background image

2.

Environments wherein dry sprinklers are employed can 

be corrosive.  For this reason, Model DH56 dry sprinklers 
have a special wax fillet placed in the gap between the 
cup that supports the bulb and the wrenching boss.  This 
wax will not interfere with the operation of the sprinkler, and 
it prevents contaminants from entering the internal portion 
of the drop nipple.  The wax must not be removed.

Application

The Model DH56 is a horizontal sidewall dry sprinkler 

intended for installation in light hazard occupancies in ac-
cordance with NFPA 13.  These sprinklers are designed to 
provide fire protection in long and narrow spaces such as 
hallways, corridors, decks and rooms up to 28 feet (8,5m) 
wide and 10 feet (3m) long.  They are rated for 250 psi (17,2 
bar) and can be mounted between 4 and 12 inches (102 
and 305mm) down from the ceiling. 

General Installation Instructions

Model DH56 dry sprinklers must be installed only in  stan-

dard (ANSI B 16.3 class 150 and ANSI B 16.4 class 125) 
pipe tees in the horizontal position, even at branch line ends.  
They should not be installed into elbows or pipe couplings 
located on drop nipples to the sprinklers.  For these and 
other fittings including CPVC, the dry sprinkler should be 
installed into a fitting to allow protrusion into the fitting in ac-
cordance with the diagrams.  The “A” dimension of the dry 
sprinkler, which extends into a freezing zone from wet pipe 
systems, should be selected to provide, as a minimum, the 
specified lengths in inches shown in Fig. 1.

Caution:

Do not install Model DH56 HSW Dry sprinklers  into CPVC 
adapter fittings or tees that have an internal obstruction. 
This will damage the sprinkler and /or the fitting. Refer to 
Fig. 8

DH56 HSW 

To install the DH56 HSW dry sprinkler cut a 2

1

/

8

” diameter 

hole in the wall as shown in Fig. 4.  Use the Model F3 instal-
lation wrench (see Fig. 3) on the square boss to tighten the 
sprinkler until it is secured in the sprinkler fitting

1

. Apply a 

Teflon* based sealant to the sprinkler threads before install-
ing in the sprinkler. Installation is completed by removing 
the orange glass bulb-protector and assembling the slip-on 
escutcheon to the sprinkler’s can.

DH56 HSW/HB 

To install the DH56 HSW/HB dry sprinkler cut a 2½” di-

ameter hole in the wall as shown in Fig. 5.  Use the Model 
F3 installation wrench (see Fig. 3) on the square boss to 
tighten the sprinkler until it is secured in the sprinkler fitting

1

Apply a Teflon* based sealant to the sprinkler threads be-
fore installing in the sprinkler. Installation is completed by 
removing the orange glass bulb-protector and assembling 
the slip-on escutcheon to the sprinkler’s can.

DH56 HSW Recessed with FP Escutcheon 

To install the DH56 HSW dry sprinkler with the FP Escutch-

eon as a recessed sprinkler cut a 2

5

/

8

” diameter hole in the 

wall as shown in Fig. 6.  Temporarily remove the plastic pro-
tective cap, and then use the Model XLO2 wrench

1

 (see 

Fig. 2) to tighten the sprinkler until it is secured in the sprin-
kler fitting. 

Note:

 The Model XLO2 wrench has a notch in it 

to accommodate the deflector top. This wrench can only 
be inserted one way. Care must be taken not to damage 
the deflector during tightening. Apply a Teflon* based seal-
ant to the sprinkler threads before installing in the sprinkler.  
It is recommended that the sprinkler be protected during 
plastering and painting operations by reinstalling the plastic 
protective cap. Installation is completed by removing the 
protective cap and inserting the push-on escutcheon. Turn 
clockwise to adjust the escutcheon against the wall. 

DH56 HSW Concealed with SWC Cover Plate

To install the DH56 HSW dry sprinkler with the SWC cover-

plate as a concealed sprinkler, cut a 2

1

/

8

” diameter hole into 

the wall as shown in Fig. 7. Temporarily remove the plastic 
protective cap, and then use the Model XLO2 wrench

1

 (see 

Fig. 2) to tighten the sprinkler until it is secured in the sprin-
kler fitting. 

