- 3 -
1.
The unit is designed for installation in external walls with a thickness up to 280 mm. For wall thicknesses up to
500 mm an extension kit is available (EXT100).
2.
The unit must be located so that the ambient temperature will
not exceed 40° C.
3.
Do not install the appliance in the vicinity of excessive levels
of airborne oil or grease.
4.
If the unit is installed in a room containing a fuel burning
appliance, suf
fi
cient air replacement shall be ensured for both
appliances.
5.
The grille frame shall not be located less than 125 mm away
from any wall or projecting surface (Fig. 2).
6.
The external grille of the unit must be placed at least
500 mm away from any
fl
ue of gas or solid fuel appliances.
This is to avoid back
fl
ow of gases entering the room.
7.
All safety regulations and requirements must be strictly followed to prevent hazards to life and property both during
and after installation and during subsequent maintenance or servicing.
8.
Ensure the mains electrical supply is switched off before commencing installation or maintenance.
2.0 Installation Conditions
Fig. 2
Fig. 3
adjustable