Measures prior to commissioning
Operating_Manual_Fan_KXE_04_en.docx
49 / 128
The fan may only ever be switched on if the duct
work is connected to inlet and discharge.
Exception:
For free inlet fans, the corresponding accessory is to
be fitted in place of the duct work at inlet (e.g. round
filter, silencer, suction box with additional accessory).
DANGER
Inlet of fan!
Fatalities or extremely serious injuries resulting from
suction.
→ For free inlet fans:
Never stand in immediate proximity of the inlet.
Remove all objects from the area in front of the
inlet.
Cordon off the area in front of the inlet.
Work must be performed in the sequence as follows:
Remove the transport shutters and shrink-wrap foil from
the inlet and discharge of the fan
Guide the duct work of the plant toward the inlet and
discharge of the fan
Fit the flexible connections (optional) to inlet and
discharge
refer to chapter 8.4
Align the duct work to the fan openings and mount onto
the fan, ensuring that the duct work is not exhibiting any
warping
8.3 Connecting the duct work