TSV3B TSV5B 6/4Mx5/4F load valve is fitted with an 

integrated thermostatic insert that will close the 

A

 inlet 

(from a heating system), if the return water temperature 

to the boiler (

AB

 outlet) is lower than the opening one. As 

soon as the opening temperature is reached, the 

thermostat starts opening the 

A

 inlet slowly and mixing 

the cold return water with the hot water from the boiler 

flow (

B

 inlet) with the aim to reach the opening temperature 

in the return pipe (

AB

 outlet).

At the same time, the valve closes the 

B

 inlet, limiting so

the hot water flow coming from the bypass till its complete

tight closure. Thanks to this, no balancing valve is needed.

The load valve is made of brass, element and plug seals 

are in EPDM, cone seal is made of NBR. 

Technical Data

Valve opening temperature

depending on the thermostatic element 

Control range

t

valve,opening

 + 5 °C

Connections

2x G 1" F, 1x G 6/4“ union nut 

Nominal inner diameter

DN 25

Materials

Housing, cone and plug 

brass

Spring

stainless steel

Element and plug seal

EPDM

Cone seal

NBR

Valve Pressure Drop Graph

The valve pressure drop value

moves between the two

curves depending on the

mixing ratio during mixing.

0,0

0,5

1,0

1,5

2,0

2,5

0,0

0,5

1,0

1,5

2,0

Δ

p [

H

2

O]

Q [m

3

/h]

A

AB, Kvs = 6,2 m

3

/h

B

AB, Kvs = 4,4 m

3

/h

B

AB

A

Содержание RGMAT E G60

Страница 1: ...www regulus eu RGMAT E G60 RGMAT E G60 EN Installation and Operation Manual RegulusRGMAT E G60 LOAD UNIT with UPM 3 insulated for heating systems...

Страница 2: ...es it prevents low temperature corrosion and boiler fire fouling Description consists of a UPM3 FLEX AS pump ball valves with union nuts TSV3B valve with automatic bypass balancing thermometer insulat...

Страница 3: ...may hinder or even disable its operation Always respect valid rules and boiler manufacturer s data during installation Possible Connection Example I The diagram shows a typical connection of a solid...

Страница 4: ...nlet limiting so the hot water flow coming from the bypass till its complete tight closure Thanks to this no balancing valve is needed The load valve is made of brass element and plug seals are in EPD...

Страница 5: ...t needed Pump control The circulation pump can be controlled by an external PWM signal profile for use in heating systems or without a PWM signal by selecting a pump performance curve A maximum curve...

Страница 6: ...n the pump runs at factory settings or the last setting The display shows the current pump performance Setting selection for UPM3 To select your desired setting press the button repeatedly until you f...

Страница 7: ...Pump wiring socket for power supply A and signal transmission B power supply A and signal B connectors N brown L brown PE yellow green PWM GDN blue PWM out black PWM in brown Permissible positions...

Страница 8: ...iping or horizontally to the left of a boiler When being installed horizontally to the left of a boiler the Load Unit needs to be turned by 180 and the TSV3B valve turned as shown in the pics below 20...

Отзывы: