Display handling

The display has the following indications:

Occupancy 

indication

Open window

Indoor / 

outdoor 

temp.

Setpoint

Forced ventilation

Changeable value

Current room 

temperature 

in °C to one 

decimal point

COOL/HEAT: 

Shows if the unit controls 

according to the heating 

or cooling setpoint

OFF: Unoc-

cupied (also  

shows tem-

perature) or 

Off 

 indication 

(only OFF)

STANDBY: 

Standby indication 

SERVICE: 

Parameter setting

Fan

Auto/Man. 

indication 

for the fan

Current 

fan speed 

(0, 1, 2, 3)

It is possible to set different parameter values in a para-
meter menu in the display, using the buttons on the con-
troller. You change parameter values with the INCREASE 
and DECREASE buttons and confirm changes with the 
Occupancy button. 

INCREASE
DECREASE

Occupancy button

The Occupancy button

If you press the Occupancy button for less than 5 seconds 
when the controller is in the preset operating mode 
(Occupied or Stand-by), the controller changes to opera-
ting mode Bypass. It will automatically return to the pre-
set operating mode after a configurable time (FS=2 hours).  
If you press the button for less than 5 seconds when the 
controller is in Bypass, it changes operating mode to the 
preset operating mode.
When the Occupancy button is held depressed for more 
than 5 seconds, the controller changes operating mode to 
”Shutdown” (Off/Unoccupied), regardless of the current 
operating mode. Via the display, you can configure which 
operating mode, Off or Unoccupied, should be activated 
on ”Shutdown” (FS=Unoccupied). If you press the 
Occupancy button for less than 5 seconds in Shutdown, 
the controller returns to Bypass.

Forced ventilation

Regio has a built-in function for forced ventilation. A 
short press on the Occupancy button activates the output 
that has been configured for forced ventilation, for exam-
ple for a damper.

Setpoint

In Occupied mode, the controller operates from a heating 
setpoint (FS=22°C) or a cooling setpoint (FS=24°C) that 
can be changed using the INCREASE and DECREASE 
buttons. 
Pressing on INCREASE increases the current setpoint by 
0.5°C with each press up to the max. limit (FS = +3°C). 
Pressing on DECREASE decreases the current setpoint by 
0.5°C with each press down to the min. limit (FS = -3°C).
Switching between heating and cooling setpoints is done 
automatically in the controller depending on the heating 
and cooling requirement.

Fan control

RU-DFO has a fan button. When you press the button, 
a symbol is shown in the display for 10 seconds. During 
this time, it is possible to change the fan speed using the 
INCREASE/DECREASE buttons. 
The controller has the following positions:

Auto

 

Automatic control of the fan speed to maintain  

 

desired room temperature. 

0

 

Fan off. 

I

 

Manual position with low speed. 

II

 

Manual position with medium speed. 

III

 

Manual position with high speed.

In operating modes Off and Unoccupied, the fan is 
stopped, regardless of the setting in the display.