Regency Horizon™ HZ42STEPV Gas Fireplace
19
INSTALLATION
Horizontal (Feet)
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
Restrictor Setting
#3 - 1-3/4” open
Restrictor Setting
#1 - 0.75” open
Restrictor Setting
#2 - 1-1/4” open
-2
-4
-6
V
ertical
(Feet)
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
0
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
42
44
46
48
50
52
-7 ft. max
Maximum total vent length = 50' + six - 90° elbows.
One 90° elbow = two 45° elbows.
Maximum total negative vent length = 10' (from centerline of pipe).
Restrictor setting 1 - Max. up to six- 90° elbows.
Restrictor setting 2 - Max. up to five- 90° elbows.
Restrictor setting 3 - Max. up to four- 90° elbows.
Note:
Must be terminated horizontally. Vertical terminations are not permitted.
The gas power vent systems is designed to allow the installation of a gas appliance when typical vent confi gurations (shown in this manual) are not
possible.
Note:
Must be terminated horizontally. Vertical terminations are not permitted.
VENTING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS
(RIGID PIPE 4" X 6-5/8" - MUST USE RIGID PIPE ADAPTOR #510-994)