3032D AUG 

15

DMD-C

Box 116   428 22  KÅLLERED    SWEDEN

Tel +46 (0)31 720 02 00  Fax +46 (0)31 720 02 50

INSTRUCTIONS

  

INSTRUCTIONS

  

!

IMPORTANT: Read these in-

structions before installation and 

wiring of the product.

Pressure transmitter with display 

and built-in PID controller

DMD-C is a micro processor based differential pressure transmitter 

intended for clean, neutral gases.

The working range is settable 0...100, 0...300, 0...500 or 0...999Pa. 

It has signals for pressure indication 0...10V DC and 4...20 mA 

which are automatically scaled to be proportional to the  set pres-

sure range.

DMD-C also contains a pressure controller with settable PID control 

and a 0...10 V DC output signal.

Installation

Remove the front cover. Mount the DMD-C on a steady, non-vibra-

ting surface. The unit should preferably be mounted vertically with 

the pressure connections pointing downwards. Use the two screw 

pockets located in the lower part of the unit.

Wiring

Wire the unit according to the wiring diagram.

For DC-supply connect teminal 1 to + and teminal 2 to -.

The earthing terminal should be connected since several protection 

functions are decoupled to this terminal.

The pressure signals are automatically scaled to the set working 

range. Both signals may be used simultaneously.

Startup and settings

All settings are done using the three buttons on the PC-board.  

Two of the buttons (

Up, Down

) are used to move up and down 

through the setting alternatives. 

The third button (

Enter

) is used to choose the displayed alternative. 

If the buttons are left untouched for longer than 10 seconds the unit 

automatically returns to running mode.

Settings

Press 

Enter 

and the display will show -01.

Press 

Up

 until the display shows the parameter you wish to change.

Press 

Enter 

and the display will show the set value for the parame-

ter. The display will alternate between showing the value and the 

menu number.

To change the value, press 

Up 

or 

Down

 until the desired value is 

displayed. Press 

Enter

 to acknowlege and save the choice. The unit 

will automatically return to normal running mode and the present 

pressure will be displayed.

Menus

Pressure range  -01 

0...100 / 300 / 500 / 999 Pa

Setpoint 

-02 

0...max of set pressure range

Damping 

-03 

0...20 seconds. 

P-band 

-04 

0...300% of the set pressure range

I-time 

-05 

0...999 seconds

D-factor 

-06 0...999

Zero-point adj.  -08 

Press 

Enter

 to make zero-point adjust-

ment

Always start by setting the working range and doing a zero-point 

adjustment . 

The zero-point adjustment should be done before connecting the 

pressure hoses.

Press 

Enter 

and the display will show -01.

Press 

Up

 until the display shows -08.

Press 

Enter 

and the display will show 000.

Damping is used If the pressure signal is experienced as being 

too unstable .The DMD-C then does a continuous mean-value 

calculation over the set damping time and uses the calculated 

value as output signal and display value.
I-time = 0 means that the integration function is shut off.

Technical data

Supply voltage 

24 V AC/DC ±15%.

Power consumption 

5 VA

Ambient temperature 

0...50°C

Humidity 

90% RH maximum

Protection class 

IP54

Pressure ranges 

0...100, 0...300, 0...500, 0...999 Pa

Maximum overpressure 

20 kPa

Material:  Pressure housing  Poly carbonate

 

Membrane 

Silicone rubber

Pressure signals 

0...10 V DC and 4...20 mA for full 

set range

Controller signal 

0...10 V DC

Load impedance 

>2 kOhms for 0...10 V DC outputs

 

<500 Ohms for 4...20 mA output

Display 

3 digit LED. Shows pressure in Pa

Accuracy 

Better than ±1% of full scale for 

the set range

EMC emission and immunity standards

This product conforms with the requirements of European EMC 

standards CENELEC EN 61000-6-1 and EN 61000-1-3 and car-

ries the CE mark.

1   24 V AC/DC

2   24 V AC/DC system neutral

3   Signal neutral

4   Pressure signal 0...10 V DC

5   Pressure signal 4...20 mA

6   Controller output 0...10 V DC

7   Not connected

8   Not connected

9   Protective earth

Содержание DMD-C

Страница 1: ...ayen visar önskad meny Tryck på Enter och displayen visar aktuellt inställningsvärde Visningen växlar mellan värdet och menynummer För att ändra tryck på knapp Up eller Down tills önskat inställnings värde visas Tryck på Enter igen för att bekräfta inställningen som då sparas i minnet Därefter återgår displayvisningen automatiskt till driftläge och visar aktuellt tryck Trycktransmitter med display...

Страница 2: ...ll alternate between showing the value and the menu number To change the value press Up or Down until the desired value is displayed Press Enter to acknowlege and save the choice The unit will automatically return to normal running mode and the present pressure will be displayed Menus Pressure range 01 0 100 300 500 999 Pa Setpoint 02 0 max of set pressure range Damping 03 0 20 seconds P band 04 0...

Страница 3: ...ur le paramètre L affichage alterne entre la valeur et le numéro du menu Pour changer la valeur appuyez sur Up ou Down jusqu à ce que la valeur souhaitée soit affichée Appuyez sur Enter pour accepter et sauvegarder L unité reviendra au mode de fonctionnement normal et la pression actuelle sera affichée Menus Pressure range 01 0 100 300 500 999 Pa Setpoint 02 0 max de la plage de mesure reglée Damp...

Страница 4: ...d der für diesen Parameter eingestellt Wert angezeigt Dabei werden im Display abwechselnd Wert oder Menünummer angezeigt Drücken Sie zum Ändern des Werts auf Up oder Down bis der ge wünschte Wert angezeigt wird Drücken Sie auf Enter um die Auswahl zu bestätigen und zu speichern Das Gerät schaltet dann automatisch in den normalen Betriebsmodus zurück und der aktuelle Druck wird angezeigt Menüs Druc...

Отзывы: