background image

DISCLAIMER

 

The information in this manual has been carefully checked and is believed to be correct. Regin, however, makes no warranties 
in  regard  to  the  contents  of  this  manual.  Users  are  requested  to  report  errors,  discrepancies  or  ambiguities  to  Regin,  so  that 
corrections may be made in future editions. The information in this document is subject to change without prior notification.  

The  software  described  in  this  document  is  supplied  under  licence  by  Regin  and  may  be  used  or  copied  only  in  accordance 
with the terms of the licence. No part of this document may be reproduced or transmitted in any form or fashion, electronically 
or mechanically, without the express, written permission of Regin. 

COPYRIGHT

 

 AB Regin. All rights reserved. 

TRADEMARKS

 

Corrigo E is a registered trademark of AB Regin. 

Other  product  names  mentioned  in  this  document  are  used  for  identification  purposes  only  and  may  be  the  registered 
trademarks of their respective companies.  

 

Revision B, December 2012 

 

Содержание E-BACNET2-V

Страница 1: ...E BACNET2 V manual Copyright AB Regin Sweden 2012 Copyright AB Regin Sweden 2012...

Страница 2: ...software described in this document is supplied under licence by Regin and may be used or copied only in accordance with the terms of the licence No part of this document may be reproduced or transmit...

Страница 3: ...HAPTER 3 CONFIGURATION 6 Refresh 6 Wink 6 Edit Change settings 6 Upgrading the software version of the unit 8 APPENDIX 1 LIST OF VARIABLES FOR E BACNET2 V 10 Analog Inputs 10 Analog Values 11 Binary I...

Страница 4: ...ace via the PLA ELA address 254 254 To change these settings see chapter 3 The Corrigo E controller is connected to the converter with the supplied cable and communicates with the SCADA system via the...

Страница 5: ...LAN1 port of the converter and a network port The converter may also be connected directly to a computer but this requires a crossover RJ45 cable not included Connect the power supply to the converter...

Страница 6: ...able converters connected to the network are displayed Refresh Pressing the Refresh button will update the list of converters Wink Wink is a function that can be used to ensure that the correct physic...

Страница 7: ...atically added after it UDP Port BACnet IP standard is 47808 The checkbox Foreign device is used when E BACNET2 V is to be connected to another IP network It is then neccessary to state the BBMD addre...

Страница 8: ...r is turned on the unit will beep once The upgrade procedure has now started 7 Wait between 30 and 60 seconds and the unit will beep again The procedure is now finished and the E BACNET2 V unit has be...

Страница 9: ...Appendix I...

Страница 10: ...a No Cor_EAFPressure Analog Input 7 Current pressure extract air Pa No Cor_DeIcingTemp Analog Input 8 De icing temperature C No Cor_FrostprotectionTemp Analog Input 9 Frost protection temperature C No...

Страница 11: ...t signal No Cor_HumidityPID_Output Analog Input 39 Humidity controller output signal No Analog Values Object name Object ID Description Unit Adjustable Cor_SupplySetpoint Analog Value 0 Supply air set...

Страница 12: ...igh supply air temperature C Yes Cor_EfficiencyLowLimit Analog Value 26 Alarm low efficiency Yes Cor_FrostLimit Analog Value 27 Alarm limit frost protection C Yes Cor_RoomHighLimit Analog Value 28 Ala...

Страница 13: ...ormal active No Cor_ExtendedRunActiveHalf Binary Input 16 Extended running reduced active No Cor_DeIcingActive Binary Input 17 De icing function active No Cor_RecycleRunActive Binary Input 18 Recircul...

Страница 14: ...in manual mode No Cor_AlaPt_39 Binary Input 57 EAF in manual mode No Cor_AlaPt_40 Binary Input 58 Frequency converter EAF in manual mode No Cor_AlaPt_41 Binary Input 59 Heating battery in manual mode...

Страница 15: ...converter SAF No Cor_AlaPt_80 Binary Input 88 Communication error frequency converter EAF No Cor_AlaPt_81 Binary Input 89 Communication error expansion unit 1 No Cor_AlaPt_82 Binary Input 90 Communica...

Страница 16: ...ort control cooling 9 CO2 control 10 Free cooling 11 Full speed stop 12 Fan stop No Multistate Values Object name Object ID Description Unit Adjustable Cor_AirUnitAutoMode Multistate Value 0 Manual se...

Страница 17: ...Box 116 S 428 22 K llered Sweden AB Regin Head office Phone 46 31 720 02 00 Fax 46 31 720 02 50 info regin se www regin se R E G I N T H E C H A L L E N G E R I N B U I L D I N G A U T O M A T I O N...