RVAN5-24A
2
SW1 Operational direction of the valve
On: The valve is closed when the stem is in its lowest position.
Off: The valve is closed when the stem is in its highest position.
SW2 Control signal
On: 2...10 V DC
Off: 0...10 V DC
The actuator can also be connected to a 4...20 mA control signal.
In this case, a 500 Ohm resistor should be installed between the
control signal input (terminal 3) and system neutral (terminal 2)
and SW2 should be set to position On (2...10 V DC).
The control signal will then be converted to 2...10 V DC.
SW3 Reverse/Direct operation
On: Reverse operation. The actuator closes the valve on increasing
control signal.
Off: Direct operation. The actuator opens the valve on increasing
control signal.
SW4 Split function
On: Split function. Two actuators can share a control signal and work
in sequence.
Off: No split function.
SW5 Working range when using split function
On: 5…10 V= 0…100 % (6…10 V when SW2=On)
Off: 0…5 V= 0…100 % (2…6 V when SW2=On)
LEDs
The actuator has two LEDs with indications according to the table
below.
Indication
Green steady light
Actuator working properly
Green light quick flashing
Test run in progress
Green light slow flashing
The setting was changed during the
operation. The new setting will be
valid after the next power on.
Red and green steady light
End position reached
Red light slow flashing
Override operating mode
Red steady light
Operation faulty, either the improper
installation or the valve stroke lost
End position markers
There is a red and a blue plastic end position marker on the actuator
linkage. The markers can easily be moved in order to show when the
actuator is closed/open for heating/cooling.
For heating valves, the red marker should be in the completely open valve
position and the blue marker in the completely closed valve position.
For cooling valves, the blue marker should be in the completely open
valve position and the red marker in the completely closed valve position.
EMC emissions & immunity standards
This product conforms to the requirements of the EMC Directive
2004/108/EC through product standards EN 60730-1:2000 and
EN 60730-2-14:1997.
RoHS
This product conforms with the Directive 2011/65/EU of the European
Parliament and of the Council.
Contact
AB Regin, Box 116, 428 22 Kållered, Sweden
Tel: +46 31 720 02 00, Fax: +46 31 720 02 50
www.regincontrols.com, [email protected]
Ventilställdon för 0(2)...10 V-styrning
RVAN5-24A är ett ventilställdon för styrning av Regins ventilsorti-
ment. Ställdonet har automatisk slaglängdsjustering och går att styra
manuellt.
Tekniska data
Matningsspänning
24 V AC ±15 %, 50/60 Hz
eller 24 V DC ±15%
Styrsignal
0(2)...10 V DC
Effektförbrukning
Max. 4,5 W
Slaglängd
10...30 mm
Ställtid
1,5 s/mm
Ställkraft
500 N
Omgivningstemperatur 0...50°C
Lagringstemperatur -40...80°C
Omgivande luftfuktighet
10...90 % RH
Dimensioner (BxHxD)
150 x 253 x 85 mm
Skyddsklass
IP54
Installation
Om spindeltopp och ventilhalsadapter inte redan är monterade på
ventilen, montera dem. Dra ut ventilspindeln så långt det går.
Ta bort muttrarna och U-klämman från ställdonets ok. Trä in ventil-
spindeln i oket. Se till att ventilhalsadaptern hakar fast i hålet i brickan
på drivspindeln.
Spåret på ventilhalsadaptern måste komma i linje med U-klämmans
skruvhål på ställdonet. Om drivspindeln behöver flyttas in eller ut
för att detta ska ske, tryck ned mittknappen på manöverratten och
vrid denna medurs för att flytta ut spindeln och moturs för att flytta in
spindeln (se Manuell överstyrning). När ventilen är i rätt läge, sätt fast
U-klämman. Dra åt muttrarna tills ventilen sitter stadigt fast.
Nedmontering sker i omvänd ordning.