57
the flow temperature exceeds a certain value, established by the
manufacturer depending on the heat pump type (see the heat pump
service manual).
Max.return t. (°C)
.......
Max. heat pump return temperature. When this temperature is
exceeded, the heat pump is switched off. The heat pump will also
switch off when the return temperature exceeds a certain value,
established by the manufacturer depending on the heat pump type
(see the heat pump service manual).
Min.outd.t. (°C)
..........
Min. outdoor temperature for heat pump operation. When the
temperature drops below this value, the heat pump is switched off. The
heat pump will also switch off when the outdoor temperature drops
below a certain value, established by the manufacturer depending on
the heat pump type (see the heat pump service manual).
Max.outd.t (°C)
.......... Max. outdoor temperature. When the outdoor temperature exceeds
this value, the heat pump is switched off.
Max.brine.t. (°C)
........ Max. brine circuit temperature. When the brine temperature exceeds
this value, the heat pump is switched off. Applies to ground-coupled
heat pumps only.
Restart time (min)
...... Min. delay between two heat pump starts.
Min.run.time (min)
.................................... Minimum time of HP operation. It is activated either after compressor
start, or after DHW heating is finished (if the heating circuit demand is
higher than 10°C), or after a defrosting cycle is finished.
5.6.
Heat pump 1 operating data
In this menu, detailed information about heat pump number 1 is displayed. For data on other
pumps in the cascade, it is necessary to use the web interface.
Flow temp. (°C)
.......... HP flow temperature
Return t. (°C)
.............. HP return temperature
Hot gas (°C)
................ HP compressor hot gas temp.
Flow temp. (°C)
.......... HP flow temperature
Cond.temp. (°C)
......... HP condensing temp.
Cond.press. (bar)
....... HP condensation pressure
Evapor.1 t. (°C)
........... Temperature of discharged air/incoming brine circuit
Evapor.2 t. (°C)
........... Temperature of brine into the ground loop from HP
Outdoor t. (°C)
............ Outdoor temp. to HP (air source HPs only)
Evapor. t. (°C)
............. HP evaporation temp.