INSTRUCTION

 

i

Read this instruction before installation 

and wiring of the product

RVAN5-24A

1

Valve actuator for 0(2)...10 V control

RVAN5-24A is a valve actuator designed for control of Regin valves. 
The actuator has automatic self stroke adjustment and can be oper-
ated manually.

Technical data

Supply voltage 

 

24 V AC ±15 %, 50/60 Hz 

 

 

or 24 V DC ±15 % 

Control signal 

 

0(2)...10 V DC 

Power consumption 

Max. 4.5 W 

Stroke 

 

10...30 mm 

Stroke time 

 

1.5 s/mm 

Force 

 

500 N 

Ambient temperature 

0...50°C 

Storage temperature 

-40...80°C 

Ambient humidity   

10...90 % RH 

Dimensions (WxHxD) 

150 x 253 x 85 mm 

Protection class   

IP54

Installation

If the valve stem adaptor and valve throat adaptor are not already mount-
ed on the valve, mount them. Pull the valve stem out as far as possible. 
Remove the locking bolt (U-bolt) from the actuator yoke. Insert the valve 
stem into the yoke and make sure that the stem adaptor engages the hole 
in the angled iron of the actuator drive spindle.
The groove in the valve throat adaptor must be made to line up with the 
U-bolt mounting holes on the actuator. If the spindle needs moving in or 
out for this to happen, depress the central part of the manual button and 
turn it clockwise for the actuator spindle to extend, and anti-clockwise for 
it to retract (see Manual override). When the valve is in the correct posi-

tion, insert the U-bolt. Tighten the bolt nuts until the valve is firmly gripped. 

Disassembly in reverse order.

Mounting positions

90º

90º

Wiring

24 V AC/DC 

1

2

3

4

5

1

2

3

4

5

6

Ov

er

ride 

in

pu

t

Y    0(2)...10 V DC

Control signal from 

controller 

U    0...10 V DC

Measuring voltage 

for position indication 

Signal neutral

Y

U

B

M

G0

G

Stroke and end position calibration

Stroke and end position calibration is not necessary due to a construction 
utilizing end position stops. When the valve reaches the end position, a 
force is generated.

 Once the force of the actuator reaches a predefined 

level, the limit switch automatically halts the drive motor.

Override

Activation of the override input will force the valve to the maximum 
open position.

Manual override

To manually set the valve position, first depress the central part of the 
knob, until it clicks and remains depressed (1 in the figure). Then the 

valve position can be changed manually by turning the knob (2 in the 

figure). When the knob is turned clockwise, the drive rod is pushed 

outwards and when the knob is turned anti-clockwise, the drive rod is 
pulled inwards. 
To return to normal operation, set the knob so that it is in line with the 
text ”Auto” on the cover. Then depress the outer parts of the knob (3 

in the figure). The central depressed part will pop out, and the actua

-

tor will return to normal operation.
Note: After any manual operation the actuator will always run through 
a zero point calibration.

DIP switches

There are five DIP switches for setting different functions. Follow the 

table below for setting the DIP switches. 
Adjusted settings will be valid only after the next power-on.

1 (On)

0 (Off)

SW1

Spindle down when the 
valve is closed

Spindle up when the valve is 
closed (FS=factory setting)

SW2

Y = 2...10 V DC

Y = 0...10 V DC (FS)

SW3

Reverse operation

Direct operation (FS)

SW4

Y signal split in accordance 
with the setting of SW5

No split function (FS)

SW5

5(6)...10 V = 0...100 %

0(2)...5(6) V = 0...100 % (FS)

RVAN5-24A

10473A

 

JUL

 13

EN

Содержание RVAN5-24A

Страница 1: ...controller U 0 10 V DC Measuring voltage for position indication Signal neutral Y U B M G0 G Stroke and end position calibration Stroke and end position calibration is not necessary due to a construct...

Страница 2: ...tion and the blue marker in the completely closed valve position For cooling valves the blue marker should be in the completely open valve position and the red marker in the completely closed valve po...

Страница 3: ...n 0 Off SW1 Spindel ned vid st ngd ventil Spindel upp vid st ngd ventil FI fabriksinst llning SW2 Y 2 10 V DC Y 0 10 V DC FI SW3 Omv nd verkan Direkt verkan FI SW4 Y signalsplit enligt inst llning av...

Страница 4: ...andbedienung B gelschraube anbringen wenn sich das Ventil in der korrekten Position befindet Muttern anziehen bis das Ventil vollkommen fest ist Demontage erfolgt in umgekehrter Reihenfolge ndl gesmar...

Страница 5: ...10 V DC umgewandelt SW3 Invertierte normale Stellrichtung On Invertierte Stellrichtung Bei ansteigendem Stellsignal schlie t der Stellantrieb das Ventil Off Normale Stellrichtung Bei ansteigendem Stel...

Страница 6: ...V DC U 0 10 V DC Signal neutre Signal de commande du r gulateur Tension de mesure pour l indicateur de position Entr e for age Y U B M G0 G talonnage de la course et des limites L talonnage de la cour...

Страница 7: ...cours Voyant vert clignotant lentement Le r glage a t chang pendant le fonctionnement Le nouveau r glage prendra effet la prochaine mise sous tension Voyants rouge et vert allum s fixes Fin de course...

Отзывы: