
57
SPEcIAl FUnctIonS
nEtwoRkIng MUltIPlE contRollERS
12.0
12.1
In larger buildings with more than 14 zones where multiple manifolds are utilised, it is possible to use multiple masters to create a
single network. One master must be defined as the “network controlling master” by setting both dials to zero (see table below).
CP
BPV
CP
BPV
IV
MP
ZV
Circulating Pump
By Pass Valve
Isolating Valve
Main Pump
Zone Valve
Network Master
Submaster
Slave
MP
BA
1,1
BA
0,0
String 1
CP
BA
2,1
String 2
Up to 15 Strings
Up to 9 Masters
Up to 9 Masters
IV
IV
IV
IV
Add On Module
BA
1,2
BA
1,3
BA
2,2
BA
2,3
Master 1
Master 2
Hot Water Centrally
Mixed by Third Party
Add On Module
Signal to Switch the Boiler
Network Master can control up to 14 heated zones
ZV
ZV
50. Hydraulic Schematic for Networking of Multiple Controllers
Left Dial
Right Dial
Using more than one secondary pump
1. If more than one secondary pump is used, a separate string should
be created for each pump (see Fig. 50). On the first string all left hand
dials in the slaves must be set to 1, and the right hand dial should
be set in sequence from 1 to 9. On the second string of masters/
slaves all left hand dials should be set to 2 and the right hand dials
again should be set in sequence from 1 to 9. This numbering can be
continued for up to 15 strings.
2. All main controllers are interconnected using special cable via the
RJ 45 socket 1 or 2.
3. RJ 45 connection of string 1 to string 2 etc., can be achieved
via string 1 slave to string 2 submaster or string 1 slave to string 2
slave as shown in Fig.50.
4. An BA Master Controller can be used as the “network
controlling master” for central mixing control of supply water and
boiler switching.
Master and Slave
Left dial set to
Right dial set to
Network Controlling Master
0
0
String 1 Submaster
1
1
String 1 Slave
1
2 to 9
String 2 Submaster
2
1
String 2 Slave
2
2 to 9
Up to String 15 Submaster
1 to F
1