkler which has been painted (other than factory applied)
or damaged in any way. A stock of spare sprinklers should
be maintained to allow quick replacement of damaged or
operated sprinklers. Prior to installation, sprinklers should be
maintained in their original cartons and packaging until used
to minimize the potential for damage to sprinklers that would
cause improper operation or non-operation.
Model DH56 Quick Response
Extended Coverage Horizontal
Sidewall Dry Sprinkler Speci
fi
cation
Sprinklers shall be a [quick response – cULus Listed] ex-
tended coverage horizontal sidewall sprinkler for light hazard
occupancies. Sprinklers to be of bronze frame construction
with a special deflector capable of providing a discharge over
a coverage area of 28 ft. (8,5m) wide, and 10 ft. (3m) long
horizontal throw. Water seal assembly shall consist of a Teflon*
coated Belleville spring washer. Installation shall permit sprin-
kler deflectors to be positioned 4“ (102mm) to 12” (305mm)
below the ceiling. Sprinklers shall have a nominal K-factor
of 5.6 (80), and 1” NPT thread. Sprinkler temperature rating
shall be [155°F (68° C)] and [200°F (93°C)]. Rated working
pressure shall be 250 psi (17.2 bar). Standard finish: [white]
[chrome][bronze][Special finish– specify]. Quick response
extended coverage horizontal sidewall dry sprinklers shall be
Reliable Model DH56, SIN RA1664 (Bulletin 016).
For recessed EC horizontal sidewall sprinklers: Replace
“horizontal sidewall” with “recessed horizontal sidewall.” Add:
(1) Recessed escutcheon assembly shall be a two-piece es-
cutcheon of push-on and thread off design with ½” (13mm)
adjustment. Standard finish shall be chrome, white and brass.
Quick response recessed horizontal sidewall sprinklers shall
be Reliable Model DH56, SIN RA1664 (Bulletin 016).
For concealed EC horizontal sidewall sprinklers: Replace
“horizontal sidewall” with “concealed horizontal sidewall.”
Add: Cover plate assembly shall consist of a brass cover
plate and copper alloy retainer flange. Method of attaching
the cover plate to the sprinkler cup shall be a push-on and
thread-off design allowing a ½” (13mm) cover plate adjust-
ment. Cover plate temperature rating shall be 135°F (57°C)
for 155°F (68°C) dry sprinkler and 165°F (74°C) for 200°F
(93°C) dry sprinkler. A bulb protector shall be provided and
factory installed inside the sprinkler cup to protect the glass
bulb from damage, which could occur during construction
before the cover plate is installed. Standard cover plate finish:
[white] [Custom Color– specify]. Quick response extended
coverage concealed horizontal sidewall dry sprinklers shall
be Reliable Model DH56, SIN RA1664 (Bulletin 016).
Technical Data:
K Factor
Thread
Size
Temperature
Rating
Maximum
Ambient
Temperature
Sprinkler
Identi
fi
cation
Number
(SIN)
US Metric
Sprinkler
SWC
Cover
5.6
80
1”
155°F
(68°C)
135°F
(57°C)
100°F
(38°C)
RA1664
175°F
(79°C)
165°F
(74°C)
150°F
(66°C)
200°F
(93°C)
165°F
(74°C)
150°F
(66°C)
Coverage Area
Maximum Coverage
Area Width x Length
ft x ft (m x m)
Flow Rate
gpm (L/min)
Pressure
psi (bar)
28 x 8 (8,5 x 2,4)
23 (87,1)
16.9 (1,2)
28 x 10 (8,5 x 3)
28 (106)
25 (1,7)
Approval Type:
• Quick Response, Extended Coverage.
• Approved for installation in accordance with NFPA 13
for light hazard occupancies.