Note:

 The Model XLO2 wrench has a notch in it 

to accommodate the deflector top. This wrench can only 
be inserted one way. Care must be taken not to damage 
the deflector during tightening. Apply a Teflon* based seal-
ant to the sprinkler threads before installing in the sprinkler. 
It is recommended that the sprinkler be protected during 
plastering and painting operations by reinstalling the plastic 
protective cap. Installation is completed by removing the 
protective cap and inserting the coverplate.  Coverplate as-
semblies provide ½” (13mm) of adjustment. Final adjust-
ment is made by turning the coverplate clockwise until the 
skirt flange makes full contact with the wall surface. Cover 
removal requires turning in the counter-clockwise direction. 

Concealed coverplate assemblies are listed only for use 

with specific sprinklers. The use of any other concealed wall 
sprinkler or the use of the SWC coverplate on any sprinkler 
with which it is not specifically listed will void all guarantees, 
warranties, listings and approvals. 

Note:

 DH56 and DH56 Recessed Sprinklers have orange 

bulb protectors to minimize bulb damage during shipping, 
handling, and installation. REMOVE THIS PROTECTION AT 
THE TIME THE SPRINKLER SYSTEM IS PLACED IN SER-
VICE FOR FIRE PROTECTION. Removal of the protectors 
before this time may leave the bulb vulnerable to damage. 
RASCO wrenches are designed to install sprinklers when 
covers are in place. REMOVE PROTECTORS BY UNDO-
ING THE CLASP BY HAND. DO NOT USE TOOLS TO RE-
MOVE THE PROTECTORS.

*DuPont Registered Trademark

1

 Installation Wrenches:

  Throughout this technical bulletin, Reliable has specified specific installation wrenches for use on each version of our sprinklers. A pipe wrench may also 

be used to install a dry sprinkler provided that it only interfaces with the steel outer tube of the assembly (Item #8 on fig 10). Keep in mind that a pipe 
wrench will incorporate a large amount of torque into the final assembly. This torque will have to be matched or exceeded upon the sprinkler’s removal at 
a later date.

Содержание DH56 HSW

Страница 1: ...See Fig 9 Approval Organizations 1 Listed by Underwriters Laboratories Inc and UL certified for Canada cULus 2 NYC MEA 258 93 E Patents US Patent No 7 841 418 Other Patents Pending Products Descriptio...

Страница 2: ...the Model XLO2 wrench1 see Fig 2 to tighten the sprinkler until it is secured in the sprin kler fitting Note The Model XLO2 wrench has a notch in it to accommodate the deflector top This wrench can o...

Страница 3: ...Fig 1 3...

Страница 4: ...me bronze Special finish specify Quick response extended coverage horizontal sidewall dry sprinklers shall be Reliable Model DH56 SIN RA1664 Bulletin 016 For recessed EC horizontal sidewall sprinklers...

Страница 5: ...nominal position Escutcheon adjustment provides 6mm to 1 32mm A dimension adjustment range Fig 4 Note The Sprinkler Can protrudes 1 when escutcheon is in nominal position Escutcheon adjustment pro vi...

Страница 6: ...6 Fig 7 Note Do not install the Model DH56 Dry EC Horizontal Recessed Sidewall Sprinkler in walls which have positive pressure in their side space Fig 6...

Страница 7: ...7 Fig 8...

Страница 8: ...f the sprinklers Escutcheon Data FP cup escutcheon assembly 13mm adjustment Finishes 1 Standard Finishes 1 Sprinkler Escutcheon Cover Plate White or Black Polyester 2 Chrome Bronze Brass 3 White Chrom...

Страница 9: ...400 6 GLASS BULB GLASS W GLYCERIN SOLUTION 7 ORIFICE ADAPTOR BRASS ALLOY PER UNS C36000 8 OUTER TUBE GALVANIZED STEEL 9 INNER TUBE BRASS ALLOY PER UNS C23000 10 YOKE BRASS ALLOY PER UNS C38000 11 INLE...

Страница 10: ...oughout the United States Canada and foreign countries Automatic sprinklers Flush automatic sprinklers Recessed automatic sprinklers Concealed automatic sprinklers Adjustable automatic sprinklers Dry...

Отзывы: