background image

4.

Step 3

Step 2

Step 1

Fig. 2 - XLO2 Wrench

Fig. 3 - F3 Wrench

Maintenance

Model DH56 Quick Response Dry Sprinklers should be in-

spected and the sprinkler system maintained in accordance 
with NFPA 25.  Do not remove the factory applied thermally 
sensitive wax fillet between the bulb supporting cup and the 
wrenching boss.  Do not replace this wax with a substitute 
substance.  An alternate substance may interfere with proper 
operation of the sprinkler.  Do not clean sprinklers with soap 
and water, ammonia or any other cleaning fluids.  Remove 
dust by using a soft brush or gentle vacuuming.  Remove any 
sprinkler which has been painted (other than factory applied) 
or damaged in any way.  A stock of spare sprinklers should 
be maintained to allow quick replacement of damaged or 
operated sprinklers.  Prior to installation, sprinklers should be 
maintained in their original cartons and packaging until used 
to minimize the potential for damage to sprinklers that would 
cause improper operation or non-operation.

Model DH56 Quick Response
Extended Coverage Horizontal
Sidewall Dry Sprinkler Speci

fi

 cation

Sprinklers shall be a [quick response – cULus Listed] ex-

tended coverage horizontal sidewall sprinkler for light hazard 
occupancies.  Sprinklers to be of bronze frame construction 
with a special deflector capable of providing a discharge over 
a coverage area of 28 ft. (8,5m) wide, and 10  ft. (3m) long 
horizontal throw. Water seal assembly shall consist of a Teflon* 
coated Belleville spring washer. Installation shall permit sprin-
kler deflectors to be positioned 4“ (102mm) to 12” (305mm) 
below the ceiling.  Sprinklers shall have a nominal K-factor 
of 5.6 (80), and 1” NPT thread.  Sprinkler temperature rating 
shall be [155°F (68° C)] and [200°F (93°C)].  Rated working 
pressure shall be 250 psi (17.2 bar).  Standard finish: [white]
[chrome][bronze][Special finish– specify]. Quick response 
extended coverage horizontal sidewall dry sprinklers shall be 
Reliable Model DH56, SIN RA1664 (Bulletin 016).

For recessed EC horizontal sidewall sprinklers:  Replace 

“horizontal sidewall” with “recessed horizontal sidewall.”  Add:  
(1) Recessed escutcheon assembly shall be a two-piece es-
cutcheon of push-on and thread off design with ½” (13mm) 
adjustment. Standard finish shall be chrome, white and brass.  
Quick response recessed horizontal sidewall sprinklers shall 
be Reliable Model DH56, SIN RA1664 (Bulletin 016).

For concealed EC horizontal sidewall sprinklers:  Replace 

“horizontal sidewall” with “concealed horizontal sidewall.” 

 

Add:  Cover plate assembly shall consist of a brass cover 
plate and copper alloy retainer flange.  Method of attaching 
the cover plate to the sprinkler cup shall be a push-on and 
thread-off design allowing a ½” (13mm) cover plate adjust-
ment.  Cover plate temperature rating shall be 135°F (57°C) 
for 155°F (68°C) dry sprinkler and 165°F (74°C) for 200°F 
(93°C) dry sprinkler.  A bulb protector shall be provided and 
factory installed inside the sprinkler cup to protect the glass 
bulb from damage, which could occur during construction 
before the cover plate is installed. Standard cover plate finish: 
[white] [Custom Color– specify]. Quick response extended 
coverage concealed horizontal sidewall dry sprinklers shall 
be Reliable Model DH56, SIN RA1664 (Bulletin 016).

Technical Data: 

K Factor

Thread 

Size

Temperature

Rating

Maximum

Ambient

Temperature

Sprinkler

Identi

fi

 cation

Number

(SIN)

US Metric

Sprinkler

SWC

Cover

5.6

80

1”

155°F   

(68°C)

135°F   

(57°C)

100°F

(38°C)

RA1664 

175°F   

(79°C)

165°F 

(74°C)

150°F

(66°C)

200°F   

(93°C)

165°F 

(74°C)

150°F

(66°C)

Coverage Area

Maximum Coverage 

Area Width x Length

ft x ft (m x m)

Flow Rate

gpm (L/min)

Pressure

psi (bar)

28 x 8 (8,5 x 2,4)

23 (87,1)

16.9 (1,2)

28 x 10 (8,5 x 3)

28 (106)

25 (1,7)

Approval Type:

•  Quick Response, Extended Coverage.
•  Approved for installation in accordance with NFPA 13  

for light hazard occupancies.

*DuPont Registered Trademark

Содержание DH56 HSW

Страница 1: ...See Fig 9 Approval Organizations 1 Listed by Underwriters Laboratories Inc and UL certified for Canada cULus 2 NYC MEA 258 93 E Patents US Patent No 7 841 418 Other Patents Pending Products Descriptio...

Страница 2: ...the Model XLO2 wrench1 see Fig 2 to tighten the sprinkler until it is secured in the sprin kler fitting Note The Model XLO2 wrench has a notch in it to accommodate the deflector top This wrench can o...

Страница 3: ...Fig 1 3...

Страница 4: ...me bronze Special finish specify Quick response extended coverage horizontal sidewall dry sprinklers shall be Reliable Model DH56 SIN RA1664 Bulletin 016 For recessed EC horizontal sidewall sprinklers...

Страница 5: ...nominal position Escutcheon adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 4 Note The Sprinkler Can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment pro vi...

Страница 6: ...6 Fig 7 Note Do not install the Model DH56 Dry EC Horizontal Recessed Sidewall Sprinkler in walls which have positive pressure in their side space Fig 6...

Страница 7: ...7 Fig 8...

Страница 8: ...f the sprinklers Escutcheon Data FP cup escutcheon assembly 13mm adjustment Finishes 1 Standard Finishes 1 Sprinkler Escutcheon Cover Plate White or Black Polyester 2 Chrome Bronze Brass 3 White Chrom...

Страница 9: ...400 6 GLASS BULB GLASS W GLYCERIN SOLUTION 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 8 OUTER TUBE GALVANIZED STEEL 9 INNER TUBE BRASS ALLOY PER UNS C23000 10 YOKE BRASS ALLOY PER UNS C38000 11 INLE...

Страница 10: ...oughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry...

Отзывы: