RU-DFO

Technical data

Supply voltage

Fed from RCP

Ambient temperature

0...50°C

Storage temperature

-20...+70°C

Ambient humidity

Max 90 % RH

Protection class

IP20

Communication

Same as RCP

Built-in temperature sensor

NTC type, measuring range 0...50°C, accuracy ±0.5°C at 15...30°C

Material, casing

Polycarbonate, PC

Weight

110g

Colour

Signal white RAL 9003

Cables

Cable for connection between RU and RCP

Type RJ12, max length 30 m

Cables that can be ordered from Regin

RU-CBL3 (length 3 m)

RU-CBL10 (length 10 m)

CE

This product carries the CE mark. For more information, see www.regincontrols.com.

Inputs and outputs

In RCP
Terminal blocks in RCP

So-called lift type for cable cross-section 2.1 mm

2

Setpoint settings via Regio tool

© 

or in the display

Basic heating setpoint

5...40°C

Basic cooling setpoint

5...50°C

Setpoint displacement

±0...10°C (FI=±3°C)