24
Regency GF900L-1 Gas Fireplace
installation
DIRECT FLUE ZERO CLEARANCE TOP EXIT VERTICAL FLUE KIT
INSTALLATION INSTRUCTIONS GF900
This flue kit has been manufactured for use with GF900L and to be installed
in accordance with AS/NZS 5601-2013. To ensure safety and correct unit
operation this flue kit must be installed as outlined in these instructions. Heater
and flue clearances from combustible materials must be in accordance with
these instructions and AS/NZS 5601-2013.
1.
Locate the heater in its proposed position and mark the point for penetra-
tion directly above the centre of the heater flue outlet. Check the heater
location allows the outer flue to clear all structural timber and combustible
surfaces as per the manual.
2.
If the enclosure consists of a ceiling – cut a 255mm square hole (minimum)
for the flue to penetrate, cut hole through roofing material and prepare
flashing for termination.
3
. Starting at the heater, install first length of inner pipe, crimped end down,
using Mill-Pac sealant and self-tapping screws (or rivets). Note – first
length of inner pipe has a swage only.
4.
Continue assembling flue pipes inner and outer, ensuring each inner
join is sealed using Mill-Pac sealant and self-tapping screws (or rivets).
Outer flue pipe is to be installed with crimped end up then sealed and
fixed together also.
5.
If required, fix outer flue in the ceiling space using non-combustible brac-
ing to stop movement. On penetration of roof, fit an appropriate flashing
or weather seal to suit the roofing material, ensure all joints outside are
sealed with appropriate sealer.
6
. Fit gas cowl (46DVA-VCH/9) or flomet cap (946-651) ensuring inner and
outer flue pipes are sealed.
7.
Start heater and run for at least 15 minutes to check flue seal. If operational
issues are noted, check flue again to ensure proper seal of inner pipe.
SUPPLIED
Mill-Pac SEALANT MUST BE USED OR WARRANTY WILL BE
VOID
– IF REQUIRED, MORE SEALANT CAN BE PURCHASED USING
PART NUMBER 948-128
Gas cowl part number 46DVA-VCH/9 or Flomet cap part number (946-651)
(GF900Lonly).
SCREWS SUPPLIED FOR INNER FLUE CONNECTION
45º bends (if required) part number 946-648 –
Note
: if bends are used at
the start of flue run, a deeper crimp may be required at the unit for inner
pipe fitment. Can be crimped on site and sealed with Mill-Pac sealant and
self- tapping screws (or rivets).
Note
– It is the installers responsibility to ensure the installation complies
with AS/NZS 5601-2013 and all local and building codes.
NOTE:
USE A MINIMUM OF 3 SCREWS
EQUIDISTANT TO SECURE EVERY
INNER FLUE PIPE JOINT AS WELL
AS MILL-PAC SEALANT
Mill-Pac SEALANT
INNER FLUE
Screws
1st Length Inner Flue
has Deep Crimp
and is marked (crimp down)
Outer Heat Shield
174mm dia x 900mm x 4
100mm dia x 900mm x 4
If required 45° Heat Shield and
Inner
Install with pop rivets or self tapping screws
and seal with Milpac
OR
Duravent Gas Cowl
46DVA-VCH/9+
Adaptor 946-725 (Not Shown)
GF900L Flomet Cap
Part Number: 946-651
Inner Flue