REGIS T-X-B – Access or time and attendance controller
10/2016
Black line
www.jantar.si
Inputs, outputs and environment
Inputs:
Inputs are realized with opto-isolators. The input is active, when
pulled to ground with an open collector transistor or mechanical
switch, which is connecting the input pin of the controller to the
Ground.
Outputs:
Output has a pre-installed protection diode for an inductive load. It
is also protected from current overload. The best way is to use a
0.25A el. strike or a 0.5A el. magnet, which has to be connected to
the same positive pole (+) as the controller. Connect the negative
pole (-) to the door strike output (wire 3). When the output is
active it is pulled to ground. This can be changed with function 5 –
negate output (for el. magnet).
Environment:
Do not install the controller on/in a place, where it can come in
contact with water. You must assure good cable joints, protected
against moisture, otherwise corrosion may damage the controller.
Damage in such cases is not covered by the warranty.
Regis T-1-B reading range:
The controller has a program algorithm that, at power start, sets
parameters based on the installation environment, so as to ensure
an optimal reading range.
DO NOT
install the controller directly on
metal surfaces and/or cover it with a metal cover; it may stop
working/reading. If you plan to test the controller and move it onto
different surfaces, then you have to reset it (power off/on) on each
surface.
Regis T-1-B reading field:
The controller has a reading card field active over 1/3 of the
controller.
If the controller is in vertical position the reading field is on the
bottom side of the controller.
If the controller is in horizontal position the reading field is on the
right side of the controller.
ACCESS OR TIME AND ATTENDANCE
CONTROLLER
Access controller
As an access controller, it is intended for controlling entries, exits
and passes of users in the system and controlling sliding doors,
ramp, el. strike, turning alarm on/off… It needs to be set with V7
or CODEKS software.
Time and attendance controller
As a time and attendance controller, it is intended to register the
employee’s arrivals and exits from work, lunch break, private and
business exits, sick leave... It needs to be set with V7 or CODEKS
software. In software you need to choose option “Time and
attendance” for controller and reader. Set the software according
to your requirements (time tables, users...) and send the tables.
The keypad will serve for choosing different time intervals (private,
business…).
The controller switches to access or time and attendance
controller when tables are sent by the software or when it is
set to mode 4 with function 9. Change the controller’s
address from 255 to any number between 1 and 254. If you
have more controllers on the communication line, don’t
duplicate addresses. Add them one by one on the
communication line, because every controller has address
255 by default.
Communication
Ethernet:
Connect the controller to the computer through your LAN via
Ethernet connector. Use at least UTP CAT 5e cable. Adjust network
settings of the controller using the Codeks Device Manager
software so that it will function properly in your network. Please
consult Codeks Device Manager manual.
S - Spider mode
In the Spider mode the controller can be used as a communication
converter, from which you can continue RS485 communication line
to the other controllers. When the controller is reset to the factory
settings (brainwash), the controller address is set to 254.
RS485:
Connect the controller to the computer, with one of the power
supplies, with communication converter, from the Spider family:
Spider W5-USB, Spider W5-NET, Spider W40+NET.
The RS485 communication bus is used between the controllers and
Jantar software. Up to 128 controllers can be lined up into one
communication line. The maximum length of the communication
line is 1000 cable meters. It is recommended that you use an FTP
or S-FTP cable. Only a serial connection of controllers in a single
communication line is allowed.
Star (parallel) connection is not
allowed
.
All shields of S-FTP cables must be wired together and at
one
point
connected to the earth. Individual connections to the earth
are not allowed. Do not connect the shield of the cable to the
ground of the controller.
Reset to the factory settings (brainwash):
When the controller is reset to the factory settings (brainwash), the
controller address is set to 254.
ORDERING CODES
REGIS
[box]-[card]-[software]
Box:
T
Card:
1
– reading frequency 125kHz (cards)
3
– reading frequency 13.56MHz (cards)
Model:
B
– Black line
Code
Description
REGIS T-1-B
Standalone or access controller in
T
box,
Frequency 125kHz, for CODEKS software,
Integrated Ethernet
REGIS T-3-B
Standalone or access controller in
T
box,
Frequency 13.56MHz, for CODEKS software,
Integrated Ethernet
OTHER
Warranty only applies when the controller Regis is used with power
supply or/and communication converter from the Spider family.
Please read through our warranty and disclaimer statements.
Connection scheme and additional support for the use of this
product can be found on:
http://www.jantar.si/forum/en